ELEQ RM27 User manual

84073/ EN2109
Technical Specifications
Safety and environmental conditions
CE marking
LV directive 2014/35/EU
RoHS directive (EU) 2015/863
Standard
EN-IEC 61010-1:2010
WEEE directive 2012/19/EU
This product is designed to be safe under the following
conditions:
Location
Altitude
Ambient temperature
Storage temperature
Relative humidity
Pollution degree
Degree of protection
Indoor use
Up to 2000m
-10°C .. +55°C
-20°C .. +70°C
5% .. 85%, non condensing
2
IP20
The RM27 is only suitable for insulated primary conductors.
Specifications
Standard
Rated short-time thermal current
(Ith):
Rated dynamic current (Idyn)
Continuous thermal current (Icth)
IEC 61869-2:2012
60 x Ipr / 1s
2,5 x Ith
100%
Rated insulation level
Rated frequency
Class of insulation ( see rating
plate)
Secondary terminal
0,72/3/-kV
50/60Hz
E (120°C) or A (105°C)
Female clamping
connector picoMAX3.5
Wago, suitable for
conductor size: 0,2 ..
1,5mm² solid, stranded
or ferruled (Strip length
8 .. 9 mm)
Specifications per type
RM27
Secondary
leads format*
0,5mm2
1,4meter
0,75mm2
2,0meter
1,0mm2
2,8meter
1,5mm2
4,0meter
Suitable for
cable
ø 7,5
Approximate
weight
40g
* Maximum length secondary leads for 0,1VA at the end of this leads.
ELEQ reserves the right to carry out modifications on its products, in
order to improve them, without prior notice.
Safety instruction
All activities for installation, commissioning and maintenance
of this current transformer must be performed by qualified
personnel that have the knowledge of applicable safety
precautions. This guide assumes that the reader of this
document has sufficient electro-
technical knowledge to
understand the content of this document.
General
The RM27 is a current transformer (CT) and can only be used
measuring electrical alternating currents. The RM27 is
suitable only for mounting on insulated primary conductors in
a weather protected and dry location.
Explanation of symbols
This product is designed according to the
EN-IEC 61010-1:2010 standards and therefore this
product meets the requirements of the Low Voltage
Directive 2014/35/EU.
Read the installation guide before mounting the
product. Unprofessional work activities on electrical
installations may result in a threat of danger to the life
and health of human beings and livestock!
Under no circumstances the secondary circuit of the
CT may be opened when the CT is mounted on a
primary current and current is flowing in the primary
circuit. High voltages may appear on the
secondary leads when this circuit is left open.
RoHS Directive (EU) 2015/863
ELEQ states that they only uses qualified component
in their products from manufacturers, whose
specifications meet or exceed the requirements of
the European Directive for the Restriction of use of
certain Hazardous Substances.
WEEE Directive 2012/19/EU
The 'crossed out wheeled bin' symbol indicates that
the equipment should not be disposed as unsorted
municipal waste
. Contact a qualified recycler for
disposal.
RM27 Current Transformer
Installation Guide
RM27 (4R27xxx)
Mounting Clip (411884)
Read this installation guide before installing the product
84073/ EN2109
Technical Specifications
Safety and environmental conditions
CE marking
LV directive 2014/35/EU
RoHS directive (EU) 2015/863
Standard
EN-IEC 61010-1:2010
WEEE directive 2012/19/EU
This product is designed to be safe under the following
conditions:
Location
Altitude
Ambient temperature
Storage temperature
Relative humidity
Pollution degree
Degree of protection
Indoor use
Up to 2000m
-10°C .. +55°C
-20°C .. +70°C
5% .. 85%, non condensing
2
IP20
The RM27 is only suitable for insulated primary conductors.
Specifications
Standard
Rated short-time thermal current
(Ith):
Rated dynamic current (Idyn)
Continuous thermal current (Icth)
IEC 61869-2:2012
60 x Ipr / 1s
2,5 x Ith
100%
Rated insulation level
Rated frequency
Class of insulation ( see rating
plate)
Secondary terminal
0,72/3/-kV
50/60Hz
E (120°C) or A (105°C)
Female clamping
connector picoMAX3.5
Wago, suitable for
conductor size: 0,2 ..
1,5mm² solid, stranded
or ferruled (Strip length
8 .. 9 mm)
Specifications per type
RM27
Secondary
leads format*
0,5mm2
1,4meter
0,75mm2
2,0meter
1,0mm2
2,8meter
1,5mm2
4,0meter
Suitable for
cable
ø 7,5
Approximate
weight
40g
* Maximum length secondary leads for 0,1VA at the end of this leads.
ELEQ reserves the right to carry out modifications on its products, in
order to improve them, without prior notice.
Safety instruction
All activities for installation, commissioning and maintenance
of this current transformer must be performed by qualified
personnel that have the knowledge of applicable safety
precautions. This guide assumes that the reader of this
document has sufficient electro-technical knowledge to
