ELEQ UAK Series User manual

83923 / EN2212
Technical Specifications
Safety and environmental conditions
CE marking
LV directive 2014/35/EU
RoHS directive (EU) 2015/863
Standard
EN 61010:2010/A1:2019*
EN 60947-7-3-2009**
WEEE directive 2012/19/EU
* Maximum temperature of the busbar: 120ºC (Sum of the busbar temperature rise and the
ambient temperature)
** Only applicable to article number 500040
The UAK is only suitable for busbar. This product is designed
to be safe under the following conditions:
Specifications
Environmental conditions
Standard:
Class:
Operating temperature:
Relative humidity:
Operating height:
Protection degree:
Pollution degree:
Measurement category:
IEC 60721-3-3:1996
3K3
+5°C - +40°C
5% - 85%, non condensing
0..2000m over NN
IP20
2
CAT III
Application conditions
Primary:
Umax:
Test voltage:
Impulse voltage:
Imax:
Voltage drop:
Fuse (UAK4Z):
Secondary lead:
Torque:
Busbar
690Vac
3kV / 50Hz
6kV 1,2 / 50µs
2A
<500mVac
5x25mm (with indicator)
10A SIBA DIN41576-2
1mm² flexible, 50cm, end-sleeve
1.5 –2.0Nm
Storage
Temperature:
Relative humidity:
Material:
-20°C - +70°C
5% - 85%, non condensing
PA 6.6, UL94 V2
Specifications per type
UAK4Z
UAK16
UAK16N
With fuse
Yes
No
No
Weight (gr)
160
160
160
Connection
1,5-4mm2
0,1-16mm2
0,1-16mm2
Colour
Black
Black
Blue
ELEQ reserves the right to carry out modifications on its products, in
order to improve them, without prior notice.
Safety instruction
All activities for installation, commissioning and maintenance
of this voltage tap must be performed by qualified personnel
that have the knowledge of applicable safety precautions.
This guide assumes that the reader of this document has
sufficient electro-technical knowledge to understand the
content of this document.
General
The UAK is a voltage tap for busbar and can only be used
measuring electrical voltages. The UAK is suitable for
measurement purposes only. The UAK should be mounted on
the primary conductors in a weather protected and dry
location.
Explanation of symbols
This product is designed according to the
EN-IEC 61010-1:2010 standards and therefore this
product meets the requirements of the Low Voltage
Directive 2014/35/EU.
Read the installation guide before mounting the
product. Unprofessional work activities on electrical
installations may result in a threat of danger to the life
and health of human beings and livestock!
RoHS Directive (EU) 2015/863
ELEQ states that they only uses qualified component
in their products from manufacturers, whose
specifications meet or exceed the requirements of
the European Directive for the Restriction of use of
certain Hazardous Substances.
WEEE Directive 2012/19/EU
The 'crossed out wheeled bin' symbol indicates that
the equipment should not be disposed as unsorted
municipal waste. Contact a qualified recycler for
disposal.
UAK (Fused) Voltage Tap
Installation Guide
UAK4Z (Fused phase, 500040)
UAK16 (Phase, 500041)
UAK16N (Neutral, 500042)
Read this installation guide before installing the product
83923 / EN2212
Technical Specifications
Safety and environmental conditions
CE marking
LV directive 2014/35/EU
RoHS directive (EU) 2015/863
Standard
EN 61010:2010/A1:2019*
EN 60947-7-3-2009**
WEEE directive 2012/19/EU
* Maximum temperature of the busbar: 120ºC (Sum of the busbar temperature rise and the
ambient temperature)
** Only applicable to article number 500040
The UAK is only suitable for busbar. This product is designed
to be safe under the following conditions:
Specifications
Environmental conditions
Standard:
Class:
Operating temperature:
Relative humidity:
Operating height:
Protection degree:
Pollution degree:
Measurement category:
IEC 60721-3-3:1996
3K3
+5°C - +40°C
5% - 85%, non condensing
0..2000m over NN
IP20
2
CAT III
Application conditions
Primary:
Umax:
Test voltage:
Impulse voltage:
Imax:
Voltage drop:
Fuse (UAK4Z):
Secondary lead:
Torque:
Busbar
690Vac
3kV / 50Hz
6kV 1,2 / 50µs
2A
<500mVac
5x25mm (with indicator)
10A SIBA DIN41576-2
1mm² flexible, 50cm, end-sleeve
1.5 –2.0Nm
Storage
Temperature:
Relative humidity:
Material:
-20°C - +70°C
5% - 85%, non condensing
PA 6.6, UL94 V2
Specifications per type
UAK4Z UAK16 UAK16N
With fuse Yes No No
Weight (gr)
160
160
160
Connection 1,5-4mm2 0,1-16mm20,1-16mm2
Colour Black Black Blue
ELEQ reserves the right to carry out modifications on its products, in
order to improve them, without prior notice.
Safety instruction
All activities for installation, commissioning and maintenance
of this voltage tap must be performed by qualified personnel
