Elmo FXUP User manual

FXUP
FXPRO expansion unit,
with integrated power supply unit
090010932
USER MANUAL
Declaration of performance
nº 0051 – CPR – 0455
15 Standards
EN54-2:2007, EN54-4:2007

FXUP - USER MANUAL - 090010932
elmospa.com
2
FOREWORD
FOR THE INSTALLER:
Please follow carefully the specifications relative to electric and security systems realization further to the manufacturer’s
prescriptions indicated in the manual provided.
Provide the user the necessary indication for use and system’s limitations, specifying that there exist precise specifications and
different safety performances levels that should be proportioned to the user needs. Have the user view the directions indicated
in this document.
FOR THE USER:
Periodically check carefully the system functionality making sure all enabling and disabling operations were made correctly.
Have skilled personnel make the periodic system’s maintenance. Contact the installer to verify correct system operation in case
its conditions have changed (e.g.: variations in the areas to protect due to extension, change of the access modes, etc.)
-------------------------------
This device has been projected, assembled and tested with the maximum care, adopting control procedures in accordance with
the laws in force. The full correspondence to the functional characteristics is given exclusively when it is used for the purpose it
was projected for, which is as follows:
FXPRO expansion unit, with integrated power supply unit.
Any use other than the one mentioned above has not been forecast and therefore it is not possible to guarantee the correct
functioning of the device. Similarly, any other use of this technical manual other than the one it has been compiled for—that is: to
illustrate the devices technical features and operating mode—is expressly prohibited.
The manufacturing process is carefully controlled in order to prevent defaults and bad functioning. Nevertheless, an extremely low
percentage of the components used is subjected to faults just as any other electronic or mechanic product. As this item is meant
to protect both property and people, we invite the user to proportion the level of protection that the system offers to the actual risk
(also taking into account the possibility that the system was operated in a degraded manner because of faults and the like), as
well reminding that there are precise laws for the design and assemblage of the systems destined to these kind of applications.
The system’s operator is hereby advised to see regularly to the periodic maintenance of the system, at least in accordance
with the provisions of current legislation, as well as to carry out checks on the correct running of said system on as regular
a basis as the risk involved requires, with particular reference to the control unit, sensors, sounders, dialler(s) and any other
device connected. The user must let the installer know how well the system seems to be operating, based on the results of
periodic checks, without delay.
Design, installation and servicing of systems which include this product, should be made by skilled staff with the necessary
knowledge to operate in safe conditions in order to prevent accidents. These systems’ installation must be made in accordance
with the laws in force. Some equipment’s inner parts are connected to electric main and therefore electrocution may occur
if servicing was made before switching off the main and emergency power. Some products incorporate rechargeable or non
rechargeable batteries as emergency power supply. Their wrong connection may damage the product, properties and the
operator’s safety (burst and fire).
According to Directive 2012/19/EU on the Waste of Electric and Electronic Equipment
(WEEE), it is here specied that this Electrical-Electromechanic Device started to be
commercialized after 13th August 2005, and it shall be disposed of separately from or-
dinary waste products.
DISPOSAL INSTRUCTIONS
This product needs batteries for correct functioning. Exhausted batteries have to be delivered
to dumping grounds authorized for battery collection. The materials used for this product are very
harmful and polluting if dispersed in the environment.
IT08020000001624

090010932 - USER MANUAL - FXUP
elmospa.com
3
1. INTRODUCTION
FXUP is an expansion unit for FXPRO fire control units. Its operating menus can be accessed using emulation from a FXPRO
unit or from a different control panel (Selected unit button).
This manual explains how to use the FXUP expansion unit.
It is part of the technical documentation of the unit, together with the technical manual, the programming manual and the
quick guide.
The FXUP unit can be operated from a PC station, using the GLOBALPRO software.
The user of the plant must not open the metallic box. Should the need arise, get in touch with the installer or an authorized
maintenance operator.
1.1 Definitions
Master and Slave: the main control panel, managing data exchange between control panels, and any other control panel.
1.2 Marginal symbols key
¤: Optional functions, whose requirements are included in the EN54 standard.
‡: Functions that refer to different parts of the EN54 standard.
2. USER INTERFACE
FXUP has no user interface of its own. To use it, it has to be part of a local network of a FXPRO unit. During emulation
mode, the Selected unit LEDs show the alarm, fault and operativity statuses of FXUP:
LED MEANING
ALARM (red) Glowing or
blinking One or more devices of this unit sent an alarm signal, or an EVACUATE command has been issued.
SILENCE SOUNDERS Glowing A user has issued a temporary sounders silencing request.
SILENCE BUZZER Glowing A user has issued a temporary buzzer silencing request.
DELAYED MODE Glowing Delayed mode is ON.
TEST Glowing Test mode is ON.
MAINS (green) Glowing Mains supply is working.
DISABLE – COMMON Glowing At least one element has been disabled.
DISABLE – DEVICES Glowing At least one device has been disabled.
DISABLE – OUTPUTS Glowing At least one zone has been disabled.
DISABLE – BELLS Glowing At least a sounder on any loop or bell output has been disabled.
COMMON FAULT Blinking At least one element has issued a fault signal.
FAULT – DEVICES Blinking At least one device has issued a fault signal.
FAULT – BELLS Blinking At least a sounder on any loop or bell output issued a fault event.
FAULT – CPU Glowing This unit has a CPU fault.
FAULT – SUPPLY Blinking At least one power supply has issued a fault event.
Emulation, level 1 (chap. 3.2) Emulation, level 2 (chap. 3.2)
During acknowledgement time, starts investigation
time. Otherwise, starts the evacuate procedure for
the emulated unit.
Starts the evacuate procedure for the emulated unit.
Silences the buzzer of the emulated unit.
If, after pressing this button, the buzzer keeps ringing, it might be the panel’s buzzer that’s ringing. Browse to the panel
managing screens and try again.
Immediately silences sounders of the emulated unit (beware: some
relay outputs are not classied as sounders even if they control
sounder devices).
If the emulated unit’s buzzer is off, pressing this button starts that
unit’s reset.

