EMKO TRANS-MINIAMF User manual

1.Introduction
The unit provides for automatic transfer of a load from mains to generator in the event of a mains
failure. Intended for unattended operation, it is able to detect failure of any phase of the mains and to
start and switch over to a generator if the mains voltage goes outside pre-set limits. Both automatic
and manual control is possible. A test mode is also available which allows the generator to be run
without taking the load.
The unit calculates engine RPM from Magnetic Pickup sensor input (Trans-MiniAMF.MPU devices
only) and/or generator voltage signal. At Trans-MiniAMF.CAN devices, unit gets engine RPM
information from J1939 ECU.
The unit monitors J1939 ECU messages and provides remote start/stop control via J1939 protocol at
only Trans-MiniAMF.CAN devices (supported ECUs: Volvo EMS2, Volvo EDC4, Perkins and standard
messages).
In the event that the engine fails to start on the first attempt, the attempt will be repeated a programmed
number of times or until successful.
The unit monitors generator operation and gives warning of any faults that are detected.
If a fault is detected, the unit shuts down the engine and shows the failure message on the LCD display.
1.1 General Specifications
1.2 Warranty
EMKO Elektronik warrants that the equipment delivered is free from defects in material and workmanship.
This warranty is provided for a period of two years. The warranty period starts from the delivery date. This
warranty is in force if duty and responsibilities which are determined in warranty document and instruction
manual performs by the customer completely.
1.3 Maintenance
Repairs should only be performed by trained and specialized personnel. Cut power to the device before
accessing internal parts.
Do not clean the case with hydrocarbon-based solvents (Petrol, Trichlorethylene etc.). Use of these
solvents can reduce the mechanical reliability of the device. Use a cloth dampened in ethyl alcohol or
water to clean the external plastic case.
Introduction Brochure. ENG TRANS-MINIAMF 01 V10 01/14
TRANS-MINIAMF
AUTOMATIC MAINS FAILURE UNIT

Ýçindekiler
A visual inspection of this product for possible damage occured during shipment is
recommended before installation. It is your responsibility to ensure that qualified mechanical
and electrical technicians install this product.
If there is danger of serious accident resulting from a failure or defect in this unit , power off
the system and seperate the electrical connection of the device from the system.
Keep the power off until all of the wiring is completed so that electric shock and trouble with
the unit can be prevented.
Before beginning installation of this product, please read the instruction
manual and warnings below carefully.
2. Installation
Ýçindekiler
2.1 Unit Configuration
Ýçindekiler
2.2 Panel Mounting
The unit is designed for panel mounting. Fixing is by two screw fixings.
1- Insert the unit in the panel cut-out from the front.
2- Insert the fixings in the slotted at the corners of the unit and tighten the fixing screws to secure
the unit against the panel.
During the equipment is putted in hole on the metal panel while mechanical
installation some metal burrs can cause injury on hands, you must be careful.
Figure 2.1 Front View Figure 2.2 Panel Cut-Out
The unit can be programmed using the buttons and LCD display on the front panel or PC
Software.
2
!
!
81mm
70mm
ü
AUTO
RESET
111mm
81mm

2.3 Electrical Connection
3
1- Connect the unit as shown in the appropriate diagram. Be sure to connect the battery
supply the right way round and battery negative should be grounded.
2- The CAN interface requires that a 120 Ohms terminator is fitted to each end of the
communications link. This termination resistor is fitted internally into the unit. So it is not
required externally. The screen is grounded at one end ONLY.
3- Screened cable must be used for connecting the Magnetic Pickup, ensuring that the
screen is grounded at one end ONLY.
4- Current transformers secondary should be grounded.
TRANS-MINIAMF three phase connections schematic
!
D+(W.L.)
Charge Alt.
13 11
12
BATTERY -
BATTERY +
23 22
14 15
BATTERY -
16
FUSE-5
3
1
21
- +
MPU
Emergency Stop or
Configurable Input-1
27 26 25
8A
8A
30 2
24 29 1
L1
GENERATOR
Max. 300VV
MAINS
L2
L3
N
M
LOAD
G
L1
L2
L3
N
El c r c l nte lock
e t iai r
Mehanica in rlkc l te oc
43
Max. 300VV
Mains
Contactor
Relay
Generator
Contactor
Relay
FUSE-1
FUSE-2
FUSE-3
FUSE-4
4
FUSE-1, FUSE-2, FUSE-3, FUSE-4 2A. T
FUSE-5 8A. T
FUSE-6, FUSE-7 8 A. T
SCR
28 31
SCR L(-)
J1939 ECUs
H(+)
2
!
!
!
!
Configurable Input-2
Configurable Input-3
18 17
20 19
Sender Common To Engine
Earth
*
*
IT CAN BE USED
AS A DIGITAL INPUT
BY SELECTING
FROM THE PROGRAM
PARAMETERS
* *
Oil Pressure Sender
or Low Oil Pressure Switch
Temperature Sender
or High Temperature Switch
Configurable Analog Input
Configurable Output-4
78 9 10
Configurable Output-3
TRANSISTOR OUTPUTS
MAX. 1 A
BATTERY +
6
Fuel Or
Configurable Output-1
Crank Or
Configurable Output-2
5
Configurable Output-5
Configurable Output-6
FUSE-6
FUSE-7

