Mounting of WS1000 Style 1
Mounting of WS1000 Style • Version: 30.06.2020 • Technical changes and errors excepted. • Elsner Elektronik GmbH • Sohlengrund 16 • 75395 Ostelsheim • Germany • www.elsner-elektronik.de • Technical Service: +49 (0) 7033 / 30945-250
Brief Instruction
Mounting of WS1000 Style
Item numbers 60201-60204, 60206-60209 (WS1000 Style),
60214 (WS1000 Style-10 PF)
Warning, mains voltage! National legal regulations are to be
observed. Installation, inspection, commissioning and
troubleshooting of the device must only be carried out by a
competent electrician.
Notes on wireless equipment
When planning facilities with devices that communicate via radio, adequate radio
reception must be guaranteed. The range will be limited by legal regulation and
structural circumstances. Avoid sources of interference and obstacles between re-
ceiver and transmitter, that could disturb the wireless communication. Those
would be for example:
• Walls and ceilings (especially concrete and solar protection glazing).
• Metal surfaces next to the wireless participants (e. g. aluminium
construction of a conservatory).
• Other wireless devices and powerful local transmitters (e.g. wireless
headphones), which transmit on the same frequency. Please maintain a
minimum distance of 30 cm between wireless transmitters for that reason.
Preparing the installation location
The device must only be installed and used in dry, interior
spaces. Avoid condensation.
Cut-out dimensions for concealed box:
W = 248 mm +1 -0 | H = 165 mm +1 -0 | D = 84 mm
An external antenna can be connected in order to improve wireless communicati-
ons. During installation, a conduit 50 cm in length should be placed beneath the
recessed housing, in which the external antenna can be mounted (antenna dimen-
sions approx. 565 x 8 x 5, L × W × H in mm):
Preparing for installation
Wall-fitting
Cavity wall fitting
Assembling the control unit with concealed box
During electrical installation, please introduce all connection cables into the con-
cealed box through the lower or upper side wall. In the process, keep the individual
connection wires short to prevent long reserve loops.
After connecting the cables screw the security covering onto the concealed box.
The security covering must be fixed before the control is put
into operation! It prevents contact with current-carrying parts
in the concealed box.
By adjusting the mounting screws, the display unit will rest flat on the wall later
and be held by the magnets safely.
Connect the flat ribbon cable to the display and place the display unit on the con-
cealed box. The magnets must be attracted by the mounting screws considerably
and the display unit must rest tightly on the concealed box.
Structure of the connector board WS1000 Style
Structure of the connector board WS1000 Style-PF
The manual with additional information about commissioning,
functions and use of the controls WS1000 Style can be down-
loaded from www.elsner-elektronik.de in the menu area "Ser-
vice/Downloads".
Conduit angled diagonally dow-
nwards (for cable access from
above or below)
Conduit angled vertically downwards (only
for cable access from above!)
concealed concealed
45°
cable
cable
box box
M16 conduit, 50 cm in length M16 conduit,
50 cm in length
The display unit is held by magnets. Re-
move the front part from the concealed
box.
Caution: The display is connected
with a flat-ribbon cable to the circuit
board in the concealed box.
Loosen the plug so that the display unit
can be removed.
Remove all parts of the transportation
lock/packing.
The security covering in the concealed
box is attached with four screws: Loosen
the screws and take off the security cover-
ing.
Remove the circuit board from the con-
cealed box to be installed a keep it in a
place where it is protected from dirt. It
may never be exposed to dust or mo-
isture!
Place the concealed box in the wall so that
the arrows point upwards.
For fitting, screw the cover (board) on to
the concealed box with the enclosed
screws.
Clamp the concealed box to the wall with
the four enclosed screws.
Upon delivery, the pouch containing the
assembly screws can be found in the con-
trol unit’s concealed box.
oder
Adjust the screws of the magnetic moun-
ting with the enclosed template. Each of
the four screws must be adjusted individi-
ally in height.
When the edge of the template rests on
the wall surface (1), the template must
rest on the mounting screws as well (2).
1
1
2
1 Multifunctional output 1
(potential-free)
2 Multifunctional output 2 (pot.-free)
3 Multifunctional output 3 (pot.-free)
4 Multifunctional output 4 (pot.-free)
5 Outer conductor L1
6 Outer conductor L1
7-11Drive group 1-5
12-16Drive group 6-10
17 Mains connection
L/N/PE 230 V/50 Hz