FXUP - USER MANUAL - 090010932
elmospa.com
4
3. FRONT PANEL BROWSING
3.1 Access to emulated unit screens
To get to the screens belonging to the unit from a control panel of the network:
• press the Selected unit button.
• key in the digit that corresponds to this unit (the same used in the U1–U8 LED columns numbering).
3.2 Access levels and passwords
FXUP screens use the following access levels:
• level 1 (public) – No password is required. Encompasses welcome, alarm and fault screens.
The Buzzer silence, Selected unit and Unit group buttons are active.
During DelayeD moDe (chap. 4.1.3), the Evacuate button starts the Investigation timer.
To access the user menu, press ESC.
• level 2 (user) – L2* password protected menu (default: 1234).
• level 3 (programming/service) – L3* password protected menu. Press ESC to exit.
To access the user menu:
The Reset pRoceDuRe (chap. 4.4) and the evacuate pRoceDuRe (chap. 4.5) ask for a L2 password.
3.2.1 User identification and lowering the access level
The L2 password of each user is a personal identification number (PIN) which usage is saved in the events log, allowing to
trace who gave each command. To avoid unauthorized users using the password-protected menus after a password has
been used, always manually lower the access level:
• choose RetuRn to l1 level from the main menu or wait for the automatic time-out (settable as described in the
programming manual for unit menus).
3.3 Screen structure and function buttons meaning
Emulated and panel screens are structured as in the example on the right:
• three lines of text with instructions or informations;
• a fourth line reminds what the 4 function buttons in the first row of the keypad mean.
The more used meaning are:
• ESC, to go back to the previous menu or page;
• -> and <-, to select the following or preceding element (if one is not valid, it disappears);
• ENT, to confirm a choice, for instance to access the selected entry or to save the data you just modified.
3.4 Screen types
Selection menus contain a (scrolling if more than three) list of entries
• -> and <- move the > cursor, pointing at the currently selected entry.
• ENT gives access to the selected submenu or function, ESC goes back to the previous menu.
• If there is no previous menu (because you are browsing the main menu), ESC does nothing:
use Exit to level 1 to close the menu.
• The current password level appears between -> and <-.
Sometimes, this manual shows all the entries of a scrolling menu, as if the display had
more than four rows.
An editing menu has a list of entries, each paired to a binary value (e.g. YES/NO).
• Press ENT to change the selected entry’s value, immediately saving the new one. Press
ESC to go back to the previous menu.
Editing pages show some data, without allowing to modify it yet.
‡ ¤
ESC ENT
n nnn
L2 PASSWORD
Line of text 1
Line of text 2
Line of text 3
ESC -> <- ENT
Submenu 1
>Submenu 2
Function A
Function B
Submenu 3
Exit to level 1
ESC -> L2 <- ENT
Zone1 ON
>Zone2 OFF
Zone3 OFF
ESC -> Ed <- ENT