4
3. Changing And Saving Parameters Values
Operation Screen
Press the Up or Down
buttons to select
the section you wish
to view/change.
Press the
Enter
button.
Enter password with
cursor (Up, Down
and Next) buttons.
Press the Enter button
to confirm password.
If the password is incorrect,
the unit will drop out of
program mode.
Press the Up or Down
buttons to select the main
parameter group you wish to
view/change.
Note1: If Enter button is pressed
and the technician password is
zero, Password screen is ignored.
Press Enter button to access to all
parameters page in currently main
parameter group.
Parameter can be
changed with Up and
Down buttons.
Press Enter button to
confirm the changed value.
Press the Enter
button to view
parameter value.
Press Enter button to access
to all parameters in currently
parameter page.
Operation
Screen
GENERATOR
Volt level
Frequency level
Current level & act.
Power level
When the Stop/Reset button is
pressed any time, previous
page can be accessed.
MAINS
V12: 380V V1: 220V
V23: 380V V2: 220V
V31: 380V V3: 220V
Wait for start
To exit from programming mode
any time, press Stop/Reset
button for 2 seconds.
MAINS
V12: 380V V1: 220V
V23: 380V V2: 220V
V31: 380V V3: 220V
Wait for start
üü
AUTO
RESET
Press Enter button
for 2 seconds to
access the menu options.
When the Enter button is
pressed, the parameters
section is asked for
accessing to parameters.
Program
Language
Event log
AUTO
RESET
üü
PROGRAM
Operator setting
Technician setting
Factory adjustment
AUTO
RESET
üü
PROGRAM
Operator setting
Technician setting
Factory adjustment
AUTO
RESET
üü
TECHNICIAN SETTING
Password
0000
AUTO
RESET
üü
TECHNICIAN SETTING
Password
0162
AUTO
RESET
üü
TECHNICIAN SETTING
System
Mains
Generator
Engine
AUTO
RESET
üü
TECHNICIAN SETTING
System
Mains
Generator
Engine
AUTO
RESET
üü
GENERATOR
Volt level
Frequency level
Current level & act.
Power level
AUTO
RESET
üü
GENERATOR VOLT LEVEL
Under volt shutdown
Under volt prealarm
Under volt return
Over volt shutdown
AUTO
RESET
üü
GENERATOR VOLT LEVEL
Under volt shutdown
320 Vac
AUTO
RESET
üü
GENERATOR VOLT LEVEL
Under volt shutdown
325 Vac
AUTO
RESET
üü
GENERATOR VOLT LEVEL
Under volt shutdown
Under volt prealarm
Under volt return
Over volt shutdown
AUTO
RESET
üü

600
60
60
60
600
600
600
VV
VV
VV
VV
60
Min DefaultMAINS VOLT LEVEL (Mains->Volt level)Max
Mains Under Voltage
Mains Under Voltage Return
Mains Over Voltage
Mains Over Voltage Return
320
340
440
420
Under volt trip
4.1 Operator Parameters
Under volt reset
Over volt trip
Over volt reset
Unit
5
Note: dis = disable
4. Parameters
Min DefaultMAINS FREQ. LEVEL (Mains->Frequency level)Max
Mains Under Frequency Hz
Hz
Hz
Hz
20.0 75.0
20.0 75.0
20.0 75.0
20.0 75.0
45.0
48.0
55.0
52.0
Mains Under Frequency Return
Mains Over Frequency
Mains Over Frequency Return
Under freq trip
Under freq reset
Over freq trip
Over freq reset
Unit
600
60(dis)
60
60
600
600
600
VV
VV
VV
VV
60(dis)
Min Default
Max
Generator Under Voltage Shutdown
Generator Under Voltage Pre-Alarm
Generator Under Voltage Pre-Alarm Return
Generator Over Voltage Shutdown
Generator Over Voltage Pre-Alarm
320
340
350
440
60(dis) 600
60 600
420
400
Generator Over Voltage Pre-Alarm Return
VV
VV
Under volt shutdown
Under volt prealarm
Under volt reset
Over volt shutdown
Over volt prealarm
Over volt reset
Unit
Shutdown delay time Generator Voltage Shutdown Delay Time
GENERATOR VOLT LEVEL (Generator->Volt level)
0.0 10.0 1.0 Sec
75.0
30.0(dis)
75.0
75.0
Hz
30.0(dis)
Min Default
Max
Generator Under Frequency Pre-Alarm
Generator Under Frequency Pre-Alarm Return
Generator Over Frequency Shutdown
Generator Over Frequency Pre-Alarm
Generator Over Frequency Pre-Alarm Return
45.0
46.0
58.0
55.0
54.0
Generator Frequency Shutdown Delay Time
Hz
Hz
Hz
Hz
30.0
30.0(dis)
30.0
75.0
75.0
Under freq prealarm
Under freq reset
Over freq shutdown
Over freq prealarm
Over freq reset
Shutdown delay time
Unit
GENERATOR FREQ LEVEL (Generator->Frequency level)
75.0
75.0
Hz
30.0
Nominal Alternator Frequency 50.0
43.0 Hz
Nominal frequency
Under freq shutdown Generator Under Frequency Shutdown 30.0(dis)
0.0 10.0 1.0 Sec
Min Default
Max
Generator Under Current Pre-Alarm Return
Generator Over Current Set
Generator Over Current Pre-Alarm
Generator Over Current Pre-Alarm Return
Under cur. reset
Over cur. set
Over cur. prealarm
Over cur. reset
Unit
GENERATOR CUR LEVEL (Generator->Current level)
Generator Under Current Set
Under cur. set
Under cur. prealarm Generator Under Current Pre-Alarm
09999 9980 AV
0
0(dis)
0
0
0(dis)
9999
9999
9999
9999
9999
1
dis
5
9999
9990
AV
AV
AV
AV
AV
4.1.1 Mains
4.1.2 Generator

