Elettronica Santerno AMS90/1 Series Instructions for use

•This manual is integrant and essential to the product. Carefully read the instructions contained herein
as they provide important hints for use and maintenance safety.
•This device is to be used only for the purposes it has been designed to. Other uses should be
considered improper and dangerous. The manufacturer is not responsible for possible damages
caused by improper, erroneous and irrational uses.
•Elettronica Santerno is responsible for the device in its original setting.
•Any changes to the structure or operating cycle of the device must be performed or authorized by the
Engineering Department of Elettronica Santerno.
•Elettronica Santerno assumes no responsibility for the consequences resulting by the use of non
original spare-parts.
•Elettronica Santerno reserves the right to make any technical changes to this manual and to the
device without prior notice. If printing errors or similar are detected, the corrections will be included in
the new releases of the manual.
•Elettronica Santerno is responsible for the information contained in the original version of the Italian
manual.
•The information contained herein is the property of Elettronica Santerno and cannot be reproduced.
Elettronica Santerno enforces its rights on the drawings and catalogues according to the law.
Elettronica Santerno S.p.A.
Via G. Di Vittorio, 3 - 40020 Casalfiumanese (BO) Italy
Tel. +39 0542 668611 - Fax +39 0542 666632
After Sales Service Tel. +39 0542 668610 - Fax +39 0542 666778
Sales Office Tel. +39 051 6010231 - Fax +39 051 534403

15P0056B1 APPLICATION MANUAL AMS90/1
2/17
TABLE OF CONTENTSTABLE OF CONTENTS
Standard configuration.............................................................................. Page 2
General features ....................................................................................... "3
External and fixing dimensions (fig. 1) ..................................................... "4
Power and supply connections ................................................................ "5
Signal connections ................................................................................... "5
Power and supply connections diagram (fig. 2) ....................................... "6
Signal connection diagram (fig. 3) ............................................................ "7
Size codes and extra-quick fuses table .................................................... "8
ES719 control board description............................................................... "9
Adjustment trimmers............................................................................ "9
Signalling LED’s................................................................................... "9
Preset jumpers..................................................................................... "10
Selection dip-switches ......................................................................... "10
ES719 control board layout (fig. 4) .......................................................... "11
Terminal board description ....................................................................... "12
Technical data table.................................................................................. "13
EMI characteristics and input filter ........................................................... "14
Installation, calibration and maintenance ................................................. "15
IMPORTANT NOTICE
If, after powering the unit, closing the run contact and sending the speed reference, the motor does
not start, check that the power circuit supply at term. 23-24 has the SAME PHASE of the control
circuit supply at term. 25-26.
If in doubt, with power circuit on (remote control switch closed, if any), check that an alternate
voltage is present with a zero effective value (±± 200mV) between terminals 23 and 25, and between
terminals 24 and 26.
STANDARD CONFIGURATIONSTANDARD CONFIGURATION
If no custom configuration is required, the standard configuration of the AMS90/1 drive
is the following:
SUPPLY VOLTAGE: 400Vac / 50Hz.
TACHO GENERATOR FEEDBACK: 180VDC max.
CURRENT LIMIT: rated value.
WARNINGWARNING:before powering the unit on, check that the voltage (TR3, J2) and
frequency (SW1) values on the plate match those of the supply mains at terminals 25-
26.

AMS90/1 APPLICATION MANUAL 15P0056B1
3/17
GENERAL FEATURESGENERAL FEATURES
Application AMS90/1 is a HALF-CONTROLLED AC/DC SINGLE-PHASE DRIVE used to
supply armature and field circuits of D.C. motors, with SMT analog circuit for
speed or torque control.
Supply mains 230/400VAC single-phase, through voltage switching jumpers, 50/60Hz through
selection dip-switches. 415/440VAC voltages on demand.
Field supply Single-phase rectifier bridge with suppression varistor.
Armature voltage 0…280VDC (for 400VAC mains).
Mains insulation Galvanic type, with tacho generator feedback.
Reference supplies Stabilized, with values ranging from +10VDC to –10VDC.
Speed inputs 1 direct input + 1 ramp input, through voltage reference signal 0…+10VDC, with
terminal board output.
1 direct input through current reference signal 4…20mA, to be selected through
proper jumper setting.
Adjustments Max. and min. speed value (min. value selectable through potentiometer).
Stability.
Internal or external current limit.
Armature compensation.
Acceleration and deceleration ramps.
Speed offset.
Light indicators Presence of supply direct voltages.
Current limit reached.
Zero speed.
Running drive.
Auxiliary functions Gradual acceleration and deceleration, with run automatic release.
Tacho generator feedback with automatic polarity rectification.
High-impedance armature feedback, with R x I drop compensation.
Current limit Selectable through internal trimmer or external voltage 0…-10VDC.
Analog outputs Voltage signal 0…+10VDC V OUT proportional to motor speed.
Current signal 0…+10VDC I OUT proportional to armature current.
Digital I/Os Input for RUN/STAND BY control through high or low voltage level, selectable
through jumper.
Output with insulated relay contact, for zero speed signalling.
Room conditions Natural ventilation.
Temperature from 0 to 40°C max. with 4% derating for every degree of increase.
Relative humidity 20…90% (without dew).
Height: 1000m max (a.s.l.). 1% derating for every 100m increase.
Weight 2.65kg for AMS90/1.10 and .20; 3.3kg for AMS90/1.30.
Protection degree IP20.