090010932 - USER MANUAL - FXUP
elmospa.com
5
• If this data is related to one element of a list (e.g. the type of a loop address or the time slots for one weekday), ->
and <- let you visualize the same data for the previous or following element (a different address, a different weekday).
• Press ESC to go back to the menu, ENT to start editing mode (the “Ed” writing appears on the fourth line of text).
If the datum has to be chosen from a list, -> and <- let you browse the built-in options.
If the datum has to be typed, -> and <- move the text cursor _, whose position is where the typed character will be
inserted. If the field accepts alphanumeric characters (instead of only numbers), press a single button several times to
rotate through all the symbols written on it.
Some editing mode screens have different data in them, e.g. a weekday (chosen from a list) and a date (typed). In this
case, it’s possible to modify the first kind of data, then press ENT to save those data and to get to modify the second type.
• Press ESC to go back to the editing page without saving, ENT to save and go back.
4. UNIT USAGE
This chapter details the contents of the menus of FXUP and the procedures that are needed to manage the fire detection
system.
If the keypad stays idle for the time set in the programming menu and marked in the last page by the installer, the access
level drops to L1 and the LCD shows the welcome screen of the emulated unit.
4.1 Basic concepts
4.1.1 Devices and addresses
Each device on a loop is identified by its loop number and by an address in the 1–254 range. Some devices have several
addresses, each set to a specific function of that device.
Some FXEXPEV2 devices have two sub-addresses (e.g. INPUT A and INPUT B).
The display and print menus only show the analogue value of the single sub-address chosen in the programming menus.
4.1.2 Zones
The applicable standards have the devices on a loop divided in zones, geographical partitions of the monitored environment.
If a fault happens in a zone, it is possible to disable it from the Disablement »Zone (chap. 5.2.1) menu and, after identifying
the faulty device thanks to its address, proceed with the maintenance operations.
4.1.3 Delayed mode
The contents of this chapter are only valid if DelayeD moDe (chap. 5.2.4) is enabled and only during the time slots set while
programming the unit and marked on the last page of this manual.
When the unit receives an alarm input, the appropriate output activation only happens after a countdown, shown on the
unit’s welcome screen.
During this delay, the operator can check for false alarms and, if need be, run a Reset pRoceDuRe (chap. 4.4) before the
outputs activate.
The countdown starts from a value called Acknowledgement time. The unit’s buzzer rings to draw the operator’s attention.
If he’s nearby he can press the Evacuate button at access level 1 to restart the timer from a value called Investigation time.
With standard settings, if the alarm signal comes from a call point or if a call point is pressed while the countdown is active,
outputs are immediately activated.
If the short time mode (not covered by the EN 54-2 standard) is active, when the alarm signal comes from a manual call
point, the countdown starts from the Short time (lower than both Acknowledgement and Investigation times) instead.
If the short time mode is active, when a second alarm signal (whether from a call point or not) is detected while the
countdown is running, the countdown value immediately drops down to the Short time value.
Acknowledgement, Investigation and Short time can be set in the programming menu.
Bomb and Prealarm events, events coming from zones excluded during programming and the evacuate pRoceDuRe (chap. 4.5)
bypass Delayed mode and immediately activate their outputs (the Prealarm event does not interrupt the delayed mode).

FXUP - USER MANUAL - 090010932
elmospa.com
6
Examples (Acknowledgement time: 200 s; Inspection time: 400 s; Short time: 100 s):
Short time is Off:
An alarm event is generated by a non-call-point device from an enabled zone: the countdown starts at 200 s.
A non-call-point device generates another alarm event: the timer keeps going.
The operator presses Evacuate: the countdown starts again from 400 s.
Someone hits a manual call point: outputs immediately activate.
Short time is On:
Someone hits a call point: the countdown starts from 100 s.
The operator presses Evacuate: the countdown starts again from 400 s.
During inspection time, before the countdown reaches 100, a new alarm event is generated: the countdown drops to 100 s.
Short time is On:
An alarm event is generated by a non-call-point device from an enabled zone: the countdown starts at 200 s.
During acknowledgement time, before the timer reaches 100, a new alarm event is generated: the timer drops to 100 s.
The operator presses Evacuate: the countdown starts again from 400 s.
During inspection time, before the countdown reaches 100, a new alarm event is generated: the countdown drops to 100 s.
4.1.4 System events
The Display and Print menus both let you see a list of system events. These events, listed in the system events table (chap.
7), are generated by some conditions such as the following:
• a signal from a loop device (e.g. Gas leak);
• specific events in the usage and programming screens (e.g. Zone disabled or Password access);
• pressing some buttons on the panel (e.g. Sounders alarm, generated by the evacuate procedure);
• a different system event is generated (e.g. Sounders alarm generates a Fire event).
Some specific system events can be used to activate outputs (e.g. by default, the Fire event activates all bell outputs, the
relay 2 output and every output of the loop).
4.2 Main screen
When no system messages are shown, the main screen of the unit shows the date and time,
the 5-digit ID used by GLOBALPRO to identify the unit and the other data shown on the right.
The star in the third row is only shown if some outputs have been manually activated from the
outputs activation (chap. 5.5) menu.
When this screen is visible, any keypad button except Evacuate and Silence Buzzer lead to a
password request to get into the user menu. Evacuate leads to a password request to activate
the evacuate pRoceDuRe (chap. 4.5).
LU 06/07/15 10:10:24
00000 Cust._Name
Installer_Name__ *
Telephone_Number
4.3 Unit screens system messages
When there are active alarm or fault events, the main screen changes to show some which
loop, address and zone generated those events.
• The first line holds the loop L, the system event that caused the fault or alarm message
and the involved zone.
• The second line contains the name and number of the address that generated the event.
• The third line hosts the name of the affected zone and the number of the last chronologically
zone affected by alarms.
• The last row shows the total number of alarm affected zones T and the current/total
message number for faults or for alarms. Use -> and <- to browse messages.
L1-DEVICE FAULT Z004
ADDRESS TEXT -A013
ZONE TEXT -Z007
ESC -> <- 02/03
L1-FIRE Z001
ADDRESS TEXT -A003
ZONE TEXT -Z007
ESC ->T004<- 03/07
The existing standards mandate absolute priority for alarm messages, included hiding all other messages while alarm
messages are present. To see these other messages, browse to the vista » messages cleaReD (chap. 5.3.1) menu.
While system message screens are active, press ESC to access the usage and programming menus.