6
Min Default
Max
Working Calendar Disable or Enable
Working Calendar Work Start Time on Monday
Working Calendar Work Stop Time on Monday
Working Calendar Work Start Time on Tuesday
Working Calendar Work Stop Time on Tuesday
Working Calendar Work Start Time on Wednesday
Working Calendar Work Start Time on Thursday
Working Calendar Work Start Time on Friday
Working Calendar Work Start Time on Saturday
Working Calendar Work Start Time on Sunday
Disable/enable select
Start time on monday
Stop time on monday
Start time on tues.
Stop time on tuesday
Start time on wednes.
Start time on thurs.
Start time on friday
Start time on satur.
Start time on sunday
Unit
Stop time on wednes.
Stop time on thursday
Stop time on friday
Stop time on saturday
Stop time on sunday
Working Calendar Work Stop Time on Wednesday
Working Calendar Work Stop Time on Thursday
Working Calendar Work Stop Time on Friday
Working Calendar Work Stop Time on Saturday
Working Calendar Work Stop Time on Sunday
GEN WORKING CALENDAR (Generator->Working calendar)
23.59
23.59
23.59
23.59
23.59
23.59
23.59
23.59
23.59
23.59
23.59
23.59
23.59
23.59
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
23.59
23.59
23.59
23.59
23.59
23.59
23.59
DISBL/ENABL DISBL
9999
9999
9999
9999
9999
9999
kVA
kVA
kVA
kVA
0(dis)
0(dis)
0
0(dis)
0(dis)
0
Min Default
Max
Generator Under Power Shutdown
Generator Under Power Pre-Alarm
Generator Under Power Pre-Alarm Return
Generator Over Power Shutdown
Generator Over Power Pre-Alarm
dis
5
Generator Over Power Pre-Alarm Return
kVA
kVA
Under power shutdown
Under power prealarm
Under power reset
Over power shutdown
Over power prealarm
Over power reset
Unit
Shutdown delay time Generator Power Shutdown Delay Time
GEN POWER LEVEL (Generator->Power level)
0 99 2 Sec
dis
dis
0
dis
4.2 Technician Parameters
4.2.1 System
Note-1 : dis = disable
Reverse power set Reverse Power Set -9999 0 0 kW
Min Default
Max
Current Transformer Ratio
Voltage Transformer Ratio
Select AC system;
Generator kVA rating set
CT ratio
PT ratio
Type of AC system
Generator kVA rating
Unit
SYSTEM NETWORK (System->Network)
3
9999
50
kVA
0
0
1
1
300
1
0- 1 Phase 2 Wire
1- 3 Phase 4 Wire
2- 2 Phase 3 Wire L1-L2
3- 2 Phase 3 Wire L1-L3
99995 100

7
Min Default Unit
BREAKERS (System->Breakers)
Max
Hardware Breaker Selection
Gen Close Breaker Contact Type
Gen Close Breaker Relay Type
Gen Close Timer
0
Gen Open Breaker Relay Type
0 2
Gen Open Timer
Mains Close Breaker Contact Type
Mains Close Breaker Relay Type
Mains Close Timer
NO / NC 0
NOR / PULS
5
1 250
0
Sec
0
NOR / PULS
0
1 250 5
0
NOR / PULS
0
1 250 5
5
NOR / PULS
0.0
0.0
0
10.0
10.0
250 2
Mains Open Breaker Relay Type
Mains Open Timer
Breaker Close Pulse Time
Breaker Open Pulse Time
Transfer Time
Spring Loading Time
Retry Number
NO / NC
Gen.brk.cls.contact
Gen.brk.cls.relay
Gen.brk.cls.time
Gen.brk.open relay
Gen.brk.open time
Type of Breaker
Mains.brk.cls.relay
Mains.brk.cls.time
Mains.brk.open relay
Mains.brk.open time
Break.close puls.time
Mains.brk.cls.contact
Transfer time
Spring loading time
Retry number
Break.open pulse time
Sec
Sec
1 250
0.5
0.5
Sec
Sec
Sec
Sec
Sec
3
5
1 250
1 250
Min Default Unit
LCD DISPLAY (System->LCD display)Max
Language Selection
Digital Contrast
ENGLISH/CHINESE
5
4 9
Contrast
Language 1
*
Auto Scroll Time
Auto Scroll Number
Scroll Time For Error Messages
0
0 (dis) 250 Sec
3
11
2
1250
Auto scroll number 2
*
Err. mesg scroll time
Auto scroll time
Sec
1
ENGLISH
Min Default Unit
COMMUNICATION (System->Communication)Max
Slave Address 1
1 247
05 3
Baud Rate
0 - 1200 baud
1 - 2400 baud
2 - 4800 baud
3 - 9600 baud
4 - 19200 baud
5 - 38400 baud
Stop Bit (0-> 1 stop bit,1-> 2 stop bit)
020
0 1 0
Slave address
Baud rate
Parity
Stop bit
Parity
0 - NONE
1 - ODD
2 - EVEN
1
Note: *= Selectable value of this parameter is “ENGLISH/TURKISH” at Trans-MiniAMF.XXX
(TR) devices.
2
*= Max. value of this parameter is equal to 17 at Trans-MiniAMF.CAN devices
NO / NC : Normally Open / Normally Close
NOR / PULS : Normal / Pulse
dis = disable