15P0056B1 APPLICATION MANUAL AMS90/1
4/17
•• Ground screw (thread M5).
‚‚ Fixing on vertical panel through 4 M4 screws.
ƒƒ Let a free space in the upper and lower side of the drive, so as the cooling air can
circulate.
„„ To access the drive inside, unscrew the two self-tapping screws 3.5x9.5 used for
cover fastening.
Fig. 1 - External and fixing dimensions
TERMINAL BOARDS

AMS90/1 APPLICATION MANUAL 15P0056B1
5/17
POWER AND SUPPLY CONNECTIONSPOWER AND SUPPLY CONNECTIONS
(See fig. 2)
EF Single-phase filter against electromagnetic interference (EMI). See
section EMI CHARACTERISTICS AND INPUT FILTER.
L1/L2 Supply single-phase mains 50/60Hz (standard 400VAC).
FU1/FU2 Fast-acting fuses for AC/DC armature bridge protection.
FU3/FU4 Delayed fuses for TC auto-transformer primary protection.
FU5 Fast-acting fuse for field AC/DC bridge.
FU6/FU7 2A fast-acting fuses to protect the control circuit supply internal
transformer.
KM Supply remote control switch for AC/D armature bridge.
L1 Switching impedance.
L2 Levelling impedance for form factor enhancement.
TC Auto-transformer (if any) for D.C. motor field supply.
The alternate voltage V
EA
on the secondary is obtained from the direct
voltage VEC through the following formula:
11.1
⋅
=
ECEA VV
M1 D.C. motor (armature circuit + field circuit).
Note: at term. 29-30, a 2A direct current can be delivered for field winding, for all AMS90/1 sizes. Do not
exceed this value.
If the motor needs a higher current, the field circuit should be supplied separately.
SIGNAL CONNECTIONSSIGNAL CONNECTIONS
(See fig. 3)
RP1 2K5 potentiometer for speed reference.
RP2 2K5 potentiometer for current limit reference (only with AMS90/1 properly
preset: see jumper J5).
KA Run contact.
BR Tacho generator.
PV Tacho instrument.
PA Ammeter instrument.
KM NO contact of supply remote control switch for AC/DC armature bridge.

15P0056B1 APPLICATION MANUAL AMS90/1
6/17
Connect term. 25-26 IN PHASE with term. 23-24 respectively.
Fig. 2 - Power and supply connections diagram

AMS90/1 APPLICATION MANUAL 15P0056B1
7/17
Note: to have the drive match the standards concerning radio-frequency immunity characteristics, keep 0V
insulated from earth. In turn, connect the earth to cable shield, through a connection that should be as
short as possible.
Always fit a NO auxiliary contact of KM remote control switch at terminal 18,
as closure of KM remote control switch AFTER closure of RUN contact, if control
section is already supplied at terminal 25-26, may destroy internal rectifier bridge.
Fig. 3 - Signal connection diagram