090010932 - USER MANUAL - FXUP
elmospa.com
7
4.4 Reset procedure
• Get to the unit’s main screen.
ESC ENT
n nnn
L2 PASSWORD
To go back to level 1: press ESC, then press -> to move the > cursor to the last entry (Exit to level 1), then press ENT.
To go back to the welcome screen of the panel, go back to level 1 as described above, then press Selected unit,.
4.5 Evacuate procedure
• Get to the unit’s main screen.
ENT
n nnn
L2 PASSWORD
To go back to the welcome screen of the panel, press Selected unit, 0.
4.6 Unit screens user menu
The following chapter illustrates the user menu entries, mapped here:
Program
User menu
Disablement
Zone
Device
Unit outputs
Delayed mode
Display
Messages cleared
Print
Address
Type
Events filter
Events filter
Date
Class
Origin
Device
Outputs ON
Service
Mode
Devices filter
Outputs activation
Test
LED
LCD
see programming
manual
Outputs
Unit outputs
Loop outputs
Events Date
Class
Origin
Exit to level 1

FXUP - USER MANUAL - 090010932
elmospa.com
8
5. USER MENU
The Program entry allows access to the programming menu, protected by a L3 password.
Press ESC to exit the password request screen.
5.1 Test
The Test LED will glow while the functions of this menu are active.
5.1.1 LED
Once in this function, press ENT again to start the test: every LED in the Unit group and
Selected unit areas will light up for some seconds, except red alarm LEDs.
To test red alarm LEDs, test bell output D (chap. 5.1.3.1).
To test the 8 LED columns, simulate an alarm or a fault on the corresponding unit.
Lamp Test
Terminal ON Sequence
5.1.2 LCD
All LCD cells get filled with a same character.
Every second, the next character in the set is shown, in rotation.
Press ESC (the first function button on the left) to go back to the menu.
00000000000000000000
00000000000000000000
00000000000000000000
00000000000000000000
5.1.3 Outputs
5.1.3.1 Unit outputs
This function lets you select a unit output using the -> and <- buttons, pressing ENT to
manually activate or deactivate it. Activating bell output D lets you test the backup alarm
propagation line and the red alarm LEDs in the front panel (chap. 5.1.1).
Remember that the outputs might disturb the peace.
Press ESC to quit this function, deactivating (OFF) any output that had been activated manually.
RELAY 2 OFF
>BELL A ON
BELL B OFF
ESC -> <- ENT
5.1.3.2 Loop outputs
This function works like the previous one, but you need to choose a loop first (type the
corresponding digit and press ENT to confirm).
The “Invalid value” message pops up if the loop has no outputs.
The “Not Saved” message pops up if the typed number doesn’t match an existing loop.
It is possible to type a new digit and press ENT even while the messages are active.
L1A001 ON
>L1A005 OFF
L1A012 ON
ESC -> <- ENT
5.2 Disablement
The functions in this menu enable (EN) or disable (DIS) entire zones, single devices or unit outputs. Their default value is
ENabled; when they get DISabled, the General disable LED and the appropriate disable LEDs light up.
This menu also contains the function to activate/deactivate the delayed mode, which is deactivated by default.
5.2.1 Zone
Devices from a disabled zone can’t generate or receive alarm or fault signals.
Chose the zone to enable/disable using -> and <-.
Press ENT to start editing mode, use -> and <- to decide if the zone has to be enabled or
disabled, then press ENT again to save and quit editing mode.
ZONE1 EN
>ZONE2 DIS
ZONE3 EN
ESC -> <- ENT
¤

090010932 - USER MANUAL - FXUP
elmospa.com
9
5.2.2 Device
A disabled device generates no alarm or fault events and never activates, but it keeps sending
its analogue value during the polling (the cyclical interrogation of all addresses made by the
loop board). Key in a loop number (as in 5.1.3.2) and press ENT to display the list of that loop’s
devices. Disable/enable them as with zones.
Disabling every device of a zone also disables the zone itself. If such a Zone (chap. 5.2.1) is
enabled again, all of its devices get automatically enabled.
L1A001 EN
>L1A002 DIS
L1A003 EN
ESC -> <- ENT
5.2.3 Unit outputs
The relay 2 and bell output A, B and C can be disabled.
A disabled unit output never activates and stops being supervised.
To enable or disable an output, use -> and <- to select it and press ENT.
RELAY 2 ON
>BELL A ON
BELL B ON
ESC -> <- ENT
5.2.4 Delayed mode
This function enables/disables the DelayeD moDe (chap. 4.1.3), making it operative for each zone
enabled from the programming menu.
Press ENT to switch to editing mode and use -> or <- to toggle the mode On and Off.
Delayed Mode
Status: OFF
ESC -> Ed <- ENT
If the delayed mode is enabled (“Status: ON”), the new Short Time line appears.
Press ENT again to edit this new line, where the new option can be turned On or Off.
Delayed Mode
Status: ON
Short Time: OFF
ESC -> Ed <- ENT
5.3 Display
5.3.1 Messages cleared
The existing standards mandate absolute priority for alarm messages, included hiding all other messages while alarm
messages are present. This function lets you look at the hidden messages.
A new alarm message, idling for 20 seconds or pressing ENT will bring back the alarm messages.
Alarm and fault messages are detailed in unit scReens system messages (chap. 4.3).
5.3.2 Events filter
5.3.2.1 Date
The events (chap. 5.3.3) function will only display the saved events whose date falls in the range
set through this editing page.
The default range is from 1st January 2000 to 31st December 2099.
EVENTS
from 01-01-00
to 31-12-99
ESC -> Ed <- ENT
5.3.2.2 Class
The events (chap. 5.3.3) function will only display the saved events whose class is set to On in
this editing page.
The system events table (chap. 7) details the system event classes.
ALARM YES
>FAULT NO
SYSTEM YES
ESC -> <- ENT
5.3.2.3 Origin
The events (chap. 5.3.3) function will only display the saved events whose origin is set to On
in this editing page.
The system events table (chap. 7) details the system event origins.
DEVICE YES
>UNIT NO
LOOP YES
PERIPHERAL YES
ESC -> <- ENT
¤
‡