8
Note: dis = disable
Min Default Unit
PASSWORD SETTINGS (System->Password settings)Max
Operator Password
Technician Password
0
0 9999
09999 0
Operator password
Technician password
Min Default Unit
DEFAULT SETTINGS (System->Default settings)Max
Save setting to default
Reset default sets
Save setting to def.
Reset default sets
YES / NO NO
Reset factory sets
Reset factory sets
YES / NO NO
YES / NO NO
600
60
60
60
600
600
600
VV
VV
VV
VV
60
Min DefaultMAINS VOLT LEVEL (Mains->Volt level)Max
Mains Under Voltage
Mains Under Voltage Return
Mains Over Voltage
Mains Over Voltage Return
320
340
440
420
Under volt trip
4.2.2 Mains
Under volt reset
Over volt trip
Over volt reset
Unit
Min DefaultMAINS FREQ. LEVEL (Mains->Frequency level)Max
Mains Under Frequency Hz
Hz
Hz
Hz
20.0 75.0
20.0 75.0
20.0 75.0
20.0 75.0
45.0
48.0
55.0
52.0
Mains Under Frequency Return
Mains Over Frequency
Mains Over Frequency Return
Under freq trip
Under freq reset
Over freq trip
Over freq reset
Unit
600
60(dis)
60
60
600
600
600
VV
VV
VV
VV
60(dis)
Min Default
Max
Generator Under Voltage Shutdown
Generator Under Voltage Pre-Alarm
Generator Under Voltage Pre-Alarm Return
Generator Over Voltage Shutdown
Generator Over Voltage Pre-Alarm
320
340
350
440
60(dis) 600
60 600
420
400
Generator Over Voltage Pre-Alarm Return
VV
VV
Under volt shutdown
Under volt prealarm
Under volt reset
Over volt shutdown
Over volt prealarm
Over volt reset
Unit
Shutdown delay time Generator Voltage Shutdown Delay Time
GENERATOR VOLT LEVEL (Generator->Volt level)
0.0 10.0 1.0 Sec
4.2.3Generator
Min Default Unit
MAINS ACTIONS (Mains->Actions)Max
Mains Failure Detection En/Dis
Look Mains Failure at Stop Mode En/Dis
Always Look Mains Return Delay
Mains failure detect
Mains fail.stop mode
Always return delay
ENABLENABL/DISBL
ENABL/DISBL
ENABL/DISBL
ENABL
DISBL
Min DefaultDATE & TIME SET (System->Date & time set)Max
Year
Month
0 99
112
Date 131
Day of week 17
Hour 023
Minute 059
Second 059
Year
Month
Day
Week
Hour
Minute
Second
Unit
Real time clock enable/disable
RTC ENABL/DISBL ENABL

