1.0 INTRODUCTION
Many applications require the accurate measurement and control of relative humidity at a
defined set point below ambient for long-term applications in a seal environment. The Model
5112 Dehumidifier Controller is specifically designed to meet these requirements and can
be used to control dehumidification in virtually any type of sealed chamber. The controlled
115/230 VAC, 3 Amp output is able to control dehumidification systems that operate within
the limits of the controller's power handling capacity.
The Model 5112 is capable of is capable of measuring relative humidity over the entire 0 to
100% range. The standard sensor supplied with the Controller has a response time
satisfactory for maintaining long-term humidity stability. For applications requiring a fast
recovery time the optional ETS Model 554 Humidity Sensor should be used.
The Controller is designed to work in conjunction with ETS Desiccant/Pump
Dehumidification Systems (Models 5461, 5471 & 5478) and the Model 5465 Dry Gas
Dehumidification System (AC Solenoid valve controls the flow of dry gas). It may also be
used with other dehumidification systems that operate within the Model 5112 operating
parameters (2 Amps).
Any drying system can be used to control the humidity in virtually any sealed environment.
However, it should be noted that the larger the chamber, the greater the variation in relative
humidity throughout the chamber from the sensor reading. Good air circulation in the
chamber is critical to maintaining a uniform humidity level throughout the controlled
environment.
2.0 DESCRIPTION
The Model 5112 Dehumidifier Controller consists of two (2) basic components: a Humidity
Sensor and a Control Unit.
2.1 Humidity Sensor
The standard Humidity Sensor is an integrated unit measuring approximately
1”lx.438”wx.375”d that plugs into a 18” multi-conductor cable that is hard-wired to the
Control unit. Longer cable lengths are available as an option. A temperature
compensated capacitive sensing element where capacitance is proportional to
humidity is used to detect the relative humidity level. This type of sensor can
measure over the entire range of 0 to 100% R.H. with accuracy better than ±2% R.H
at a temperature of 20-40°C. The sensor has a slew rate (response time) of 0.35%
R.H./sec.
The sensor can be mounted to the wall of the chamber using an adhesive backed
clamp or Velcro or through a ½” NPT compression fitting inserted in the chamber
wall. Other mounting configurations can also be used to meet the user’s specific
requirement.