that have the knowledge of applicable safety precautions.
This guide assumes that the reader of this document has
sufficient electro-technical knowledge to understand the
content of this document.
General
The UAK is a voltage tap for busbar and can only be used
measuring electrical voltages. The UAK is suitable for
measurement purposes only. The UAK should be mounted on
the primary conductors in a weather protected and dry
location.
Explanation of symbols
This product is designed according to the
EN-IEC 61010-1:2010 standards and therefore this
product meets the requirements of the Low Voltage
Directive 2014/35/EU.
Read the installation guide before mounting the
product. Unprofessional work activities on electrical
installations may result in a threat of danger to the life
and health of human beings and livestock!
RoHS Directive (EU) 2015/863
ELEQ states that they only uses qualified component
in their products from manufacturers, whose
specifications meet or exceed the requirements of
the European Directive for the Restriction of use of
certain Hazardous Substances.
WEEE Directive 2012/19/EU
The 'crossed out wheeled bin' symbol indicates that
the equipment should not be disposed as unsorted
municipal waste. Contact a qualified recycler for
disposal.
UAK (Fused) Voltage Tap
Installation Guide
UAK4Z (Fused phase, 500040)
UAK16 (Phase, 500041)
UAK16N (Neutral, 500042)
Read this installation guide before installing the product
83923 / EN2212
Technical Specifications
Safety and environmental conditions
CE marking
LV directive 2014/35/EU
RoHS directive (EU) 2015/863
Standard
EN 61010:2010/A1:2019*
EN 60947-7-3-2009**
WEEE directive 2012/19/EU
* Maximum temperature of the busbar: 120ºC (Sum of the busbar temperature rise and the
ambient temperature)
** Only applicable to article number 500040
The UAK is only suitable for busbar. This product is designed
to be safe under the following conditions:
Specifications
Environmental conditions
Standard:
Class:
Operating temperature:
Relative humidity:
Operating height:
Protection degree:
Pollution degree:
Measurement category:
IEC 60721-3-3:1996
3K3
+5°C - +40°C
5% - 85%, non condensing
0..2000m over NN
IP20
2
CAT III
Application conditions
Primary:
Umax:
Test voltage:
Impulse voltage:
Imax:
Voltage drop:
Fuse (UAK4Z):
Secondary lead:
Torque:
Busbar
690Vac
3kV / 50Hz
6kV 1,2 / 50µs
2A
<500mVac
5x25mm (with indicator)
10A SIBA DIN41576-2
1mm² flexible, 50cm, end-sleeve
1.5 –2.0Nm
Storage
Temperature:
Relative humidity:
Material:
-20°C - +70°C
5% - 85%, non condensing
PA 6.6, UL94 V2
Specifications per type
UAK4Z
UAK16
UAK16N
With fuse
Yes
No
No
Weight (gr)
160
160
160
Connection
1,5-4mm2
0,1-16mm2
0,1-16mm2
Colour
Black
Black
Blue
ELEQ reserves the right to carry out modifications on its products, in
order to improve them, without prior notice.
Safety instruction
All activities for installation, commissioning and maintenance
of this voltage tap must be performed by qualified personnel
that have the knowledge of applicable safety precautions.
This guide assumes that the reader of this document has
sufficient electro-
technical knowledge to understand the
content of this document.
General
The UAK is a voltage tap for busbar and can only be used
measuring electrical voltages. The UAK
is suitable for
measurement purposes only. The UAK should be mounted on
the
primary conductors in a weather protected and dry
location.
Explanation of symbols
This product is designed according to the
EN-IEC 61010-1:2010 standards and therefore this
product meets the requirements of the Low Voltage
Directive 2014/35/EU.
Read the installation guide before mounting the
product. Unprofessional work activities on electrical
installations may result in a threat of danger to the life
and health of human beings and livestock!
RoHS Directive (EU) 2015/863
ELEQ states that they only uses qualified component
in their products from manufacturers, whose
specifications meet or exceed the requirements of
the European Directive for the Restriction of use of
certain Hazardous Substances.
WEEE Directive 2012/19/EU
The 'crossed out wheeled bin' symbol indicates that
the equipment should not be disposed as unsorted
municipal waste. Contact a qualified recycler for
disposal.
UAK (Fused) Voltage Tap
Installation Guide
UAK4Z (Fused phase, 500040)
UAK16 (Phase, 500041)
UAK16N (Neutral, 500042)
Read this installation guide before installing the product
83923 / EN2212
ELEQ b.v.
Tukseweg 130, 8331 LH Steenwijk, The Netherlands
ELEQ b.v.
Tukseweg 130, 8331 LH Steenwijk, The Netherlands
2014/35/EU.