15P0056B1 APPLICATION MANUAL AMS90/1
8/17
SIZE CODES AND EXTRA-QUICK FUSES TABLESIZE CODES AND EXTRA-QUICK FUSES TABLE
Drive Product
code Size
code Max.
mean
curr.
(A)
Max.
allowed
form
factor
F.A.
fuses
FU1/2
(A)
Max I2T
for FU1/2
VALIM +10%
(A2s)
AMS90/1.10 supp.230V ZZ0045020 01230
AMS90/1.10 supp.400V ZZ0045020 01400
AMS90/1.10 supp.415V ZZ0045020 01410
AMS90/1.10 supp.440V ZZ0045020 01440
10 25 150
AMS90/1.20 supp.230V ZZ0045020 02230
AMS90/1.20 supp.400V ZZ0045020 02400
AMS90/1.20 supp.415V ZZ0045020 02410
AMS90/1.20 supp.440V ZZ0045020 02440
20 25 150
AMS90/1.30 supp.230V ZZ0045030 03230
AMS90/1.30 supp.400V ZZ0045030 03400
AMS90/1.30 supp.415V ZZ0045030 03410
AMS90/1.30 supp.440V ZZ0045030 03440
30
1,5
32..35 250
WARNING: The use of extra-quick fuses FU1/2 is recommended to protect the internal
power module in case of undesired external short-circuits. Comply with the max.
prescribed value for I2t.
The L1 switching impedance is 35A/150µH
(ELETTRONICA SANTERNO code: IM0100354).
The current FF form factor can be obtained by measuring the effective value
[ ]
ae
Iof the
alternate component of the current absorbed by the motor (with a A.C. instrument with
real effective value) and the mean value Imof the same current (with a D.C. instrument).
The result is given by the following formula:
[ ]
m
mae
I
II
FF
22 +
=
Since the motor and drive heating, as well as the periodical maintenance operations on
brushes and manifold, depend on the form factor, apply the levelling inductance L2 so
as to keep the form factor value as close as possible to 1.
Through the following formula, you can get the L2 mH value of the levelling inductance
to be inserted, assuming the motor one is negligible, using the desired form factor FF
value, the supply alternate voltage Vavalue and the mean output current Imvalue:
[ ]
1
9.0
2
2−⋅
⋅
=FFI
V
mHL
m
a

AMS90/1 APPLICATION MANUAL 15P0056B1
9/17
ES719 CONTROL BOARD DESCRIPTIONES719 CONTROL BOARD DESCRIPTION
(see fig. 4)
ADJUSTMENT TRIMMERSADJUSTMENT TRIMMERS
(RV1) 10V Supply voltages ±10V.
Do not change.
(RV2) n MIN Min. speed, selectable on the negative terminal of the RP1 speed
potentiometer.
(RV3) STAB Stability (PI time constant of voltage amplifier).
(RV4) UP Acceleration ramp (0,5 ... 100sec).
(RV5) DOWN Deceleration ramp (0,5 ... 100sec).
(RV6) n OUT Signal output at term. 11, proportional to the motor rotation speed
(tacho generator feedback), or to the voltage output at terminals 21-
22 in case of armature feedback.
(RV7) I LIM Internal current limitation.
(RV8) COMP Compensation for armature drop R x I.
Note: in case of tacho generator feedback, keep it in CCW position.
(RV9) n MAX Max. speed.
Tacho generator feedback: selectable within the range 40…230V
DC
at term. 1-2.
Armature feedback: selectable within the range 55…325V
CC
at term.
21-22.
(RV10) n OFS Speed amplifier offset: the correct adjustment of this trimmer avoids
speed drift with zero reference and, at the same time, an area
insensitive to minimum references. Change it only if required: see section
CALIBRATION.
SIGNALING LEDSSIGNALING LEDS
(L1) 15V Presence of ±15Vdc supply voltages.
(L2) n=0 Motor at zero speed.
(L3) RUN Operation enabling.
(L4) LIM Drive in current limitation.
... cont.