understand the content of this document.
General
The RM27 is a current transformer (CT) and can only be used
measuring electrical alternating currents. The RM27 is
suitable only for mounting on insulated primary conductors in
a weather protected and dry location.
Explanation of symbols
This product is designed according to the
EN-IEC 61010-1:2010 standards and therefore this
product meets the requirements of the Low Voltage
Directive 2014/35/EU.
Read the installation guide before mounting the
product. Unprofessional work activities on electrical
installations may result in a threat of danger to the life
and health of human beings and livestock!
Under no circumstances the secondary circuit of the
CT may be opened when the CT is mounted on a
primary current and current is flowing in the primary
circuit. High voltages may appear on the
secondary leads when this circuit is left open.
RoHS Directive (EU) 2015/863
ELEQ states that they only uses qualified component
in their products from manufacturers, whose
specifications meet or exceed the requirements of
the European Directive for the Restriction of use of
certain Hazardous Substances.
WEEE Directive 2012/19/EU
The 'crossed out wheeled bin' symbol indicates that
the equipment should not be disposed as unsorted
municipal waste. Contact a qualified recycler for
disposal.
RM27 Current Transformer
Installation Guide
RM27 (4R27xxx)
Mounting Clip (411884)
Read this installation guide before installing the product
84073/ EN2109
Technical Specifications
Safety and environmental conditions
CE marking
LV directive 2014/35/EU
RoHS directive (EU) 2015/863
Standard
EN-IEC 61010-1:2010
WEEE directive 2012/19/EU
This product is designed to be safe under the following
conditions:
Location
Altitude
Ambient temperature
Storage temperature
Relative humidity
Pollution degree
Degree of protection
Indoor use
Up to 2000m
-10°C .. +55°C
-20°C .. +70°C
5% .. 85%, non condensing
2
IP20
The RM27 is only suitable for insulated primary conductors.
Specifications
Standard
Rated short-time thermal current
(Ith):
Rated dynamic current (Idyn)
Continuous thermal current (Icth)
IEC 61869-2:2012
60 x Ipr / 1s
2,5 x Ith
100%
Rated insulation level
Rated frequency
Class of insulation ( see rating
plate)
Secondary terminal
0,72/3/-kV
50/60Hz
E (120°C) or A (105°C)
Female clamping
connector picoMAX3.5
Wago, suitable for
conductor size: 0,2 ..
1,5mm² solid, stranded
or ferruled (Strip length
8 .. 9 mm)
Specifications per type
RM27
Secondary
leads format*
0,5mm2
1,4meter
0,75mm2
2,0meter
1,0mm2
2,8meter
1,5mm2
4,0meter
Suitable for
cable
ø 7,5
Approximate
weight
40g
* Maximum length secondary leads for 0,1VA at the end of this leads.
ELEQ reserves the right to carry out modifications on its products, in
order to improve them, without prior notice.
Safety instruction
All activities for installation, commissioning and maintenance
of this current transformer must be performed by qualified
personnel that have the knowledge of applicable safety
precautions. This guide assumes that the reader of this
document has sufficient electro-technical knowledge to
understand the content of this document.
General
The RM27 is a current transformer (CT) and can only be used
measuring electrical alternating currents. The RM27 is
suitable only for mounting on insulated primary conductors in
a weather protected and dry location.
Explanation of symbols
This product is designed according to the
EN-IEC 61010-1:2010 standards and therefore this
product meets the requirements of the Low Voltage
Directive 2014/35/EU.
Read the installation guide before mounting the
product. Unprofessional work activities on electrical
installations may result in a threat of danger to the life
and health of human beings and livestock!
Under no circumstances the secondary circuit of the
CT may be opened when the CT is mounted on a
primary current and current is flowing in the primary
circuit. High voltages may appear on the
secondary leads when this circuit is left open.
RoHS Directive (EU) 2015/863
ELEQ states that they only uses qualified component
in their products from manufacturers, whose
specifications meet or exceed the requirements of
the European Directive for the Restriction of use of
certain Hazardous Substances.
WEEE Directive 2012/19/EU
The 'crossed out wheeled bin' symbol indicates that
the equipment should not be disposed as unsorted
municipal waste. Contact a qualified recycler for
disposal.
RM27 Current Transformer
Installation Guide
RM27 (4R27xxx)
Mounting Clip (411884)
Read this installation guide before installing the product
84073 / EN2109
ELEQ b.v.
Tukseweg 130, 8331 LH Steenwijk, The Netherlands
ELEQ b.v.
Tukseweg 130, 8331 LH Steenwijk, The Netherlands

