Important Noce
• Wiring and connecon must be carried out by a
registered electrician.
• Connecon by an unqualied person voids the
warranty.
• Please check the suitability of the motor before
aempng to connect it to the device.
• Ensure the motor terminals are congured to
suit supply from VSD, for 1ph supply VFD the
motor must be connected in DELTA. For 3ph
supply VFD please consult the motors name tag
for 400V connecon.
• Display will show ether F, H, A, U aer power up.
• Press the enter buon.
• 00. will appear on the screen, this is the parameter group.
• Use the up and down keys to change parameter group to the
desired one. Press “ENTER”.
• 00.00 will appear on the screen, this is the sub group.
• Use the up and down keys to change parameters selecons to
the desired one. Press “ENTER”
• You will now be able to change the required seng of the pa-
rameter to the desired value or seng. Press “ENTER”. End
will ash on your screen to indicate that your seng has been
saved.
• Connue the above steps ll all of your required parameters
have been set.
• If you need to back out of a sub parameter group you can press
the “MODE” buon.
• Once all the parameters have been set press the “MODE”
buon ll the F50.0 screen comes up again.
List of quick set up parameters
1.Status Display –Display the drives current status
2.LED Display—Indicates frequency, voltage, current, user
dened units
3.Potenometer—For local frequency seng
4.Run Key— to start drive locally
5.UP & DOWN Key—Used to change numerical numbers,
frequency, parameters
6.Mode—Change between dierent display mode
7.STOP/RESET— Stops AC drive operaon and resets the drive
aer a fault has occurred
8.ENTER—Used to enter and save the parameters
See back page for power and remote control connecons
and set up
Quick Setup for Variable Speed Drive
Turn on power to unit and follow as below: • 00.02 All parameters are reset to factory sengs or 50Hz
sengs, set to 9 (must be none aer inial powerup)
• 00.20 Source of master Frequency Command.
0 = UP/DOWN arrow (Factory seng)
2 = External analog input
3 = External UP/DOWN terminals
7 = Digital keypad potenometer
• 00.21 Source of master Operaon Command.
0 = Digital keypad (Factory seng )
1 = External terminals
• 01.00 Change to the maximum Frequency required
• 01.01 Change value to match Hz on motor nameplate
• 01.02 Change to match voltage on motor nameplate (Max
Voltage output)
• 01.10 Upper limit Frequency
• 01.11 Lower limit Frequency
• 01.12 Acceleraon me (factory seng 10sec)
• 01.13 Deceleraon me (factory seng 10sec)
• 05.01 Set to Motor Name Plate Current
• 05.02 Set to Motor Name Plate kW
• 05.03 Set to Motor Name Plate Speed (rpm)
• 05.04 Set as the number of poles of the motor
(3000rpm=2pole; 1500rpm=4pole;1000rpm=6pole;
750rpm=8pole) (factory seng 4 pole)
• 05.00 Auto tuning, opon 1 Dynamic test for inducon
motor = 1 (note motor must be unloaded), Stac test for
inducon motor = 2, aer the parameter number is
entered press “MODE” buon to return to main screen
showing “F30.00 or F33.33”, press the “RUN” buon to
start auto tune, Auto tuning should only be preformed
aer all the data is entered.
• 06.13 Electronic thermal relay.
0 = Inverter motor (with external forced cooling ed)
1 = Standard motor (motor with fan on sha)
2 = Disable (factory seng)
FOR ADVANCED SET UP REFER TO THE FULL MANUAL