15P0056B1 APPLICATION MANUAL AMS90/1
10/17
... cont. ES719 CONTROL BOARD DESCRIPTIONES719 CONTROL BOARD DESCRIPTION
(see fig. 4)
PRESET JUMPERSPRESET JUMPERS
(Pos. STANDARD: J2 ⇒⇒ 400, J3 ⇒⇒ L, J4 ⇒⇒ V, J5 ⇒⇒ I)
J2 pos. 230 230Vac supply at terminals 25 and 26.
J2 pos. 400 400Vac supply at terminals 25 and 26.
NOTE: If required, our transformer with code TR0102121 (instead of TR0102122) can be installed
as transformer TR3 to supply with voltage the terminals 25 and 26, according to the position of jumper J2,
415Vac or 440Vac.
J3 pos. L Drive enabling at term. 18 (RUN) closing towards 0V, through insulated
relay contact or NPN transistor.
J3 pos. H Drive enabling at term. 18 (RUN) closing towards a positive voltage of
0…30VDC, through insulated relay contact or NPN transistor.
J4 pos. V Term. 7 configured as ramp input for a voltage speed reference of
0…+10VDC.
J4 pos. I Term. 7 configured as ramp input for a current speed reference of
4…20mA (current output from term. 7).
J5 pos. I Inner adjustment of current limit.
J5 pos. E External control of current limit.
SELECTION DIP-SWITCHESSELECTION DIP-SWITCHES
(Pos. STANDARD: SW1(1+2) ⇒⇒ OFF, SW2(1+2+3+4) ⇒⇒ OFF)
SW1 contacts 1+2 ⇒⇒ OFF
(bottom contacts) Presetting for mains supply with 50Hz frequency.
SW1 contacts 1+2 ⇒⇒ ON
(top contacts: 60)Presetting for mains supply with 60Hz frequency.
SW2 contacts 1+2+3+4 ⇒⇒ OFF
(bottom contacts) Presetting for tacho generator feedback at
terminals 1 and 2.
SW2 contacts 1+2+3+4 ⇒⇒ ON
(top contacts: ARM)Presetting of armature feedback, at high
impedance. In this case, the tacho generator signal
should NOT be present at term. 1 and 2.
Note: act on contacts SW2 only when term. 25-26 are NOT
supplied.
Note: under TACHO GENERATOR feedback, if you close only
the key no. 4 (the right one) of SW2, you LOWER the max.
speed range, which can be obtained through trimmer RV9 (n
MAX) – up to 16…92VDC at term. 1-2.

AMS90/1 APPLICATION MANUAL 15P0056B1
11/17
Fig. 4 - ES719 control board layout
n MIN
SW1
UP
n OUT
I LIM
n MAX
STAB
DOWN
SW2
COMP
n OFS
J3
J4
J5
J2
TR3
15V
LIM
n =0
RUN

15P0056B1 APPLICATION MANUAL AMS90/1
12/17
TERMINAL BOARD DESCRIPTIONTERMINAL BOARD DESCRIPTION
SIGNAL TERMINAL BOARDSIGNAL TERMINAL BOARD
10V 0V
2TG Input for tacho generator feedback Rin ≈107kΩ
30V 0V
4D IN Input for direct reference 0…+10VCC Rin ≈10kΩ
7R IN With J4 in pos. V:
ramp input for voltage signal 0…+10VDC.
With J4 in pos. I:
direct input for current signal 4…20mA.
J4 ⇒V:
Rin ≈107kΩ
J4 ⇒I:
Rin ≈107kΩ
8R OUT Ramp circuit output 0…+10VDC +10VDC max
(6mA max)
9I LIM With J5 in pos. I:
terminal not connected.
With J5 in pos. E:
input for external setting of current limit 0…-10VDC.
A reference of -10VDC can be used to set the AMS90/1 rated current. Rin = 10kΩ
11 n OUT Speed signal output (voltage) for tacho (voltmeter) or for cascade
reference distribution.
Adjustable through trimmer RV6 up to 10VDC.
STANDARD calibration: +10VDC at max. speed. +10VDC max
(6mA max)
12 I OUT Current signal output for possible ammeter.
STANDARD calibration: +10VDC at drive rated current. +10VDC max
(6mA max)
13 +10VCC Supply output for +10VDC reference. (6mA max)
14 -10VCC Supply output for -10VCC reference. (6mA max)
18 RUN With J3 in pos. L:
the drive is operated if term. 18 is connected to 0V
(through insulated relay contact or NPN transistor output).
With J3 in pos. H:
the drive is operated if term. 18 is connected to a positive voltage
10…30VDC (through insulated relay contact or NPN transistor
output).
J3 ⇒L:
12VDC / 1.2mA
J3 ⇒H:
0.5mA con 10VDC
1.9mA con 30VDC
19 0V 0V.
20 n MIN Resistive limit switch on negative end (CCW) of speed potentiometer,
for min. reference. Rin max = 10kΩ
31 nZ(C)
32 nZ(NO)
NO contact of inner relay signalling motor at zero speed.
The relay is energized at stopped motor, by closing contact at term. 31-
32.
The relay switching usually occurs at 2.1% of max. speed. 250VAC / 1250VA
... cont.

