manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Electrex
  6. •
  7. Protection Device
  8. •
  9. Electrex Atto RCM D4 ECT User manual

Electrex Atto RCM D4 ECT User manual

INSTALLATION GUIDE
!
COPYRIGHT
Electrex is a trademark of Akse S.r.l. All rights reserved.
It is forbidden to duplicate, adapt, transcript this document without Akse written
authorization, except when regulated accordingly by the Copyright Laws.
WARRANTY
This product is covered by a warranty against material and manufacturing defects for a 24
months period from the manufacturing date.
The warranty does not cover the defects that are due to:
• Negligent and improper use
• Failures caused by atmospheric hazards
• Acts of vandalism
• Wear out of materials
• Firmware upgrades
Akse reserves the right, at its discretion, to repair or substitute the faulty products
The warranty is not applicable to the products that will result defective in consequence o
f
a negligent and improper use or an operating procedure not contemplated in this manual.
RETURN AND REPAIR FORMALITIES
Akse accepts the return of instruments for repair only when authorized in advance. Th
e
transport costs are at customer charge.
RE-SHIPPING OF REPAIRED PRODUCT
The terms for re-shipment of repaired products are ex-works, i.e. the transport costs ar
e
at customer charge.
Products returned as detective but found to be perfectly working by our laboratories, will
be charged a fl at fee to account for checking and testing time irrespective of the warrant
y
terms.
SAFETY
This instrument was manufactured and tested in compliance with IEC 61010-1 CAT III
-
300V class 2 standards for operating voltages up to 300 VAC rms phase to neutral.
In order to maintain this condition and to ensure safe operation, the user must comply with
the indications and markings contained in the following instructions:
• When the instrument is received, before starting its installation, check that it i
s
intact and no damage occurred during transport.
• Before mounting, ensure that the instrument operating voltages and the main
s
voltage are compatible then proceed with the installation.
• The instrument power supply needs no earth connection.
• The instrument is not equipped with a power supply fuse; a suitable external
protection fuse must be foreseen by the contractor.
• Maintenance and/or repair must be carried out only by qualifi ed, authorized
personnel
• If there is ever the suspicion that safe operation is no longer possible, the instrumen
t
must be taken out of service and precautions taken against its accidental use.
Operation is no longer safe when:
•There is clearly visible damaged.
•The instrument no longer functions.
•After lengthy storage in unfavorable conditions.
• After serious damage occurred during transport
The instruments must be installed in respect of all the local regulations.
OPERATOR SAFETY
Warning: Failure to observe the following instructions may lead to a serious danger o
f
death.
• During normal operation dangerous voltages can occur on instrument terminals and
on voltage and current transformers. Energized voltage and current transformer
s
may generate lethal voltages. Follow carefully the standard safety precautions whil
e
carrying out any installation or service operation.
• The terminals of the instrument must not be accessible by the user after the installation.
The user should only be allowed to access the instrument front panel where th
e
display is located.
• Do not use the digital outputs for protection functions nor for power limitation functions.
The instrument is suitable only for secondary protection functions.
• The instrument must be protected by a breaking device capable of interrupting both
the power supply and the measurement terminals. It must be easily reachable by th
e
operator and well identifi ed as instrument cut-off device.
• The instrument and its connections must be carefully protected against short-circuit.
Precautions: Failure to respect the following instructions may irreversibly damage to th
e
instrument.
• The outputs and the options operate at low voltage level; they cannot be powered b
y
any unspecifi ed external voltage.
• The application of currents not compatible with the current inputs levels will damag
e
to the instrument.
Further documentation may be downloaded from our web site www.electrex.it.
This document is owned by company AKSE that reserves all rights.
DECLARATION OF CONFORMITY
Akse hereby declares that its range of products complies with the following directives EM
C
2014/30/EU, 2014/35/EU and complies with the following product’s standard CEI EN
61326 - Ed. 2.0 (2012) – IEC 61326 - Ed. 2.0 (2012), CEI EN 61010- Ed. 3 (2010) – IE
C
61010- Ed. 3 (2010). The product has been tested in the typical wiring confi guration and
with peripherals conforming to the EMC directive and the LV directive.
Atto RCM D4 ECT
MODELS
PFA74D1-D2-B ATTO RCM D4 ECT RS485 230÷240V 2DI 2DO
4COMMON TRANSDUCER / ANALYZER
2
1
LED
LED description:
LED (1) A green LED pulses indicating the operation of the instrument