18 Wall button 1 (terminals 1-3)
Wall button 2 (terminals 4-6)
Wall button 3 (terminals 7-9)
Wall button 4 (terminals 10-12)
19 Wall button 5 (terminals 1-3)
Wall button 6 (terminals 4-6)
Wall button 7 (terminals 7-9)
Wall button 8 (terminals 10-12),
20 Wall button 9 (terminals 1-3)
Wall button 10 (terminals 4-6),
21*Multifunctional input 1
(terminals 1-3)
Multifunctional input 2
(terminals 4-6)
22 Weather station (terminals 1-2)
Wire assignment: red = 1, black = 2,
yellow and white = not connected
23*Multifunctional input 3
(terminals 3-5)
Multifunctional input 4
(terminals 6-8)
24 Connector for flat-ribbon cable to
front board
25 Microfuse T6.3 A (Drive 1-5)
26 Microfuse T6.3 A (Drive 6-10)
27 Microfuse T630 mA
28 Slot KNX interface
* Supply voltage indoor sensor possi-
ble via MF inputs
(No. 21, terminals 1(+), 2(-) | 4(+),
5(-) and No. 23, term. 3(+), 4(-) | 6(+),
7(-)), max. 400 mA altogether.
20
12
34
5
6
78910 11
12 13 14 15 16 17
18
19
21 22 23
24
25
26
27
28
1 Multifunctional output 1
(potential-free)
2 Multifunctional output 2 (pot.-free)
3 Multifunctional output 3 (pot.-free)
4 Multifunctional output 4 (pot.-free)
5-9Drive group 1-5
10-14Drive group 6-10
15 Outer conductor L1
16 Outer conductor L1
17 Mains connection
L/N/PE 230 V/50 Hz
18 Wall button 1 (terminals 1-3)
Wall button 2 (terminals 4-6)
Wall button 3 (terminals 7-9)
Wall button 4 (terminals 10-12)
19 Wall button 5 (terminals 1-3)
Wall button 6 (terminals 4-6)
Wall button 7 (terminals 7-9)
Wall button 8 (terminals 10-12),
20 Wall button 9 (terminals 1-3)
Wall button 10 (terminals 4-6),
21*Multifunctional input 1
(terminals 1-3)
Multifunctional input 2
(terminals 4-6)
22 Weather station (terminals 1-2)
Wire assignment: red = 1, black = 2,
yellow and white = not connected
23*Multifunctional input 3
(terminals 3-5)
Multifunctional input 4
(terminals 6-8)
24 Connector for flat-ribbon cable to
front board
25 Microfuse T6.3 A (Drive 1-5)
26 Microfuse T6.3 A (Drive 6-10)
27 Microfuse T630 mA
28 Slot KNX interface
* Supply voltage indoor sensor possi-
ble via MF inputs
(No. 21, terminals 1(+), 2(-) | 4(+),
5(-) and No. 23, term. 3(+), 4(-) | 6(+),
7(-)), max. 400 mA altogether.
20
12
34
5 6 7 8 9
10 11 12 13 14
15
16 17
18
19
21 22 23
24
25
26
27
28
EN
Mounting of WS1000 Style 2
Mounting of WS1000 Style • Version: 30.06.2020 • Technical changes and errors excepted. • Elsner Elektronik GmbH • Sohlengrund 16 • 75395 Ostelsheim • Germany • www.elsner-elektronik.de • Technical Service: +49 (0) 7033 / 30945-250
Technical specifications Control Unit WS1000 Style
The product conforms with the provisions of EU directives.
Connection diagrams
Drive and MF outputs WS1000 Style (60201-60204, 60206-60209):
max. 400 W per motor output,
total max. 1.5 kW for all motor outputs
Drive and MF outputs WS1000 Style-PF (60214):
per motor output max. 5 A / 230 V
Motors with different voltages may be operated at the drive outputs (230 V AC and
low voltages SELV). The low voltage drives still correspond to the SELV specifica-
tions.
230 V and SELV must not be mixed at adjacent multifunction outputs (1 and 2 or 3
and 4). A mixed connection does not correspond to the SELV specifications. Either
230 V or extra-safety voltages are permitted here.
E.g. it is possible to connection SELV to MF outputs 1 and 2 and 230 V to MF out-
puts 3 and 4 (or vice versa).
Inputs WS1000:
Connection examples for multifunctional outputs
Connecting 230 V consumers to MF outputs
Connecting low-voltage consumers and potential-free contacts to MF
outputs
Housing Glass, plastic material
Colours • White/grey
• Dark grey/black
Mounting Flush/cavity wall
Dimensions Display front approx. 1270× 185 (W × H, mm),
mounting depth approx. 9 mm,
concealed box approx. 254 × 171 × 85 (W × H × D, mm)
Ambient temperature Operation 0…+55°C, Storage -30…+70°C
Ambient humidity 5...95% RH, avoid bedewing
Operating voltage 230 V AC, 50 Hz
Power consumption Stand-by max. 17 W
Loading capacity
drive outputs
230 V outputs:
per motor output, max. 400 W,
total max. 1.5 kW
Potential-free outputs (PF model):
per motor output max. 5 A / 230 V
Frequency
wireless channels
868.2 MHz
Protection category IP 20
multifunctional outputs 1-4 WS1000 Color/Style
multifunctional outputs 1-2 WS1 Color/Style
MF output 1 MF output 2 MF output 3
neutral conductor
heating valve 230 V
lamp 230 V
Contactor / Relay (on-site)
MF output 4
L1 / L1connector
ventilator 230 V
F1 6,3A slow-blow
radiant heater
multifunctional outputs 1-4 WS1000 Color/Style
multifunctional outputs 1-2 WS1 Color/Style
MF output 1 MF output 2 MF output 3 MF output 4
e.g. 24 V (ext.power supply)
heating valve 24 V
other consumers 24 V
signal contact for e.g.
rain / wind / frost /
smoke detector / alarm
thermostat
(on-site)
replacement