Always avoid working on live parts of an installation.
Mounting instruction
Tools are only required connecting the primary cable running
through the Current Transformer. To connect the CT to the
meter correctly, please consult the installation guide of the
meter.
Assembly
Under no circumstances the secondary circuit of the CT may
be opened when the current is flowing in the primary circuit.
High voltages may appear on the secondary leads when this
circuit is left open.
1. Ensure a safe working area during assembly,
maintenance and inspection of the CT. Disconnect the
power of the primary circuit and make sure it can not be
enabled unintentionally.
2. Find the power direction of the cable you want to
measure. It is recommended to mount P1 side to power
source and P2 side to power consumer. If so the arrow on
the CT will indicate the direction of power flow.
3. Mount the CT on the cable. The RM27 can be mounted
stand-alone and clicked on each other. Optional: screw
mounting or mounting on a DIN-rail via the mounting clip
(411884).
4. Reinstall the primary conductor.
5. Connect the secondary leads (S1, S2) to the low
impedance current input of the measurement instrument
(e.g., an ammeter or current input of kWh-meter). For
more information about the secondary leads, please
consult the specifications table under ‘Technical
Specifications’.
6. Check if the CT is mounted properly.
Check if the secondary leads are connected properly and
firmly.
7. Enable the primary circuit.
Wiring Diagram
Accuracy
The CT may not meet its accuracy specification when the
secondary burden is to high. For example due to a secondary
cable which is too long or too thin.
Maintenance and inspection
Check whether the secondary leads are connected firmly.
Check whether the CT is mounted firmly.
Remove severe pollution on the casing.
Attention
Always avoid working on live parts of an installation.
Temporarily disconnecting the CT
The secondary leads of the CT always have to be connected
to a low impedance burden such as an ammeter. When,
during maintenance, no burden is available to connect to, the
secondary leads of the CT (the two secondary terminals)
must be short-circuited.
Problem solving
e.g. unexpected values, incorrectly values, reversed power
Check the settings of the meter by using the installation
guide of the meter.
Check whether the CT is mounted on the intended cable in
the right direction.
Check the value of the secondary burden (secondary leads
length/diameter and meter impendent). See product/data
sheet for the maximum burden value.
Attention
Always follow the disassembling instructions when reversing
the CT.
Disassembly instruction
Tools are only required disconnecting the primary cable
running through the RM27. To disconnect the meter from the
CT, please consult the installation guide of the meter.
1. Ensure a safe working area during disassembling the CT.
Disconnect the power of the primary circuit and make sure
it cannot be enabled unintentionally.
2. Dismount the CT from the primary conductor.
3. Disconnect the secondary leads from the measurement
instrument.
4. Reinstall the primary conductor.
5. Enable the primary circuit if is necessary.
Recycling
When the product has reached ‘end of life’, it must be
recycled. Do not dispose this product as unsorted municipal
waste. Contact a qualified recycler for disposal.
Always avoid working on live parts of an installation.
Mounting instruction
Tools are only required connecting the primary cable running
through the Current Transformer. To connect the CT to the
meter correctly, please consult the installation guide of the
meter.
Assembly
Under no circumstances the secondary circuit of the CT may
be opened when the current is flowing in the primary circuit.
High voltages may appear on the secondary leads when this
circuit is left open.
1. Ensure a safe working area during assembly,
maintenance and inspection of the CT. Disconnect the
power of the primary circuit and make sure it can not be
enabled unintentionally.
2. Find the power direction of the cable you want to
measure. It is recommended to mount P1 side to power
source and P2 side to power consumer. If so the arrow on
the CT will indicate the direction of power flow.
3. Mount the CT on the cable. The RM27 can be mounted
stand-alone and clicked on each other. Optional: screw
mounting or mounting on a DIN-rail via the mounting clip
(411884).
4. Reinstall the primary conductor.
5.
Connect the secondary leads (S1, S2) to the low
impedance current input of the measurement instrument
(e.g., an ammeter or current input of kWh-meter). For
more information about the secondary leads, please
consult the specifications table under ‘Technical
Specifications’.
6. Check if the CT is mounted properly.
Check if the secondary leads are connected properly and
firmly.
7. Enable the primary circuit.
Wiring Diagram
Accuracy
The CT may not meet its accuracy specification when the
secondary burden is to high. For example due to a secondary
cable which is too long or too thin.
Maintenance and inspection
Check whether the secondary leads are connected firmly.
Check whether the CT is mounted firmly.
Remove severe pollution on the casing.
Attention
Always avoid working on live parts of an installation.
