Always avoid working on live parts of an installation.
Mounting instruction
In order to mount this CT 4 spring fitted screws need to be
placed and tightened with a M5 Hex / Allen key.
Assembly
Under no circumstances the secondary circuit of the CT may
be opened when the CT is closed and the current is flowing in
the primary circuit. High voltages may appear on the
secondary leads when this circuit is left open.
1. Ensure a safe working area during assembly,
maintenance and inspection of the CT. If necessary,
disconnect the power of the primary circuit and make sure
it can not be enabled unintentionally.
2. Find the power direction of the primary. It is recommended
to mount the P1 side to power source and the P2 side to
power consumer. If the CT is installed like this, the arrow
on the CT will indicate the direction of the power flow.
3. Connect the secondary leads (S1, S2) to the TQ
terminals. Ensure that the leads are capable of carrying
the current output of the CT.
4. Connect the secondary leads (S1, S2) to the low
impedance current input of the measurement instrument
(e.g., an ammeter or current input of kWh-meter).
5. To mount the CT, use the Allen key to securely fasten the
screws in a crisscross pattern.
6. Enable the primary circuit if necessary.
Wiring Diagram
Maintenance and inspection
Check whether the secondary leads are connected firmly.
Check whether the CT is closed properly.
Check whether the CT is mounted firmly.
Remove severe pollution on the casing. Contact with
moisture, especially with the core, must be avoided.
Attention
Do not touch the core surfaces by hand: skin acid may
damage the core.
Temporarily disconnecting the CT
The secondary leads of the CT always have to be connected
to a low impedance burden such as an ammeter. When
during maintenance, no burden is available to connect to, the
secondary leads of the CT (the two secondary terminals)
must be short-circuited. Before changing the secondary circuit
the CT core shall be opened.
Problem solving
e.g. unexpected values or incorrect values , reversed power,
Check the settings of the meter by using the installation
guide of the meter.
Check whether the CT is mounted on the intended cable in
the right direction.
Check if the CT is closed properly.
Check the value of the secondary burden (secondary leads
length/diameter and meter impedance). See product/data
sheet for the maximum burden value.
If previous points did not solve the problem:
Check carefully whether there is dust or other pollution
present between the two parts of the core. In case there is
pollution, the core surfaces can be cleaned with a lint free
cloth and then protected with an extremely thin layer of acid
free petroleum jelly (Vaseline).
Attention
Always follow the disassembling instructions when reversing
the CT.
Disassembly instruction
1. Ensure a safe working area during disassembling the CT.
If necessary, disconnect the power of the primary circuit
and make sure it cannot be enabled unintentionally.
2. Open the CT by removing the screws.
3. Disconnect the secondary leads from the measurement
instrument.
4. Disconnect the secondary leads from the meter.
5. Enable the primary circuit if is necessary.
Recycling
When the product has reached ‘end of life’, it must be
recycled. Do not dispose this product as unsorted municipal
waste. Contact a qualified recycler for disposal.