Other manuals for WS1000 Style

7

This manual suits for next models

8

Other elsner elektronik Control Panel manuals

elsner elektronik WS1 Style Series Reference guide

elsner elektronik

elsner elektronik WS1 Style Series Reference guide

elsner elektronik WS1000 Style User manual

elsner elektronik

elsner elektronik WS1000 Style User manual

elsner elektronik KNX WS1000 Color Reference guide

elsner elektronik

elsner elektronik KNX WS1000 Color Reference guide

elsner elektronik KNX eTR 208 User manual

elsner elektronik

elsner elektronik KNX eTR 208 User manual

Popular Control Panel manuals by other brands

Mircom FA-300 Series Installation and operation manual

Mircom

Mircom FA-300 Series Installation and operation manual

Ness D8X user manual

Ness

Ness D8X user manual

Fagor CNC 8070 operating manual

Fagor

Fagor CNC 8070 operating manual

SILENT KNIGHT SK-2224 Installation and operation manual

SILENT KNIGHT

SILENT KNIGHT SK-2224 Installation and operation manual

Sony RCP-750 Operation manual

Sony

Sony RCP-750 Operation manual

Sleipner PJC421 user manual

Sleipner

Sleipner PJC421 user manual

Siemens SINAMICS G130 operating instructions

Siemens

Siemens SINAMICS G130 operating instructions

Jackson Systems Comfort System Z-300-HP Wiring diagram

Jackson Systems

Jackson Systems Comfort System Z-300-HP Wiring diagram

Satel CA10 plus user manual

Satel

Satel CA10 plus user manual

Impromat Klima UTI-IQCP user guide

Impromat Klima

Impromat Klima UTI-IQCP user guide

Spectron BE56-2U user manual

Spectron

Spectron BE56-2U user manual

Honeywell PL-1000 Installation and user manual

Honeywell

Honeywell PL-1000 Installation and user manual

NAPCO Gemini GEM-X255 Programming instructions

NAPCO

NAPCO Gemini GEM-X255 Programming instructions

Fancom AURA 37 manual

Fancom

Fancom AURA 37 manual

DeDietrich MIT/E iSystem user guide

DeDietrich

DeDietrich MIT/E iSystem user guide

QOLSYS IQ4 Hub installation manual

QOLSYS

QOLSYS IQ4 Hub installation manual

Radionics D10024A user manual

Radionics

Radionics D10024A user manual

Leviton Z-MAX Series user guide

Leviton

Leviton Z-MAX Series user guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.