Technical Specification
Safety and environmental conditions
LV directive 2014/35/EC
RoHS directive 2011/65/EU
WEEE directive 2012/19/EU
This product is designed to be safe under the following
conditions:
Specification
Environmental conditions
Operating temperature:
Relative humidity:
Protection degree:
Installation class:
Pollution degree:
-5°C - +55°C
5% - 85%, non condensing
IP23
|| (double insulation)
2
Application conditions
Umax:
InA:
Frequency:
Fuse:
Strain relief:
Maximum wire cross section
and torque :
Diameter ø (mm)
Height (mm)
400V
63A (mantle terminals)
50Hz
2 or 3x D01 (E14), max 16A
Yes, maximum 2 ground cables
23mm and 2 light poles cords
Terminal N, 1, 2, 3: 2x 16mm2, 2-
4Nm
Terminal 4, 5, 6, 7: 2.5mm2 1-2Nm*
84
279,5
Storage
Temperature:
Relative humidity:
-20°C - +70°C
5% - 85%, non condensing
* Multi-wire flexible conductors must be assembled in ring-tongues,
ferrules or wire pins.
Specification per type
Please be aware, product liability, standards and warranty are all
expired when modifications on the product are made.
ELEQ reserves the right to carry out modifications on its products, in
order to improve them, without prior notice.
Safety instruction
All activities for installation, commissioning and maintenance of
this connection box must be performed by qualified personnel
that has the knowledge of applicable safety precautions. This
guide assumes that the reader of this document has sufficient
electro-technical knowledge to understand the content of this
document.
General
The LS-84 is a connection box for public lighting and intended
to be used in lighting poles. The connection box should be
mounted in a weather protected and dry location. In the
connection box the incoming (ground) cable can be connected.
If desired, looped circuits wiring to the next lighting pole is
possible. The cable of the armature should be connected on
the outgoing terminals.
Fuses protect the installation against overload and short-
circuiting.
Explanation of symbols
This product is designed according to the
EN-IEC 61439-2:2011 standards and meets the
requirements of theLow Voltage Directive 2014/35/EC.
Read the installation guide before mounting the
product. Unprofessional work activities on electrical
installations may result in a threat of danger to the life
and health of human beings and livestock!
RoHS Directive 2014/35/EC
ELEQ states that it uses qualified components in its
products only from manufacturers which meet the
requirements of the European Directive for the
"Restriction of use of certain Hazardous Substances
WEEE Directive 2012/19/EU
This equipment should not be disposed as unsorted
municipal waste. Contact a qualified recycler for
disposal.
LS-84 Connection Box for
Public Lighting
Installation Guide
5L4162
LS-84 5L4162
5L4163
Read this installation guide before installing the product