FXUP - USER MANUAL - 090010932
elmospa.com
10
5.3.3 Events
This function lets you look at the events log of a unit, which is the list of all the system events
that occurred on the unit since the first one (the system reset). The log holds up to 4000
entries, memorized in a circular event queue: once the end of the queue is reached, new events
overwrite the oldest ones.
02/01/15 18:55
SYSTEM RESET
ESC -> <- 0000
Different events are displayed along different data but some data is the same for every event: the date and time (on the
first line) and their progressive number (on the low right). The second row describes the event, the third hosts additional
parameters. Use -> and <- to browse the stored events.
The events filteR (chap. 5.3.2) functions can be used to only visualize a subset of the events log.
5.3.4 Device
This function asks for a device’s loop and address.
-> and <- move the text cursor.
Press ENT to see the data of that address.
L:# A:###
ESC -> <- ENT
The first line of the following page has the loop L, the address A, the zone Z and the real time
analogue value of the selected device (or the temperature in °C for heat sensors on FXEXPEV2).
This value is updated in real time even when the device or its zone are disabled: only the
device’s fault prevents the updates. The second line has the type or model of the device, the
third displays the 16-characters device text.
Use -> and <- to display the following/previous device.
L1A001Z002 An:06
TP: OPTICAL SMOKE
“DEVICE NAME ”
ESC -> <- ENT
5.3.5 Outputs ON
Key in a loop number to display a list of every output device on that loop, each one showing
if it’s been MANually or AUTOmatically activated. If the loop has no output devices, the “No
output on” message appears. MANually activated outputs are those activated using the outputs
activation (chap. 5.5) menu, AUTOmatically activated ones are activated by the unit.
L1 A001 MAN
>L1 A002 AUTO
L1 A003 AUTO
ESC -> <-
If an output has been AUTOmatically activated because of an alarm event or because of a input monitoring, they can’t be
stopped manually. If a MANually activated output is later AUTOmatically activated, it is seen as AUTOmatically activated (it
gets the AUTO label and it can’t be manually disabled).
Automatic activations are logged with the “On output” event.
Manual activations and deactivations are logged with the “Output on/m” and “Output off/m” events.
The “On output” event is due to an Evolution input monitoring if preceded by an “Input set” event, otherwise it’s due to a
system or logic event or to a pattern.
5.3.6 Service
Key in a loop number to see a scrolling list of the sensors that reached the service threshold
set in the programming menu.
If no sensor has reached that threshold, the “No sensors under maintenance” message appears.
No sensors
under maintenance
ESC
5.4 Print
5.4.1 Mode
Use -> and <- to choose a functioning mode for the printer, press ENT to confirm.
• Offline (default): the printer is inactive.
• Events log: print events as soon as they happen.
• Events: print the events log, applying the events filteR (chap. 5.4.3).
• Devices: print the device list, applying the Devices filteR (chap. 5.4.2).
• Service: print the list of all sensors who reached the service threshold.
To stop the printer, set the mode to Offline.
MODE
-> OFFLINE
ESC -> Ed <- ENT
¤

090010932 - USER MANUAL - FXUP
elmospa.com
11
5.4.2 Devices filter
5.4.2.1 Address
This function lets you set a loop-and-addresses range for the printer.
To print a single address, select it as starting and ending value of the range.
By default, the filter includes every address: L1A001÷L5A254
Loop: 1 - 5
Id: 001 - 254
ESC -> Ed <- ENT
5.4.2.2 Type
This function shows different device types and lets you choose which ones to print (Yes) or
ignore (No).
CALL POINT YES
>IONISATION NO
HEAT YES
ESC -> <- ENT
5.4.3 Events filter
This menu includes the Date, Class and Origin entries, which operation is similar to the functions with the same name in
Display » events filteR (chap. 5.3.2).
5.5 Outputs activation
This function is used to manually activate or deactivate output modules. Key in the loop number
and press ENT: a list of all output modules appears, with the rightmost column reading On if
the output is active because of a manual activation, Off it is deactivated or automatically active.
To activate/deactivate an output, use -> and <- to select it and press ENT.
L1A001 OFF
>L1A002 ON
L1A003 OFF
ESC -> <- ENT
If the output is already active (because of an event, a pattern or an input monitoring), the status can’t be changed from Off.
If a manually activated (On) output gets activated by an event/pattern/monitoring, its status goes back to off.
If there is at least one manually activated output, the main screen of the unit will show a star (“*”) at the end of the third
line and the test LED will be blinking.
A unit reset deactivates all active outputs, including manually activated ones.
5.6 Exit to level 1
This function quits the main menu of the unit and set the access level back to 1.