AMS90/1 APPLICATION MANUAL 15P0056B1
13/17
... cont. TERMINAL BOARD DESCRIPTIONTERMINAL BOARD DESCRIPTION
POWER TERMINAL BOARDPOWER TERMINAL BOARD
21
22
D.C. supply output for armature winding.
Positive polarity on term. 22.
23
24
Single-phase supply (STANDARD 400VAC) for AC/DC conversion bridge.
If required, 415/440VAC supply voltages are available.
SUPPLY TERMINAL BOARDSUPPLY TERMINAL BOARD
25
26
Single-phase supply (STANDARD 230/400VAC – 50Hz with voltage change jumper).
Supply frequency 60Hz with presetting by closing the two contacts of dip-switch SW1.
Note: If required, 415/440VAC supply voltages are available.
10VA
27
28
Single-phase supply (STANDARD 400VAC max) for inner rectifier for field winding. 400VAC max
2A max
29
30
D.C. supply output for field winding.
Positive polarity on term. 29.360VDC max
2A max
TECHNICAL DATA TABLETECHNICAL DATA TABLE
AMS90/1 size Rated
current
(A)
Max. armature
voltage
(V)
Output electric
power
(kW)
Motor power
(η=0.8)
(HP)
AMS90/1.10 supp. 230VAC 10 170 1.7 1.8
AMS90/1.10 supp. 400VAC 10 280 2.8 3
AMS90/1.20 supp. 230VAC 20 170 3.4 3.7
AMS90/1.20 supp. 400VAC 20 280 5.6 6
AMS90/1.30 supp. 230VAC 30 170 5.1 5.5
AMS90/1.30 supp. 400VAC 30 280 8.4 9.1

15P0056B1 APPLICATION MANUAL AMS90/1
14/17
EMI CHARACTERISTICS AND INPUT FILTEREMI CHARACTERISTICS AND INPUT FILTER
Radio-frequency interferences (RFI) can be generated in the area where the drive is installed. The
interferences can occur both on the air (irradiated interferences), and through the power and signal cables
(conducted interferences). Sometimes, due to these interferences, the drive can operate improperly, even
if the AMS90/1 unit is provided with a high noise immunity and complies with the EMI standards. Also, the
drive itself can produce interferences due to switching over of power semi-conductors representing its
output stage.
A malfunction can be detected in the devices installed close to the drive or connected at the same supply
or earth conductor.
To eliminate any interference that can affect the drive operation, proceed as follows:
-keep the drive power cables separated from the signal cables;
-use shielded cables for drive control signals and connect the shield to ground, as shown on the
connection diagram; for shield grounding, choose the shortest connection, that should be direct and
without any intermediate connection;
-always install anti-noise filters on the coils of remote control switches, solenoid valves, etc.
IMMUNITY TESTS OF AMS90/1
Electrostatic discharges: level 3 EN 61000 - 4 – 2
Burst: level 3 EN 61000 - 4 – 4
Surge: level 3 EN 61000 - 4 – 5
Radio-frequency electromagnetic fields: 10V/m IEC 1000 - 4 - 3
If malfunctions are detected in the devices installed close to the drive, take the following precautions:
- install the drive input filter;
-keep the drive power cables separated from any other cable;
-use shielded cables to connect sensors, instruments, etc.
-install any noise-sensitive devices as far as possible away from the drive.
WARNING! THE CONNECTION CABLES BETWEEN FILTER AND DRIVE SHOULD BE AS
SHORT AS POSSIBLE.
Here is a list of the filters recommended for the different drive models, so that the conducted and irradiated
interferences are included within the levels conforming to EN55011 class B and VDE0875G (civil
environment) standards. On the contrary, these filters are not required for industrial environments,
where the switching inductance is enough.
Drive type Filter type Rated voltage (V) Rated current (A) Filter code
AMS90/1.10 supp. 230Vac max FLTA-B 1,5M 250 at 50/400 Hz 2 x 12 AC1710220
AMS90/1.20 supp. 230Vac max FLTA-B 2,2M 250 at 50/400 Hz 2 x 24 AC1710320
AMS90/1.30 supp. 230Vac max FLTA-B 11T (*) 460 at 50/60 Hz 2 x 30 AC1710305
AMS90/1.10 supp. 440Vac max FLTA-B 4T 460 at 50/60 Hz 3 x 10 AC1710105
AMS90/1.20 supp. 440Vac max FLTA-B 11T 460 at 50/60 Hz 3 x 30 AC1710305
AMS90/1.30 supp. 440Vac max FLTA-B 11T (*) 460 at 50/60 Hz 3 x 30 AC1710305
(*) Use just two of the three lines available on the filter.

