Terminal block description for Monitoring system EKO-KE8
Terminal 1: L/phase 230 V
Terminal 2: N/neutral 230 V
Terminal 3: PE
Terminal 4: Buzzer alarm 1/fan output*
Terminal 5: Buzzer alarm 1/fan output*
Terminal 6: Buzzer alarm 2/alarm output**
Terminal 7: Buzzer alarm 2/alarm output**
Terminal 8: Buzzer alarm 3/service output***
Terminal 9: Buzzer alarm 3/service output***
Terminal 10: Smoke detector loop (-)
Terminal 11: Smoke detector loop (+)
1 2 3 4 5 6 7 8 9 10 1112131415 16 .. .. 47
TRIG IN
* Breaks upon power outage, function text,
error and alarm
** Breaks upon power outage and alarm
*** Breaks upon power outage and error
Terminal 12: External alarm input 1
Terminal 13: External alarm input 1
Terminal 14: External alarm input 2/Night closing
Terminal 15: External alarm input 2/Night closing
Terminal 16, 20, 24, 28, 32, 36, 40, 44:
Actuator feed 1, AC 24 V
Terminal 17, 21, 25, 29, 33, 37, 41, 45
Actuator feed 2, +S1, +S4, AC 24 V
Terminal 18, 22, 26, 30, 34, 38, 42, 46
Signal contact S2
Terminal 19, 23, 27, 31, 35, 39, 43, 47:
Signal contact S6
Trigg in: External timer
No Function ON OFF Terminal Description
1 Smoke detector Connected Disconnected 10-11 Detects if detector is present even if it is not
selected. In such case, ashes red and yellow
even during startup.
2 Night closing Connected Disconnected 14-15 Alarm input 2. If night closing is not selected, no
jumper is required at the input. If night closing
is activated, both red and yellow light. Concluded
with a manoeuvring operation.
3 Post-cooling Connected Disconnected 4-5 Releases buzzer alarm 1 seven minutes before
manoeuvring. Manoeuvring with button has no
post-cooling.
4 External
trigger input
Connected Disconnected J10 A jumper is not necessary at the input if it is not
used. If post-cooling is selected, it will be used.
5 Extra long closing
and opening time
Connected Disconnected 16-31 60 sec. closing time instead of the normal 30 sec.
400 sec closing time instead of the normal 200 sec.
6 Auto-reset of
external alarm
Connected Disconnected 12-13 Option to automatically or manually reset
external re alarm.
7 External re alarm Connected Disconnected 12-13 Option to connect existing re alarm.
8 Function test Connected Disconnected 4-5 When activated (on) alarm 1 does not break
during function test
DIP switch functions
(Located under the front panel)
ON = Pressed on top edge
OFF = Pressed on bottom edge