Always avoid working on live parts of an installation.
Assembly black fused UAK
Attention
Remove the fuse during assembly of the UAK4Z.
1. Ensure a safe working area during assembly,
maintenance and inspection of the voltage tap. Disconnect
the power of the primary circuit and make sure it can not
be enabled unintentionally.
2. Mount the voltage tap around the busbar which should be
tapped by turning the lower part.
Attention
Please note, the screwhead of the UAK should be positioned
straight above the busbar when mounting.
3. Connect the secondary lead to the high impedance
voltage input of the measurement instrument (e.g., a
voltmeter or voltage input of kWh-meter).
4. Install the fuse.
5. Check if the easy voltage tap is mounted properly. Check
if the secondary lead is connected properly and firmly.
6. Mark the label of the UAK with year, month and number of
repeat installations.
7. Enable the primary circuit.
Assembly blue UAK
Attention
The UAK16N is only meant for assembly on a neutral.
1. Ensure a safe working area during assembly,
maintenance and inspection of the voltage tap. Disconnect
the power of the primary circuit and make sure it cannot
be enabled unintentionally.
2. Connect the secondary lead to the high impedance
voltage input of the measurement instrument (e.g., a
voltmeter or voltage input of kWh-meter).
3. Mount the voltage tap around the busbar which should be
tapped by turning the lower part.
4. Check if the voltage tap is mounted properly.
Check if the secondary lead is connected properly and
firmly.
5. Mark the label of the UAK with year, month and number of
repeat installations.
6. Enable the primary circuit.
Wiring Diagram
Maintenance and inspection
Check whether the secondary lead is connected firmly.
Check whether the easy voltage tap is mounted firmly.
Attention
Always avoid working on live parts of an installation.
Problem solving
e.g. unexpected values, incorrect values
Check the settings of the meter by using the installation
guide of the meter.
Check whether the voltage tap is mounted on the intended
cable.
Disassembly instruction
To disconnect the meter from the voltage tap, please consult
the installation guide of the meter.
1. Ensure a safe working area during disassembling the
voltage tap. Disconnect the power of the primary circuit
and make sure it cannot be enabled unintentionally.
2. UAK4Z: Remove the fuse and disconnect the
measurement device. As next step remove the UAK from
the connector.
UAK16 and UAK16N: Remove the UAK from the
connector and disconnect the measurement device.
3. Repair or replace the busbar after removal to ensure safe
isolation. Not repairing the busbar may result in an unsafe
situation.
4. Enable the primary circuit if is necessary.
Recycling
When the product has reached ‘end of life’, it must be
recycled. Do not dispose this product as unsorted municipal
waste. Contact a qualified recycler for disposal.
UAK4Z
UAK16(N)
Always avoid working on live parts of an installation.
Assembly black fused UAK
Attention
Remove the fuse during assembly of the UAK4Z.
1. Ensure a safe working area during assembly,
maintenance and inspection of the voltage tap. Disconnect
the power of the primary circuit and make sure it can not
be enabled unintentionally.
2. Mount the voltage tap around the busbar which should be
tapped by turning the lower part.
Attention
Please note, the screwhead of the UAK should be positioned
straight above the busbar when mounting.
3. Connect the secondary lead to the high impedance
voltage input of the measurement instrument (e.g., a
voltmeter or voltage input of kWh-meter).
4. Install the fuse.
5. Check if the easy voltage tap is mounted properly. Check
if the secondary lead is connected properly and firmly.
6. Mark the label of the UAK with year, month and number of
repeat installations.
7. Enable the primary circuit.
Assembly blue UAK
Attention
The UAK16N is only meant for assembly on a neutral.
1. Ensure a safe working area during assembly,
maintenance and inspection of the voltage tap. Disconnect
the power of the primary circuit and make sure it cannot
be enabled unintentionally.
2. Connect the secondary lead to the high impedance
voltage input of the measurement instrument (e.g., a
voltmeter or voltage input of kWh-meter).
3. Mount the voltage tap around the busbar which should be
tapped by turning the lower part.
4. Check if the voltage tap is mounted properly.
Check if the secondary lead is connected properly and
firmly.
5. Mark the label of the UAK with year, month and number of
repeat installations.
6. Enable the primary circuit.
Wiring Diagram
Maintenance and inspection