AMS90/1 APPLICATION MANUAL 15P0056B1
15/17
INSTALLATION, CALIBRATION AND MAINTENANCEINSTALLATION, CALIBRATION AND MAINTENANCE
PRELIMINARY CONTROLSPRELIMINARY CONTROLS
After receiving the drive, check it carefully in order to verify the presence of damages
due to transport. If so, take the necessary measures. Check that all the rating
corresponds to the application, as shown on the cover label.
If not, contact your dealer or ELETTRONICA SANTERNO.
INSTALLATIONINSTALLATION
The drive must be positioned so as to allow for air circulation in vertical direction. See
fig. 1: External and fixing dimensions.
When connecting the unit, comply with the following precautions:
1. Avoid positioning the wires of the tacho generator and of signals closes to the power
cables and other possible electromagnetic trouble sources. If more accuracy is
required in the control system, use shielded cables externally insulated for speed
reference and tacho generator feedback. The shield must be connected in the
shorter and more direct way to the ground, without any intermediate connection.
2. Make connections as short as possible.
3. After wiring, check if connections and solderings are correct and check the proper
positioning of jumpers and dip-switches, as regards the supply voltage and
frequency and the drive application.
4. Supply the control section at terminals 25 and 26 and check that LEDs (L1) 15V and
(L2) n=0 are on.
5. After supplying the field rectifier circuit at terminals 27 and 28, check the presence
of the direct voltage required for D.C. motor field supply at terminals 29 and 30.
6. Close the KM remote control switch and the KA contact (if any) connected in series
to the NO auxiliary contact of the remote control switch, and check that LED (L3)
RUN is turned on.
7. Send the speed reference to term. 7 (or 4) and check the motor is started. If this
does not happen and the LED (L4) LIM turns on, check if this condition is caused by
one of the following reasons:
a) The supply of term. 25-26 IS NOT IN PHASE with that of term. 23-24 (with closed remote control
switch, a zero alternate voltage should be present between term. 23 and 25, and term. 24 and 26).
b) An interruption occurred in one of the extra-quick fuses FU1-2 or in the armature connection.
c) Trimmer RV7 (I LIM) is fully rotated in counter-clockwise position (current limit is zero).
d) The drive is preset for external current limit (J5 ⇒E) and no negative voltage is applied to term. 9.
... cont.

15P0056B1 APPLICATION MANUAL AMS90/1
16/17
... cont. INSTALLATION, CALIBRATION AND MAINTENANCEINSTALLATION, CALIBRATION AND MAINTENANCE
CALIBRATION
The drive is usually delivered with preset calibrations, according to the data received
when ordering the unit, or based on the STANDARD CONFIGURATION.
If calibration data have to be checked or changed, proceed as follows:
a) Reduction of current limit below rating value:
1. Disconnect one of the two cables powering term. 27-28 and insulate it.
2. Connect an instrument for motor armature D.C. measurement.
3. Send a speed reference with intermediate value, close the line remote control switch
and the RUN contact.
4. Check the armature current value through the previously connected instrument, and,
if required, adjust the current value by rotating trimmer (RV7) I LIM. The value
shown by the instrument must reach the required continuous value.
5. If an ammeter is connected to terminal 12, check for data consistency, always
remembering that the unit sends a +10VDC signal at rated current (10, 20 or 30A,
depending on the circumstances).
IMPORTANT: The last two operations should be performed in the shortest time. Finally, reset the
supply of the field rectifier circuit (term. 27-28).
b) Maximum speed calibration
1. Start the machine by pressing the start push-button.
2. Rotate the speed potentiometer to the max. value.
3. Turn trimmer (RV9) n MAX so that the machine speed is at max. value, and check
that motor rating data, that is max. speed and max. armature voltage, is not
exceeded.
c) Speed ramp adjustment
1. Rotate the potentiometer to the max. value.
2. Start the drive.
3. If the time required by the drive to reach the maximum speed (voltage) is too short
or too long, rotate trimmer (RV4) UP. Otherwise, use trimmer (RV5) DOWN to
adjust the slope. Note: the drive can control the slope only if the set ramp is longer
than the normal inertia slope (i.e. the one obtained through idle stop). Further, it can
control the rise, provided that it does not enter the current limit condition, i.e.
provided that the rise ramp is not too short.
... cont.