9
Min Default
Max
Generator Under Current Pre-Alarm Return
Generator Under Current Actions Delay Time
Generator Over Current Set
Generator Over Current Pre-Alarm
Generator Over Current Pre-Alarm Return
Generator Over Current Actions Delay Time
Generator Short Circuit Current Set
Under cur. reset
Under cur. act.
Under act. delay time
Over cur. set
Over cur. prealarm
Over cur. reset
Over cur. act.
Over act. delay time
Short circuit cur.
Unit
GEN CUR LEVEL & ACT (Generator->Current level & act.)
Generator Under Current Set
Under cur. set
Under cur. prealarm Generator Under Current Pre-Alarm
0
0(dis)
0
0
9999
3
99
9999
9980
dis
2
9999
AV
AV
0
0(dis)
0
0(dis)
0
0
0(dis)
9999
9999
9999
3
99
9999
9999
1
dis
5
dis
2
9999
9990
AV
AV
AV
AV
AV
Sec
Sec
Generator Under Current Actions
0 - Disable
1 - Warning (Alarm Only, No Shutdown)
2 - Electrical Trip (Alarm/Off Load Generator
Followed By Shutdown After Cooling)
3 - Shutdown (Alarm And Shutdown)
Generator Over Current Actions
0 - Disable
1 - Warning (Alarm Only, No Shutdown)
2 - Electrical Trip (Alarm/Off Load Generator
Followed By Shutdown After Cooling)
3 - Shutdown (Alarm And Shutdown)
9999
9999
9999
9999
9999
9999
kVA
kVA
kVA
kVA
0(dis)
0(dis)
0
0(dis)
0(dis)
0
Min Default
Max
Generator Under Power Shutdown
Generator Under Power Pre-Alarm
Generator Under Power Pre-Alarm Return
Generator Over Power Shutdown
Generator Over Power Pre-Alarm
dis
5
Generator Over Power Pre-Alarm Return
kVA
kVA
Under power shutdown
Under power prealarm
Under power reset
Over power shutdown
Over power prealarm
Over power reset
Unit
Shutdown delay time Generator Power Shutdown Delay Time
GEN POWER LEVEL (Generator->Power level)
0 99 2 Sec
dis
dis
0
dis
Note: dis = disable
75.0
30.0(dis)
75.0
75.0
Hz
30.0(dis)
Min Default
Max
Generator Under Frequency Pre-Alarm
Generator Under Frequency Pre-Alarm Return
Generator Over Frequency Shutdown
Generator Over Frequency Pre-Alarm
Generator Over Frequency Pre-Alarm Return
45.0
46.0
58.0
55.0
54.0
Generator Frequency Shutdown Delay Time
Hz
Hz
Hz
Hz
30.0
30.0(dis)
30.0
75.0
75.0
Under freq prealarm
Under freq reset
Over freq shutdown
Over freq prealarm
Over freq reset
Shutdown delay time
Unit
GENERATOR FREQ LEVEL (Generator->Frequency level)
75.0
75.0
Hz
30.0
Nominal Alternator Frequency 50.0
43.0 Hz
Nominal frequency
Under freq shutdown Generator Under Frequency Shutdown 30.0(dis)
0.0 10.0 1.0 Sec
Reverse Power Set
Reverse Power Action Delay Time
-9999
0(dis)
0
0
3
99
0
0(dis)
2
kW
Sec
Reverse Power Actions
0 - Disable
1 - Warning (Alarm Only, No Shutdown)
2 - Electrical Trip (Alarm/Off Load Generator
Followed By Shutdown After Cooling)
3 - Shutdown (Alarm And Shutdown)
Reverse power set
Reverse power act.
Rv.pow.act.delay time

10
4.2.4 Engine
ENABL/DISBL
Sec
Min Default Unit
ENGINE START OPTIONS (Engine->Starting options)Max
Audible Alarm Prior To Starting En/Dis
Number Of Start Attempts
Cranking Time
Crank Rest Time
DISBL
3
5
1
1
10
99
10
5 99
Pickup Sensor Fail Delay(Pickup)
3.0
0.1 10.0
Horn prior start
No. of start attemp
Cranking time
Crank rest time
Pickup fail delay 3
*
Sec
Sec
Min Default Unit
ENG. CRANK DISCONNECT (Engine->Crank disconnect)Max
Crank Disconnect On Gen. Frequency
Crank Disconnect On Gen. Voltage
Crank Disconnect On Charge Alt. Voltage
30.0
Crank Disconnect On Oil Pressure
25.0 75.0 Hz
500
500 6000 RPM
300
60 (dis) 600 VV
dis
6.0 (dis) 30.0 VZ
dis
1.0 (dis) 30.0 BAR
Generator frequency
Engine speed
Generator volt
Alt. Charge volt
Oil pressure
Crank Disconnect On Engine RPM
Min Default Unit
ENGINE SPEED SETS (Engine->Speed settings)Max
Engine Under Speed Shutdown
Engine Under Speed Prealarm
Engine Under Speed Prealarm Return
dis
Engine Over Speed Shutdown
500(dis) 5000
500(dis) RPM
500
500 5000
Engine Over Speed Prealarm Return
Engine Speed Shutdown Delay Time
500
1.0
RPM
RPM
RPM
RPM
RPM
Sec
5000
500(dis) 5000
5000
5000
10.0
Engine Over Speed Prealarm
Under speed shutdown
Under speed prealarm
Under speed reset
Over speed shutdown
Over speed prealarm
Over speed reset
Shutdown delay time
500
0.0
Nominal Speed 1500
500 5000 RPM
Nominal speed
dis
dis
dis
500(dis)
Min Default Unit
GENERATOR GENERAL (Generator->General)Max
Sensing Options Generator Frq En/Dis
Sens.option gen.freq ENABL
ENABL/DISBL
0(dis)
Sensing Opt Pickup En/Dis & Flywheel DISBL1000
All Warnings Are Latched En/Dis
Sens.opt.pickup&flywh 3
*
All warning are latch ENABL/DISBL DISBL
3
Note: *= These parameters are only available at Trans-MiniAMF.MPU
dis = disable
Min Default
Max
Working Calendar Disable or Enable
Working Calendar Work Start Time on Monday
Working Calendar Work Stop Time on Monday
Working Calendar Work Start Time on Tuesday
Working Calendar Work Stop Time on Tuesday
Working Calendar Work Start Time on Wednesday
Working Calendar Work Start Time on Thursday
Working Calendar Work Start Time on Friday
Working Calendar Work Start Time on Saturday
Working Calendar Work Start Time on Sunday
Disable/enable select
Start time on monday
Stop time on monday
Start time on tues.
Stop time on tuesday
Start time on wednes.
Start time on thurs.
Start time on friday
Start time on satur.
Start time on sunday
Unit
Stop time on wednes.
Stop time on thursday
Stop time on friday
Stop time on saturday
Stop time on sunday
Working Calendar Work Stop Time on Wednesday
Working Calendar Work Stop Time on Thursday
Working Calendar Work Stop Time on Friday
Working Calendar Work Stop Time on Saturday
Working Calendar Work Stop Time on Sunday
GEN WORKING CALENDAR (Generator->Working calendar)
23.59
23.59
23.59
23.59
23.59
23.59
23.59
23.59
23.59
23.59
23.59
23.59
23.59
23.59
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
23.59
23.59
23.59
23.59
23.59
23.59
23.59
DISBL/ENABL DISBL