FXUP - USER MANUAL - 090010932
elmospa.com
12
6. DEVICE FEATURES
This list, containing all AS and Evolution devices currently available, is not final.
AS devices Evolution devices Address type (in order) Used addresses
1IASBOBX
MTB Input Module 1
4IASBOX 4 Input Modules 4
1OASBOX Output Module 1
4OASBOX 4 Output Modules 4
4I4OASBOX 4 Output Modules + 4 Input Modules 8
MCM-AS3B
MCMAS5 Zone Module 1
SCM-AS2B
SCMAS5
VCT-03NTAS
RFP-AS2B
EV-ABS
EV-HIOP-SB
EV-AV
EV-SM
Bells Control Module 1
NAM-ASG Ionisation Smoke Sensor 1
ST-PY-AS EV-P
EV-DP Optical Smoke Sensor 1
ST-H-AS
EV-H/A1R
EV-H/CS
EV-UV
Heath Sensor 1
ST-NCP-AS2B
ST-NCP-EN2
ST-NCP-IP
EV-MCP Call Point 1
EV-PH Optical Smoke Sensor + Heat Sensor 2
EV-AIN1 Detector 1
EV-AIO21
Dip-switch set to 1 Detector 1
Dip-switch set to 7 Output Module + 2 Input Modules 3
Dip-switch set to 9, 10
or 12 Output Module 1
Dip-switch set to 13 or
15 Output Module + Input Module 2
EV-AIN2
Dip-switch set to 1, 4
or 7 Detector 1
Dip-switch set to 2 2 Input Modules 2
Dip-switch set to 8 or
14 Input Module 1
2DASBOX 2 Output Modules + 2 Input Modules 4
4DASBOX 4 Output Modules + 4 Input Modules 8
2I1OASBOX Output Module + 2 Input Modules 3
1I1OASBOX Output Module + Input Module 2
1DASBOX Output Module + Input Module 2
1D1IASBOX Output Module + 2 Input Modules 3
Devices on FXEXPEV2 always use a single address which is not associated to any type.

090010932 - USER MANUAL - FXUP
elmospa.com
13
7. SYSTEM EVENTS TABLE
System events are displayed in the system messages and are saved to the events log.
Their class and origin can be used to filter events for log visualization or printing purposes.
Event message Class Origin Global event Event message Class Origin
Sounders alarm Alarm Panel Fire Closed contact Control² Device
Fire Alarm Device Reopen contact³ Control² Device
Bomb Alarm Device Open contact Control² Device
Safety Alarm Device Reclosed contact³ Control² Device
Help Alarm Device Open door Control² Device
Technologic Alarm Device Closed door³ Control² Device
Gas leak Alarm Device Door in closing Control² Device
Water leak Alarm Device Reopen door³ Control² Device
Prealarm Alarm Device Ventilation on Control² Device
Dev. alarm Alarm Device Ventilation off³ Control² Device
Device fault Fault Device Fault Input on System Device
ID conflict Fault Device Fault Input off System Device
Fault Fault Device Fault Device disable System Panel
O/C circuit Fault Device Fault Device enable System Panel
24 V fault Fault Device Fault Out on System Panel
Not saved Fault Device Fault Out off System Panel
Wrong type Fault Device Fault Out on/m System Panel
Unknown Fault Device Fault Out off/m System Panel
Cable break Fault Device Fault Out pulse System Panel
Cable short Fault Device Fault Out pulse/alert System Panel
Output stuck Fault Device Fault Zone omit System Panel
Shortcirc. loop Fault Loop Fault Zone enable System Panel
Open loop Fault Loop Fault Relay omit System Panel
Flash error Fault Loop Fault Relay enable System Panel
RAM error Fault Loop/Panel Fault Password access System Panel
Open pos loop Fault Loop Fault Delayed mode en. System Panel
Open neg loop Fault Loop Fault Delayed mode dis. System Panel
Short “A” loop Fault Loop Fault Temp. silence System Panel
Short “B” loop Fault Loop Fault Buzzer silence System Panel
Short not detect. Fault Loop Fault Panel reset System Panel
Comm. error Fault Device/Loop Fault PC connect System Panel
No data Fault Device/Loop/Peripheral Fault PC disconnect System Panel
Open circuit Fault Panel Fault Begin PC prog. System Panel
Short circuit Fault Panel Fault End PC prog. System Panel
Inner flash error Fault Panel Fault Phase 1 delayed System Panel
Extern flash error Fault Panel Fault Phase 2 delayed System Panel
Modem fault Fault Panel Fault Exit to L1 System Panel
No loop saved Fault Panel General Fault Exit to L2 System Panel
LOAD fuse fault Fault Peripheral General Fault Time out L2 System Panel
CPU fuse fault Fault Peripheral General Fault Time out L3 System Panel
Shortcirc. earth-GND Fault Peripheral General Fault Maintenance System Panel
Shortcirc. earth-POS Fault Peripheral General Fault Multiple alarms System Panel
Battery fault Fault Peripheral Empty battery¹ Panel start System Panel
Empty battery Fault Device/Peripheral General Fault System reset System Panel
Mains fault Fault Device/Peripheral General Fault DST end program System Panel
Battery overvolt Fault Device/Peripheral General Fault DST start program System Panel
No battery Fault Device/Peripheral General Fault
¹Battery fault activates Low battery, which in turn activates General Fault. ²Control events are logged, but never shown as active events.
³This event is written to the logs when, after a device generated the event listed in the previous row of this table, no device in the same unit
generates that event anymore.