Temporarily disconnecting the CT
The secondary leads of the CT always have to be connected
to a low impedance burden such as an ammeter. When,
during maintenance, no burden is available to connect to, the
secondary leads of the CT (the two secondary terminals)
must be short-circuited.
Problem solving
e.g. unexpected values, incorrectly values, reversed power
Check the settings of the meter by using the installation
guide of the meter.
Check whether the CT is mounted on the intended cable in
the right direction.
Check the value of the secondary burden (secondary leads
length/diameter and meter impendent). See product/data
sheet for the maximum burden value.
Attention
Always follow the disassembling instructions when reversing
the CT.
Disassembly instruction
Tools are only required disconnecting the primary cable
running through the RM27. To disconnect the meter from the
CT, please consult the installation guide of the meter.
1. Ensure a safe working area during disassembling the CT.
Disconnect the power of the primary circuit and make sure
it cannot be enabled unintentionally.
2. Dismount the CT from the primary conductor.
3. Disconnect the secondary leads from the measurement
instrument.
4. Reinstall the primary conductor.
5. Enable the primary circuit if is necessary.
Recycling
When the product has reached ‘end of life’, it must be
recycled. Do not dispose this product as unsorted municipal
waste. Contact a qualified recycler for disposal.
Always avoid working on live parts of an installation.
Mounting instruction
Tools are only required connecting the primary cable running
through the Current Transformer. To connect the CT to the
meter correctly, please consult the installation guide of the
meter.
Assembly
Under no circumstances the secondary circuit of the CT may
be opened when the current is flowing in the primary circuit.
High voltages may appear on the secondary leads when this
circuit is left open.
1. Ensure a safe working area during assembly,
maintenance and inspection of the CT. Disconnect the
power of the primary circuit and make sure it can not be
enabled unintentionally.
2. Find the power direction of the cable you want to
measure. It is recommended to mount P1 side to power
source and P2 side to power consumer. If so the arrow on
the CT will indicate the direction of power flow.
3. Mount the CT on the cable. The RM27 can be mounted
stand-alone and clicked on each other. Optional: screw
mounting or mounting on a DIN-rail via the mounting clip
(411884).
4. Reinstall the primary conductor.
5. Connect the secondary leads (S1, S2) to the low
impedance current input of the measurement instrument
(e.g., an ammeter or current input of kWh-meter). For
more information about the secondary leads, please
consult the specifications table under ‘Technical
Specifications’.
6. Check if the CT is mounted properly.
Check if the secondary leads are connected properly and
firmly.
7. Enable the primary circuit.
Wiring Diagram
Accuracy
The CT may not meet its accuracy specification when the
secondary burden is to high. For example due to a secondary
cable which is too long or too thin.
Maintenance and inspection
Check whether the secondary leads are connected firmly.
Check whether the CT is mounted firmly.
Remove severe pollution on the casing.
Attention
Always avoid working on live parts of an installation.
Temporarily disconnecting the CT
The secondary leads of the CT always have to be connected
to a low impedance burden such as an ammeter. When,
during maintenance, no burden is available to connect to, the
secondary leads of the CT (the two secondary terminals)
must be short-circuited.
Problem solving
e.g. unexpected values, incorrectly values, reversed power
Check the settings of the meter by using the installation
guide of the meter.
Check whether the CT is mounted on the intended cable in
the right direction.
Check the value of the secondary burden (secondary leads
length/diameter and meter impendent). See product/data
sheet for the maximum burden value.
Attention
Always follow the disassembling instructions when reversing
the CT.
Disassembly instruction
Tools are only required disconnecting the primary cable
running through the RM27. To disconnect the meter from the
CT, please consult the installation guide of the meter.
1. Ensure a safe working area during disassembling the CT.
Disconnect the power of the primary circuit and make sure
it cannot be enabled unintentionally.
2. Dismount the CT from the primary conductor.
3. Disconnect the secondary leads from the measurement
instrument.
4. Reinstall the primary conductor.
5. Enable the primary circuit if is necessary.
Recycling
When the product has reached ‘end of life’, it must be
recycled. Do not dispose this product as unsorted municipal
waste. Contact a qualified recycler for disposal.
Other ELEQ Transformer manuals
Popular Transformer manuals by other brands

ATL Transformers
ATL Transformers T2914 O & M Manual

Sifam Tinsley
Sifam Tinsley Omega Xmer operating manual

Sifam Tinsley
Sifam Tinsley Omega XMER Series operating manual

Skyworks
Skyworks LinkCom PC07 001R-A Series Reference manual

DiodeDrive
DiodeDrive LVT-W-12VAC Series user manual

Crown
Crown TP-170V datasheet