11
Note: = Parameters in this table are only available at Trans-MiniAMF.CAN
4
*
Min Default
ENGINE PLANT BATTERY (Engine->Plant battery)Max
Battery Undervolts Warning
Battery Undervolts Warning Return
Battery Undervolts Volts Delay
Battery Overvolts Warning
10.0
Battery Overvolts Warning Return
6.0(dis) 30.0
10.5
6.0
1.0
0.0 9.9
30.0
29.5
Charge Alternator Warning dis
30.0
30.0
6.0 30.0
Battery Overvolts Delay 1.0
0.0 9.9
30.0
6.0(dis)
6.0(dis)
Under volt
Under volt reset
Under volt delay
Over volt
Over volt reset
Over volt delay
Alt. chg. warning
Unit
VZ
VZ
VZ
VZ
Sec
Sec
VZ
4
CANBUS ECU (Engine->CanBus ECU)*
Baud Rate:
0 - 20
1 - 50
2 - 100
3 - 125
4 - 250
5 - 500
6 - 800
7 - 1.000
J1939 ECU Type Selection:
0 - Disable
1 - Standard
2 - Volvo EMS1
3 - Volvo EMS2
4 - Volvo EMS2b
5 - Volvo EDC3
6 - Volvo EDC4
7 - Deutz EMR2
8 - Deutz EMR3
9 - Perkins 1300
10 - Perkins ADEM3
11 - Perkins ADEM4
Baud rate
J1939 ECU type
Device address
Engine cont. address
Min Default UnitMax
07 4
11 0
0255 17
0 255 0
kBaud
ECU remote control
Speed control enable
Oil pres cont. enab
Temp. control enable
DISBL
Device Address
0(dis)
Engine Control Address
ECU Remote Control via J1939
Speed Control via J1939
Oil Pressure Control via J1939
Coolant Temperature Control via J1939
Speed correction 50
Speed Correction Value
%
0 100
Speed set point 1500
1500 / 1800
Speed Set Point Selection
RPM
ENABL/DISBL
ENABL/DISBL
ENABL/DISBL
ENABL/DISBL
DISBL
DISBL
DISBL

Min Default Unit
5
CANBUS ERROR SET (Engine->CanBus error set)*Max
Can Fault Actions:
0- Disable
1- Warning Non-Latching
2- Warning (Alarm Only, No Shutdown)
3- Electrical Trip (Alarm/Off Load Generator
Followed By Shutdown After Cooling)
4- Shutdown (Alarm And Shutdown)
0
0 2
0
0(dis) 4
CAN fault activation
CAN fault actions
SecCan Fault Delay 10
2 250
CAN fault delay
Can Fault Activation:
0- Active From Starting
1- Active From Safety On
2- Always Active
J1939 Amber Warning Lamp Actions:
0- Disable
1- Warning Non-Latching
2- Warning (Alarm Only, No Shutdown)
3- Electrical Trip (Alarm/Off Load Generator
Followed By Shutdown After Cooling)
4- Shutdown (Alarm And Shutdown)
2
0 2
0
0(dis) 4
Amber warn.activation
Amber warn.actions
SecJ1939 Amber Warning Lamp Delay 2
0 250
Amber warn.delay
J1939 Amber Warning Lamp Activation:
0- Active From Starting
1- Active From Safety On
2- Always Active
J1939 Red Stop Lamp Actions:
0- Disable
1- Warning Non-Latching
2- Warning (Alarm Only, No Shutdown)
3- Electrical Trip (Alarm/Off Load Generator
Followed By Shutdown After Cooling)
4- Shutdown (Alarm And Shutdown)
2
0 2
0
0(dis) 4
Red stop activation
Red stop actions
SecJ1939 Red Stop Lamp Delay 2
0 250
Red stop delay
J1939 Red Stop Lamp Activation:
0- Active From Starting
1- Active From Safety On
2- Always Active
12
Note: = Parameters in this table are only available at Trans-MiniAMF.CAN
dis = disable
5
*