AMS90/1 APPLICATION MANUAL 15P0056B1
17/17
... cont. INSTALLATION, CALIBRATION AND MAINTENANCEINSTALLATION, CALIBRATION AND MAINTENANCE
d) Stability calibration
Connect the speed potentiometer to the direct input at term. 4 and suddenly increase
the reference. Then, adjust trimmer (RV3) STAB so that the new speed value is
reached without excessive overshoot with a long settling time, and without too quick
and unstable dampings. In the first case, rotate the trimmer in CW direction, otherwise
rotate it CCW.
e) Calibration of RxI compensation (without tacho generator only).
Adjust trimmer (RV8) COMP to minimize the speed loss that occurs in motor when the
load requires an increase of torque and absorbed current.
Note: an excessive adjustment may cause instability.
f) Speed offset calibration
If, with potentiometer at zero speed, the motor rotates slowly (unless a min. reference
has been applied to the potentiometer negative end), carefully rotate trimmer (RV10) n
OFS in CCW direction and stop the motor.
Note: an excessive adjustment may introduce an initial not-sensitive area in the speed
reference adjustment scale.
MAINTENANCEMAINTENANCE
The drive maintenance is mainly a matter of periodical checking.
The first precautions against troubles due to malfunction, are the cleanliness of the
machine and its installation in an environment free of vibrations and not too hot. All this
will allow for a long life of all components.
A prompt attention to any trouble, even the smallest ones, detected during periodical
inspections, will certainly help for drive longlife and avoid expensive operation breaks.

15D1011B1.DOC−D1011B1.DOC
ELETTRONICA SANTERNO S.P.A.
ViaG.DiVittorio,3
40020Casalfiumanese(BO)Italia
Telefono+39542668611
Fax+39542666632
CapitaleSociale:L.1.100.000.000i.v.
C.C.I.A.203016-“M”BO000183
IscrizioneTribunaleBologna:n.18335
Cod.Fisc.00330410374-Part.IVA00504051202
Cod.IndentificativoIVAIntracomunitario:IT00504051202
EC DECLARATION OF CONFORMITY
Elettronica Santerno S.p.A.
Via G. Di Vittorio, 3 - 40020 Casalfiumanese (BO) - Italy
AS MANUFACTURER
DECLARE
UNDER OUR SOLE RESPONSABILITY
THAT THE MONODIRECTIONAL HALF-CONTROLLED SINGLE-PHASE AC/DC CONVERTER
OF AMS90/1 TYPE, AND RELATED ACCESSORIES,
TO WHICH THIS DECLARATION RELATES, APPLIED UNDER CONDITIONS SUPPLIED IN THE
USER’S MANUAL,
CONFORMS TO THE FOLLOWING STANDARDS OR NORMATIVE DOCUMENTS:
EN61800-3 Adjustable speed electrical power drive systems.
Part 3: EMC product standard including specific test methods.
EN55011
Limits and methods of measurement of radio disturbance characteristics of industrial,
scientific and medical (ISM) radio-frequency equipment.
EN61000-4-2 Electromagnetic compatibility (EMC). Part 4: Testing and measurement techniques.
Section 2: Electrostatic discharge immunity test. Basic EMC Publication.
EN61000-4-4 Electromagnetic compatibility (EMC). Part 4: Testing and measurement techniques.
Section 4: Electrical fast transient/burst immunity test. Basic EMC Publication.
EN61000-4-5 Electromagnetic compatibility (EMC). Part 4: Testing and measurement techniques.
Section 5: Surge immunity test.
EN61000-4-8 Electromagnetic compatibility (EMC). Part 4: Testing and measurement techniques.
Section 8: Power frequency magnetic field immunity test. Basic EMC Publication.
IEC1000-4-3 Electromagnetic compatibility (EMC). Part 4: Testing and measurement techniques.
Section 3: Radiated, radio-frequency, electromagnetic field immunity test.
FOLLOWING THE PROVISIONS OF ELECTROMAGNETIC COMPATIBILITY DIRECTIVE
89/336/EEC AND SUBSEQUENT AMENDMENTS 92/31/EEC, 93/68/EEC AND 93/97/EEC.
PLACE AND DATE OF ISSUE
Casalfiumanese, 01/10/1997 SIGNATURE
General manager
Ing. Pietro CASELLI