FXUP - USER MANUAL - 090010932
elmospa.com
14
8. CENTRAL BOOKLET
Copy according to your needs. File in two copies, one for the installer and one for archive.
Installing company:
Address:
Telephone number:
Installer engineer:
Telephone number:
Installation date:
Action # Date / time Identified failure Remedial action taken Time used Signature

090010932 - USER MANUAL - FXUP
elmospa.com
15
9. SUMMARY
10. CERTIFICATIONS
1. INTRODUCTION ..............................................................3
1.1 Definitions ...................................................................3
1.2 Marginal symbols key.................................................3
2. USER INTERFACE ...........................................................3
3. FRONT PANEL BROWSING ............................................4
3.1 Access to emulated unit screens ...............................4
3.2 Access levels and passwords ....................................4
3.2.1 User identification and lowering the access level4
3.3 Screen structure and function buttons meaning.......4
3.4 Screen types ...............................................................4
4. UNIT USAGE....................................................................5
4.1 Basic concepts............................................................5
4.1.1 Devices and addresses .........................................5
4.1.2 Zones......................................................................5
4.1.3 Delayed mode ........................................................5
4.1.4 System events........................................................6
4.2 Main screen.................................................................6
4.3 Unit screens system messages .................................6
4.4 Reset procedure..........................................................7
4.5 Evacuate procedure....................................................7
4.6 Unit screens user menu..............................................7
5. USER MENU ....................................................................8
5.1 Test...............................................................................8
5.1.1 LED .........................................................................8
5.1.2 LCD.........................................................................8
5.1.3 Outputs...................................................................8
5.1.3.1 Unit outputs.......................................................8
5.1.3.2 Loop outputs.....................................................8
5.2 Disablement ................................................................8
5.2.1 Zone........................................................................8
5.2.2 Device.....................................................................9
5.2.3 Unit outputs............................................................9
5.2.4 Delayed mode ........................................................9
5.3 Display.........................................................................9
5.3.1 Messages cleared..................................................9
5.3.2 Events filter ............................................................9
5.3.2.1 Date ...................................................................9
5.3.2.2 Class..................................................................9
5.3.2.3 Origin.................................................................9
5.3.3 Events...................................................................10
5.3.4 Device...................................................................10
5.3.5 Outputs ON ..........................................................10
5.3.6 Service..................................................................10
5.4 Print ...........................................................................10
5.4.1 Mode.....................................................................10
5.4.2 Devices filter ........................................................11
5.4.2.1 Address ...........................................................11
5.4.2.2 Type .................................................................11
5.4.3 Events filter ..........................................................11
5.5 Outputs activation.....................................................11
5.6 Exit to level 1 .............................................................11
6. DEVICE FEATURES .......................................................12
7. SYSTEM EVENTS TABLE ..............................................13
8. CENTRAL BOOKLET .....................................................14
9. SUMMARY .....................................................................15
10. CERTIFICATIONS........................................................15
11. DATA SET BY THE INSTALLER...................................16
Global Security Solutions
EL.MO. spa
Via Pontarola 70
Tel. +39 049.9203333
IT-35011 Campodarsego (PD) www.elmospa.com
Fax. +39 049.9200306
CA.23.1109.1
DICHIARAZIONE
DI CONFORMITA’
E PRESTAZIONE (DoP)
DECLARATION OF
CONFORMITY and
PERFORMANCE (DoP)
N°. 0051-CPR-0455
EL.MO. spa
dichiara sotto la propria responsabilità che il prodotto / declares that the product:
FXPRO – FXUP - FXMASTER
Centrale di controllo e segnalazione incendio / Control and indicating Pannel for Fire detection
al quale questa dichiarazione di conformità e prestazione(DoP) si riferisce, è conforme alle seguenti norme:
to which this declaration of conformity and Performance (DoP) is reffered with the following:
EN 50130-4:2011
Sistemi d’allarme:Parte 4: Compatibilità elettromagnetica
Norma per famiglia di prodotto: Requisiti di immunità per componenti di sistemi antincendio,
antintrusione e di allarme personale.
Alarm systems:Part 4: Electromagnetic compatibility
Product family standard: Immunity requirements for components of fire, Intruder and social
alarm system
EN 61000-6-3:2007 Compatibilità elettromagnetica(EMC). Parte 6-3: Norme generiche – Emissione per gli
ambienti residenziali, commerciali e dell’industria leggera.
Electromagnetic compatibility (EMC). Part 6-3:Generic standards – Emission standard for
residential, commercial and light-industrial environments.
CEI EN 60950-1:2006
+A11:2009
Apparecchiature per la tecnologia dell’informazione - Sicurezza. Parte 1:Requisiti generali
Information technology equipment – Safety. Part 1: General requirements
EN-54-2:1997
+A1:2006
Sistemi di rilevazione e di segnalazione d’incendio(centr. Di controllo e segn.) Fire detection
and fire alarm system (control and indicating equipment).
EN-54-4:1997
+A1:2002
+A2:2006
Sistemi di rilevazione e di segnalazione d’incendio (app. di alimentazione)
Fire detection and fire alarm system (power supply equipment)
e quindi rispondente ai requisiti essenziali delle direttive:
and then in accordance with the following directives:
2004/108/CE Compatibilità elettromagnetica
Electromagnetic compatibility
2006/95/CE Sicurezza di bassa tensione
Low voltage security
1999/5/CE (R&TTE) Direttiva Europea apparati radio e apparecchiature terminali di telecomunicazione.
European Directive wireless equipment and telecommunication apparatus.
2011/65/UE (RoHS) Direttiva Europea sulla restrizione dell'uso di determinate sostanze pericolose nelle
apparecchiature elettriche ed elettroniche
European Directive
R
eduction of
H
azardous Substances
Regulation (EU)
N°. 305/2011
Regolamento (UE) N°.305/2011 del Parlamento Europeo e del Consiglio del 9 Marzo
2011, che fissa condizioni armonizzate per la commercializzazione dei prodotti da
costruzione e che abroga la direttiva 89/106/CEE del Consiglio
REGULATION (EU) No 305/2011 OF THE EUROPEAN PARLIAMENT AND OF THE
COUNCIL of 9 March 2011, laying down harmonised conditions for the marketing of
construction products and repealing Council Directive 89/106/EEC
Pagina/Page 1 di 2
Global Security Solutions
EL.MO. spa
Via Pontarola 70
Tel. +39 049.9203333
IT-35011 Campodarsego (PD) www.elmospa.com
Fax. +39 049.9200306
CA.23.1109.1
DICHIARAZIONE DI PRESTAZIONE (DoP) / DECLARATION OF PERFORMANCE (DoP)
Sistema1/Sistem1
Caratteristiche essenziali(Allegato ZA, Prospetto ZA.1)
Essential caracteristics(Annex ZA, Table ZA.1)
Prestazione
Performance
Specifiche tecniche armonizzate:
Harmonized Technical
Specification:
Note
Notes
EN54-2:1997
+A1:2006
EN54-4:1997
+A12002+A220
06
Prestazione di alimentazione
Performance of power supply
Pass NA OK
Affidabilità operativa
Operational reliability
Pass OK OK
Durabilità dell’affidabilità funzionale: resistenza termica
Durability of operational reliability: Temperature
resistance
Pass OK OK
Durabilità dell’affidabilità funzionale: resistenza vibrazioni
Durability of operational reliability: Vibration resistance
Pass OK OK
Durabilità dell’affidabilità funzionale: stabilità elettrica
Durability of operational reliability:Electrical stability
Pass OK OK
Durabilità dell’affidabilità funzionale: resistenza
all’umidità
Durability of operational reliability: Humidity resistance
Pass OK OK
Prestazioni in condizioni d’incendio
Performance under fire conditions
Pass OK NA
Ritardo di risposta(tempo di risposta)
Response delay (response time to fire)
Pass OK NA
NA: non applicabile/
not applicable
Campodarsego 29/03/2016
Pagina/Page 2 di 2