13
Note: dis = disable
Min Default
EXERCISE (Engine->Exercise)Max
0(dis) 99 dis
1
7
0.0 23.59 0.00
1
Time of period
Week
Start time
Generator exercise working period on related day
Generator exercise working day of week
Generator exercise work start time on related day
Unit
Min
H.Min
Min Default
LOAD TEST (Engine->Load test)Max Unit
1-NO LOAD
Disable/enable select Disable, No Load or On Load Selection 0-DISABLE
1-NO LOAD
2-ON LOAD
Min Default
ENGINE MAINTENANCE (Engine->Maintenance)Max
Running Hours Interval
Maintenance Date Interval
Force Engine Shutdown When Maintenance Is Due
Engine Running Hour (Lsb)
5000
Engine Running Hour
0(dis) 9999
Engine Running Hour(Msb)
ENABL/DISBL
0
0 255
DISBL
0
0
0(dis) 12 6
0 255
0 14
Maint. date interval
Eng. stop when maint
Eng.running hour(lsb)
Eng. running hour
Eng. running hour(msb)
Running hour interval
Unit
Hour
Month
Maintenance Okay NO
Maintenance okay YES/NO
Min Default Unit
ENGINE GENERAL (Engine->General)Max
Engine Fuel Selection 1-DIESEL
Stop Solenoid Time 5 2099
Ignition Delay 1 599 Sec
Gas Valve Delay 1 599 Sec
Minimum Ignition Speed 10 2001500 RPM
Fuel selection
Stop solenoid time
Ignition delay
Gas valve delay
Min. of ignition speed
Sec
Choke time Choke Time Sec
0.0 0.830.0
0-GAS
1-DIESEL
2-GASOLINE

14
4.2.5 Inputs
Min Default Unit
SENDER INPUTS (Inputs->Sender inputs)Max
Oil Pressure Input Type
Oil Pressure Pre-Alarm
Oil Pressure Pre-Alarm Reset
Coolant Temperature Input Type
1.2
0.0 (dis) 30.0 BAR
1.4
0.0 30.0 BAR
1.0
0.0 30.0 BAR
0 - Not Used (Disable)
1 - Digital NC
2 - Digital NO
3 - VDO 5 BAR
4 - VDO 7 BAR
5 - VDO 10 BAR
6 - DATCON 5 BAR
7 - DATCON 7 BAR
8 - MURPHY 7 BAR
9 - User Configured
90
0 (dis) 300
88
0 300
95
0 300
0 (dis) 3000 %
0 3000
3000
High Temperature Pre-Alarm
Oil Pressure Shutdown
High Temp. Pre-Alarm Reset
High Temperature Shutdown
C
C
C
High temp. prealarm
High temp. reset
High temp. shutdown
Conf. AI type
Conf. AI low prealrm
Temp. input type
Oil pressure shutdown
Oil pressure reset
Oil pressure prealarm
Oil press. input type
%
%
0 (dis)
60
0(dis) 70
Low Temperature Warning C
Low temp. warning
Conf. AI unit
Configurable Analog Input Type
3000
90
0 3000
Conf. AI low shutdwn
Conf. AI high prealr
Conf. AI high shutd.
3
0 - Not Used (Disable)
1 - Digital NC
2 - Digital NO
3 - VDO 120 ºC
4 - VDO 150 ºC
5 - DATCON
6 - MURPHY
7 - PT100
8 - User Configured
3
0 - Not Used (Disable)
1 - Digital NC
2 - Digital NO
3 - VDO OHM (10-180)
4 - VDO TUBE (90-0)
5 - US OHM (240-33)
6 - GM OHM (0-90)
7 - FORD (73-10)
8 - User Configured
0 (dis)
0 (dis)
0 (dis)
0 (dis)
0 (dis) %
%
0 (dis)
Oil Pressure Unit
Oil pressure unit BARBAR/PSI/KPA
Conf. AI high reset
Coolant Temperature Unit
Temperature unit ºCºC/ºF
BAR/PSI/KPA/ºC/ºF/%/Lt %
Configurable Analog Input Unit
Configurable Analog Input
Low Pre-Alarm
Conf. AI low reset
Configurable Analog Input
Low Reset
Configurable Analog Input
Low Shutdown
Configurable Analog Input
High Pre-Alarm
Configurable Analog Input
High Reset
Configurable Analog Input
High Shutdown
0 (dis) 3000 %
0 (dis)
0 (dis)
0 (dis) 3000 %
Conf. AI control ON
Configurable Analog Input
control ON
75
0 3000 %
Conf. AI control OFF
Configurable Analog Input
control OFF
Temperature Sensor Break
Temp. sensor break
DISBL/ENABL DISBL