15D2011B1.DOC−D2011B1.DOC
ELETTRONICA SANTERNO S.P.A.
ViaG.DiVittorio,3
40020Casalfiumanese(BO)Italia
Telefono+39542668611
Fax+39542666632
CapitaleSociale:L.1.100.000.000i.v.
C.C.I.A.203016-“M”BO000183
IscrizioneTribunaleBologna:n.18335
Cod.Fisc.00330410374-Part.IVA00504051202
Cod.IndentificativoIVAIntracomunitario:IT00504051202
EC DECLARATION OF CONFORMITY
Elettronica Santerno S.p.A.
Via G. Di Vittorio, 3 - 40020 Casalfiumanese (BO) - Italy
AS MANUFACTURER
DECLARE
UNDER OUR SOLE RESPONSABILITY
THAT THE MONODIRECTIONAL HALF-CONTROLLED SINGLE PHASE AC/DC CONVERTER
OF AMS90/1 TYPE, TO WHICH THIS DECLARATION RELATES,
CONFORMS TO THE FOLLOWING STANDARDS OR NORMATIVE DOCUMENTS:
EN60146-1-1 Semiconductor convertors.
General requirements and line commutated convertors.
Part 1-1: Specifications of basic requirements.
IEC146-1-2 Semiconductor convertors.
General requirements and line commutated convertors.
Part 1-2: Application guide.
EN60146-1-3 Semiconductor convertors.
General requirements and line commutated convertors.
Part 1-3: Transformers and reactors.
IEC146-6 Semiconductor convertors.
Part 6: Application guide for the protection of semiconductor convertors against
overcurrent by fuses.
IEC664-1 Insulation coordination for equipment within low-voltage systems.
Part 1: Principles, requirements and tests.
IEC22G/22/CDV Power electronics.
Semiconductor power converters for adjustable speed electric drive systems.
General purpose adjustable speed d.c. drive systems.
EN60204-1 Safety of machinery. Electrical equipment of machines.
Part 1: General requirements.
EN60204-1
Amendment 1
Electrical equipment of industrial machines.
Part 2: Item designation and examples of drawings, diagrams, tables and
instructions.
EN60529 Degrees of protection provided by enclosures (IP Code).
prEN50178 Electronic equipment for use in power installations.
FOLLOWING THE PROVISIONS OF LOW VOLTAGE DIRECTIVE 73/23/EEC AND SUBSEQUENT
AMENDMENT 93/68/EEC.
LAST TWO DIGITS OF THE YEAR IN WHICH THE CE MARKING WAS AFFIXED: 97
PLACE AND DATE OF ISSUE
Casalfiumanese, 01/10/1997 SIGNATURE
General Manager
Ing. Pietro CASELLI

15D3011B1.DOC−D3011B1.DOC
ELETTRONICA SANTERNO S.P.A.
ViaG.DiVittorio,3
40020Casalfiumanese(BO)Italia
Telefono+39542668611
Fax+39542666632
CapitaleSociale:L.1.100.000.000i.v.
C.C.I.A.203016-“M”BO000183
IscrizioneTribunaleBologna:n.18335
Cod.Fisc.00330410374-Part.IVA00504051202
Cod.IndentificativoIVAIntracomunitario:IT00504051202
MANUFACTURER’S DECLARATION
Elettronica Santerno S.p.A.
Via G. Di Vittorio, 3 - 40020 Casalfiumanese (BO) - Italy
AS MANUFACTURER
DECLARE
UNDER OUR SOLE RESPONSABILITY
THAT THE MONODIRECTIONAL HALF-CONTROLLED SINGLE-PHASE AC/DC CONVERTER
OF AMS90/1 TYPE,TO WHICH THIS DECLARATION RELATES, APPLIED UNDER
CONDITIONS SUPPLIED IN THE USER’S MANUAL,
CONFORMS TO THE FOLLOWING STANDARDS OR NORMATIVE DOCUMENTS:
EN60204-1 Safety of machinery. Electrical equipment of machines.
Part 1: General requirements.
EN60204-1
Amendment 1
Electrical equipment of industrial machines.
Part 2: Item designation and examples of drawings, diagrams, tables and instructions.
AND MUST NOT BE PUT INTO SERVICE UNTIL THE MACHINERY INTO WHICH IT IS TO BE
INCORPORED HAS BEEN DECLARED IN CONFORMITY WITH THE PROVISIONS OF
MACHINERY DIRECTIVE 89/392/EEC AND SUBSEQUENT AMENDMENTS 91/368/EEC,
93/44/EEC AND 93/68/EEC.
PLACE AND DATE OF ISSUE
Casalfiumanese, 01/10/1997
SIGNATURE
General Manager
Ing. Pietro CASELLI
This manual suits for next models
5
Table of contents
Other Elettronica Santerno Media Converter manuals
Popular Media Converter manuals by other brands

TRENDnet
TRENDnet TFC-110MST Specifications

Microcyber
Microcyber NCS-MH105 user manual

Progressive Dynamics
Progressive Dynamics PD4635 Installation and operation guide

Polytron
Polytron HDI 32 C user manual

Lantronix
Lantronix C3210-10 Series installation guide

DVTEL
DVTEL Ioimage trk-101 installation manual