FXUP - FXPRO expansion unit, with integrated power supply unit - USER MANUAL
March 2016 edition - May 2016 rev. 090010932
Product specications as described above do not bind the manufacturer and may be altered without prior notice.
EL.MO. SpA Via Pontarola, 70 - 35011 Campodarsego (PD) - Italy
Tel. +390499203333 - Fax +390499200306 - Technical Ass. +390499200426 - www.elmospa.com - [email protected]
11. DATA SET BY THE INSTALLER
Delayed mode:
Start time End time List of devices not influenced by delayed mode
MO : :
TU : :
WE : :
TH : :
FR : :
SA : :
SU : :
Acknowledgement time __________
Inspection time __________
Reduced/Short time __________
Daylight savings time end (D/M) ____/_____
Daylight savings time start (D/M) ____/_____
Menu time-out: __________
This manual suits for next models
1
Table of contents
Other Elmo Computer Hardware manuals
Popular Computer Hardware manuals by other brands

Behringer
Behringer BASS V-AMP LX1B quick start guide

National Semiconductor
National Semiconductor DP8400 Application note

Synology
Synology RXD1219sas Hardware installation guide

HighPoint
HighPoint RocketRAID 3700 Series Quick installation guide

SIIG
SIIG NN-E20022-S1 installation guide

Ratoc Systems
Ratoc Systems CBU2 user manual