LED (2) Two LEDs pulsate indicating the communication activity of the RS485 port (red
TX LED, green RX LED)
MECHANICAL CHARACTERISTICS
Case Self-extinguishing plastic material class V0
Protection degree IP40 on front panel
Size 70 x 90 x 58 mm (4 DIN modules)
VOLTAGE INPUTS
Direct Up to 300 Vrms phase-neutral
or 519 Vrms phase to phase
Overload: 900 Vrms phase to phase for 1 sec
Power supply 230/240Vac +/- 10% 50/60Hz
Self consumption < 2,5VA
SETUP SEQUENCE
PARAMETERS VALUES AVAILABLE DEFAULT
DIGITAL OUT 1
POLARITY (note A) N.O.,N.C. N.O.
DIGITAL OUT 2 (see DIGITAL OUT 1)
INPUTS - OUTPUTS
OUTPUTS INPUTS
10 C1 Common 1 (negative) 19 C2 Common 2 (negative)
11 O1 Diff erential intervention 20 I2 Function test
12 C2 Common 2 (negative) 21 C1 Common 1 (negative)
13 O2 Pre-alarm intervention 22 I1 Diff erential intervention reset
OUTPUTS INPUTS
Maximum applicable voltage: 27 Vdc Supply voltage (external): from 10 to 30
Vdc
Maximum switchable current: 27mA Current consumption: from 2 to
10mA
Max. count frequency 10 or 100Hz
N.B. Digital outputs (Optocoupled NPN transistor
type for DIN 43864).
N.B. For gas meters a galvanic separation is
needed per ATEX standards
101112
1920
AUX
AUX
13
2122
NO
C
NC
NO
C
NC
R
e
l
a
y
R
e
l
a
y
230 V~
24V =
N L
- +
NOTE: A
N.O. Normally open
N.C. Normally closed
TABLE n.1 - Eg. Modbus registers reading parameters, for the complete list refer to
the instrument’s protocol)
INPUT REGISTERS
REGISTER DESCRIPTION TYPE UNIT
30219 Frequency of U1N (f) Float IEEE754 [Hz]
30221 Phase to Neutral Voltage, RMS Amplitude (U1N) Float IEEE754 [V]
30223 Phase to Neutral Voltage, RMS Amplitude (U2N) Float IEEE754 [V]
30225 Phase to Neutral Voltage, RMS Amplitude (U3N) Float IEEE754 [V]
30233 Phase Current, RMS Amplitude (I1) Float IEEE754 [A]
30235 Phase Current, RMS Amplitude (I2) Float IEEE754 [A]
30237 Phase Current, RMS Amplitude (I3) Float IEEE754 [A]
SETUP SEQUENCE
PARAMETERS VALUES AVAILABLE DEFAULT
RS-485
ADDR (485 address) 1 ... 247 27
COM (Baud rate) 2400, 4800, 9600, 19200, 38400 38400
COM (Data Bit) 7 or 8 8
COM (Parity) N = no parity, E = even parity,
O = odd parity N
COM (Stop bit) 1 or 2 2
S.T. (Silent Time) 0 ... 1000 mS (Step of 10) 100
NETWORK
IMAX 5 ... 16 A / 5 ... 16 mA 5/.005
CUTOFF (Current) 0 ... 16 0
DIFFERENTIAL
RCD ENABLING CH 1, 2, 3 CH 1
INTERVENTION
THRESHOLD 0 ... X mA 30 mA
PRE-ALARM THRESHOLD 0 ... X mA 30 mA
INTERVENTION TIME 0 ... 5000 mS 0
PRE-ALARM TIME 0 ... 5000 mS 0
PRE-ALARM HYSTERESIS 0 ... 100 % 5 %
TABLE n.2 (Eg. Modbus registers writing parameters, for the complete list refer to
the instrument’s protocol).
HOLDING REGISTERS
REGISTER DESCRIPTION TYPE
41001 RCD status:
Bit 0 = CH 1 intervention
Bit 1 = CH 2 intervention
Bit 2 = CH 3 intervention
Bit 4 = CH 1 pre-alarm
Bit 5 = CH 2 pre-alarm
Bit 6 = CH 3 pre-alarm
Integer
41002 RCD enabling:
Bit 0 = Channel 1 (default)
Bit 1 = Channel 2
Bit 2 = Channel 3
Integer
41003 RCD tripping threshold (mA) Integer
41004 RCD tripping time (ms) Integer
41005 RCD pre-alarm threshold (mA) Integer
41006 RCD pre-alarm time (ms) Integer
41007 Pre-alarm hysteresis Integer
The instrument is equipped with a separate power supply. The power supply terminals
are numbered (17) and (18). Use cables with max cross-section of 2,5 mm2 if stranded,
4 mm2 if rigid.
POWER SUPPLY
17 18 1920U1 U2 U3 N
AUXVOLTAGE INPUT POWER
2122
1
2
SERIAL LINE CONNECTION
S1 S2 S1 S2 S1 S2 A B
T
101112
I1 I2 I3 RS-485 AUX
13
POWER SUPPLY
1 230/240Vac +/- 10% 50/60Hz
2 F: 500 mA T
Max cable length: 1000 meters.
RS485
Address 27
Baud rate 38400
Parity None
Bit of Stop 2
3P3W
3P4W1P2W
2P2W
CURRENT CONNECTION
Use only the CT’s provided with the instrument. Connect the CT outputs to the terminals
marked I1, I2, I3 according to the applicable diagrams that follow. Each input corresponds
to a diff erential channel.
S1 S2 S1 S2 S1 S2
CH1 CH2 CH3
L1
L2
1P2W
2P2W / 3P3W-B
Use cables with max cross-section of 2,5 mm2 if stranded, 4 mm2 if rigid and connect them
to the terminals marked VOLTAGE INPUT on the instrument according to the applicable
diagrams that follow.
VOLTAGE CONNECTION
U1 U2 U3 N
VOLTAGE INPUT
L
N
U1 U2 U3 N
VOLTAGE INPUT
L1
L2
L3
N
U1 U2 U3 N
VOLTAGE INPUT
L1
L2
L3
U1 U2 U3 N
VOLTAGE INPUT
L1
L2
L3
N
U1 U2 U3 N
VOLTAGE INPUT
L
N
3P4W / 3P4W-B-3U / 3I
3P3W / 3P3W-B-3U
3I
3P4W-B
U1 U2 U3 N
VOLTAGE INPUT
L1
N
L2
L3
3CH
EXAMPLE CONNECTION OF 3 DIFFERENTIAL CHANNELS
L1
L2
L3
N
S1 S2 S1 S2 S1 S2
CH1 CH2 CH3
L1
N
L1
L2
L3
The instrument can measure up to 3 specifi c diff erential channels at the same time. Enable
the corresponding RCD channels according to the wiring used.
S1 S2 S1 S2 S1 S2
CH1 CH2 CH3
L1
N
S1 S2 S1 S2 S1 S2
CH1 CH2 CH3
L1
L2
L3
N
S1 S2 S1 S2 S1 S2
CH1 CH2 CH3
L1
L2
L3
akse srl Via Aldo Moro, 39 42124 Reggio Emilia Italy
Tel. +39 0522 924 244 Fax +39 0522 924 245 [email protected] www.akse.it
P.I. 01544980350 R.E.A. 194296 Cap. Soc. Euro 85.800,00 i.v.
Subject to modifi cation without notice.
Edition 2020 09 03 ENG0351
Made
in Italy
Pensato, progettato e prodotto in Italia
Engineered and manufactured in Italy