Check whether the secondary lead is connected firmly.
Check whether the easy voltage tap is mounted firmly.
Attention
Always avoid working on live parts of an installation.
Problem solving
e.g. unexpected values, incorrect values
Check the settings of the meter by using the installation
guide of the meter.
Check whether the voltage tap is mounted on the intended
cable.
Disassembly instruction
To disconnect the meter from the voltage tap, please consult
the installation guide of the meter.
1. Ensure a safe working area during disassembling the
voltage tap. Disconnect the power of the primary circuit
and make sure it cannot be enabled unintentionally.
2. UAK4Z: Remove the fuse and disconnect the
measurement device. As next step remove the UAK from
the connector.
UAK16 and UAK16N: Remove the UAK from the
connector and disconnect the measurement device.
3. Repair or replace the busbar after removal to ensure safe
isolation. Not repairing the busbar may result in an unsafe
situation.
4. Enable the primary circuit if is necessary.
Recycling
When the product has reached ‘end of life’, it must be
recycled. Do not dispose this product as unsorted municipal
waste. Contact a qualified recycler for disposal.
UAK4Z
UAK16(N)
Always avoid working on live parts of an installation.
Assembly black fused UAK
Attention
Remove the fuse during assembly of the UAK4Z.
1. Ensure a safe working area during assembly,
maintenance and inspection of the voltage tap. Disconnect
the power of the primary circuit and make sure it can not
be enabled unintentionally.
2. Mount the voltage tap around the busbar which should be
tapped by turning the lower part.
Attention
Please note, the screwhead of the UAK should be positioned
straight above the busbar when mounting.
3. Connect the secondary lead to the high impedance
voltage input of the measurement instrument (e.g., a
voltmeter or voltage input of kWh-meter).
4. Install the fuse.
5. Check if the easy voltage tap is mounted properly. Check
if the secondary lead is connected properly and firmly.
6. Mark the label of the UAK with year, month and number of
repeat installations.
7. Enable the primary circuit.
Assembly blue UAK
Attention
The UAK16N is only meant for assembly on a neutral.
1. Ensure a safe working area during assembly,
maintenance and inspection of the voltage tap. Disconnect
the power of the primary circuit and make sure it cannot
be enabled unintentionally.
2. Connect the secondary lead to the high impedance
voltage input of the measurement instrument (e.g., a
voltmeter or voltage input of kWh-meter).
3. Mount the voltage tap around the busbar which should be
tapped by turning the lower part.
4. Check if the voltage tap is mounted properly.
Check if the secondary lead is connected properly and
firmly.
5. Mark the label of the UAK with year, month and number of
repeat installations.
6. Enable the primary circuit.
Wiring Diagram
Maintenance and inspection
Check whether the secondary lead is connected firmly.
Check whether the easy voltage tap is mounted firmly.
Attention
Always avoid working on live parts of an installation.
Problem solving
e.g. unexpected values, incorrect values
Check the settings of the meter by using the installation
guide of the meter.
Check whether the voltage tap is mounted on the intended
cable.
Disassembly instruction
To disconnect the meter from the voltage tap, please consult
the installation guide of the meter.
1. Ensure a safe working area during disassembling the
voltage tap. Disconnect the power of the primary circuit
and make sure it cannot be enabled unintentionally.
2. UAK4Z: Remove the fuse and disconnect the
measurement device. As next step remove the UAK from
the connector.
UAK16 and UAK16N: Remove the UAK from the
connector and disconnect the measurement device.
3. Repair or replace the busbar after removal to ensure safe
isolation. Not repairing the busbar may result in an unsafe
situation.
4. Enable the primary circuit if is necessary.
Recycling
When the product has reached ‘end of life’, it must be
recycled. Do not dispose this product as unsorted municipal
waste. Contact a qualified recycler for disposal.
UAK4Z
UAK16(N)
This manual suits for next models
3
Other ELEQ Cables And Connectors manuals
Popular Cables And Connectors manuals by other brands

Tektronix
Tektronix Keithley 4200-TRX Series instruction sheet

Eagle
Eagle E250EG product manual

DX Engineering
DX Engineering Anderson Powerpole DXE-PP30 manual

Super Handy
Super Handy GUR058 Operator's manual

Connective Peripherals
Connective Peripherals ES-U-1001-R10 datasheet

Humminbird
Humminbird NMEA 2000 module installation guide