2 Description
Door operator control module KNX A2-B2 • Version: 24.04.2013 • Technical changes and errors reserved.
1. Description
The Door operator control module KNX A2-B2 has two outputs for door controls
and two binary inputs.
Functions:
•2 outputs for door operation (impulse or dead-man mode)
•2 binary inputs for the bus functions switches, toggle switches, blinds,
shutters, marquees, windows, dimmers, 8 but encoders, temperature
encoders, brightness encoder, scenes
Configuration is made using the KNX software ETS. The programme file (format VD),
the data sheet and the manual can be downloaded from the Elsner Elektronik
homepage on www.elsner-elektronik.de in the “Service” menu.
1.0.1. Deliverables
• Door operator control module in the installation casing
1.1. Technical data
The following standards have been considered for the evaluation of the product in
terms of electro magnetic compatibility:
Transient emissions:
• EN 60730-1:2000 Section EMC (23, 26, H23, H26) (threshold category: B)
• EN 50090-2-2:1996-11 + A1:2002-01 (threshold category: B)
Housing Plastic
Colour White
Assembly Installation
Protection category IP 20
Dimensions approx. 38 x 47 x 24 (W × H × D, mm)
Weight approx. 20 g
Ambient humidity max. 95% RH, avoid condensation
Operating voltage bus voltage
Bus current max. 10 mA
Data output KNX +/- Bus connector terminal
BCU type unit's own microcontroller
PEI type 0
Group addresses max. 230
Assignments max. 230
Communication objects 20
Inputs 2 x binary inputs (for potential-free contacts),
maximum output length 5 m
Outputs 2 x semi-conductor output (open collector)
max. 60 V AC/DC, 300 mA