Other Electrex Protection Device manuals

Electrex Rexcon Die Sentry User manual

Electrex

Electrex Rexcon Die Sentry User manual

Electrex PLUS User manual

Electrex

Electrex PLUS User manual

Popular Protection Device manuals by other brands

GE D60 instruction manual

GE

GE D60 instruction manual

Curve TRINITI HIGHWAY CASS S4 Product Description Assembly Manual

Curve

Curve TRINITI HIGHWAY CASS S4 Product Description Assembly Manual

Acrel ARD2M operating manual

Acrel

Acrel ARD2M operating manual

tepro 8532 quick start guide

tepro

tepro 8532 quick start guide

Honeywell 1101 manual

Honeywell

Honeywell 1101 manual

Mustang Survival MD1270 owner's manual

Mustang Survival

Mustang Survival MD1270 owner's manual

Thytronic XMR-T manual

Thytronic

Thytronic XMR-T manual

ensto Arcteq AQ-F205 instruction manual

ensto

ensto Arcteq AQ-F205 instruction manual

XTline XT90119 Original instruction manual

XTline

XTline XT90119 Original instruction manual

Würth FMB 26 Instructions for use

Würth

Würth FMB 26 Instructions for use

Silverstein OmniGuard user manual

Silverstein

Silverstein OmniGuard user manual

Siemens 5SD7411-2 operating instructions

Siemens

Siemens 5SD7411-2 operating instructions

STI Euro Stopper STI-15000 Series quick start guide

STI

STI Euro Stopper STI-15000 Series quick start guide

Datalogic SLIM instruction manual

Datalogic

Datalogic SLIM instruction manual

ESPE JGGD001 instruction manual

ESPE

ESPE JGGD001 instruction manual

Furse ESP Cat-5 Series Technical note

Furse

Furse ESP Cat-5 Series Technical note

Ilsco SSI SpecPRO CSM Series manual

Ilsco

Ilsco SSI SpecPRO CSM Series manual

Creative Conners Safety Interlock Pro manual

Creative Conners

Creative Conners Safety Interlock Pro manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.