15
Min Default Unit
SENDER LINEARISATION (Inputs->Sender linearisation)Max
Oil Pressure Sender Point-1
Oil Pressure Sender Point-2
Oil Pressure Sender Point-3
Oil Pressure Sender Point-4
Oil Pressure Sender Point-5
Oil Pressure Sender Point-6
Oil Pressure Sender Point-7
Oil Pressure Sender Point-8
Oil Pressure Sender Point-9
Oil Pressure Sender Point-10
Temperature Sender Point-1
Temperature Sender Point-2
Temperature Sender Point-3
Temperature Sender Point-4
Temperature Sender Point-5
Temperature Sender Point-6
Temperature Sender Point-7
Temperature Sender Point-8
Temperature Sender Point-9
Temperature Sender Point-10
Configurable Analog Input Sender Point-1
Configurable Analog Input Sender Point-2
Configurable Analog Input Sender Point-3
Configurable Analog Input Sender Point-4
Configurable Analog Input Sender Point-5
Oil Pressure Point-1
Oil Pressure Point-2
Oil Pressure Point-3
Oil Pressure Point-4
Oil Pressure Point-5
Oil Pressure Point-6
Oil Pressure Point-7
Oil Pressure Point-8
Oil Pressure Point-9
Oil Pressure Point-10
Temperature Point-1
Temperature Point-2
Temperature Point-3
Temperature Point-4
Temperature Point-5
Temperature Point-6
Temperature Point-7
Temperature Point-8
Temperature Point-9
Temperature Point-10
Configurable Analog Input Point-1
Configurable Analog Input Point-2
Configurable Analog Input Point-3
Configurable Analog Input Point-4
Configurable Analog Input Point-5
11
29
47
65
82
100
117
134
151
184
291
197
134
97
70
51
38
29
22
15
10
30
50
70
90
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1300
1300
1300
1300
1300
1300
1300
1300
1300
1300
1300
1300
1300
1300
1300
1300
1300
1300
1300
1300
1300
1300
1300
1300
1300
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
5.0
40
50
60
70
80
90
100
110
120
140
0
11
22
33
44
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
BAR
BAR
BAR
BAR
BAR
BAR
BAR
BAR
BAR
BAR
ºC
ºC
ºC
ºC
ºC
ºC
ºC
ºC
ºC
ºC
%
%
%
%
%
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
30.0
30.0
30.0
30.0
30.0
30.0
30.0
30.0
30.0
30.0
300
300
300
300
300
300
300
300
300
300
3000
3000
3000
3000
3000
Oil pressure sender 1
Oil pressure sender 2
Oil pressure sender 3
Oil pressure sender 4
Oil pressure sender 5
Oil pressure sender 6
Oil pressure sender 7
Oil pressure sender 8
Oil pressure sender 9
Oil pressure sender 10
Temperature sender 1
Temperature sender 2
Temperature sender 3
Temperature sender 4
Temperature sender 5
Temperature sender 6
Temperature sender 7
Temperature sender 8
Temperature sender 9
Temperature sender 10
Conf. AI sender 1
Conf. AI sender 2
Conf. AI sender 3
Conf. AI sender 4
Conf. AI sender 5
Oil pressure 1
Oil pressure 2
Oil pressure 3
Oil pressure 4
Oil pressure 5
Oil pressure 6
Oil pressure 7
Oil pressure 8
Oil pressure 9
Oil pressure 10
Temperature 1
Temperature 2
Temperature 3
Temperature 4
Temperature 5
Temperature 6
Temperature 7
Temperature 8
Temperature 9
Temperature 10
Conf. AI value 1
Conf. AI value 2
Conf. AI value 3
Conf. AI value 4
Conf. AI value 5

16
Configurable Analog Input Sender Point-6
Configurable Analog Input Sender Point-7
Configurable Analog Input Sender Point-8
Configurable Analog Input Sender Point-9
Configurable Analog Input Sender Point-10
Configurable Analog Input Point-6
Configurable Analog Input Point-7
Configurable Analog Input Point-8
Configurable Analog Input Point-9
Configurable Analog Input Point-10
110
130
150
170
190
0
0
0
0
0
1300
1300
1300
1300
1300
55
66
77
88
100
0
0
0
0
0
R
R
R
R
R
3000
3000
3000
3000
3000
Conf. AI sender 6
Conf. AI sender 7
Conf. AI sender 8
Conf. AI sender 9
Conf. AI sender 10
Conf. AI value 6
Conf. AI value 7
Conf. AI value 8
Conf. AI value 9
Conf. AI value 10
%
%
%
%
%

17
Note-1 : x = 1(input ), 2(input ) or 3(input )
Note-2 : dis = disable
-1 -2 -3
Min Default Unit
CONF. INPUT-X (Inputs->Conf. input-x)Max
20(dis)
10
4
20
0
2500 Sec
0
Dis,user conf.or list
Polarity
Indication
Activation
Select from list
Active delay
0- Disable
1- User Configured
2- Select From List
0- Normally Open (Close To Activate)
1- Normally Close (Open To Activate)
If User Configured
0- Status
1- Warning Non-Latching
2- Warning Latching
3- Electrical Trip
4- Shutdown
If User Configured
0- Active From Starting
1- Active From Safety On
2- Always Active
If Select From List
0-Remote Start On Load
1-Remote Start Off Load
2-Auxiliary Mains Fail
3-Reserved
4-Reserved
5-Reserved
6-Simulate Auto Button
7-Simulate Test Button
8-Reserved
9-Simulate Start Button
10-Simulate Stop Button
11-Generator Closed Auxiliary
12-Generator Load Inhibit
13-Mains Closed Auxiliary
14-Mains Load Inhibit
15-Auto Restore Inhibit
16-Auto Start Inhibit
17-Panel Lock
18-Scheduled Runs(Exercise) Inhibited
19-Reserved
20-Reserved
21-Reserved
22-Remote Inhibit
23-Being Found Alive
24-Reserved
25-Low Oil Pressure
26-High Temperature
27-Emergency Stop
28-Low Oil Level
Input active delay
in1=27
in2=3
in3=4
in1=2
in2=0
in3=0
in1=0
in2=0
in3=0
in1, 2=2
in3=2
in1=0
in2=5
in3=5
in1=1
in2, 3=0
28

18
4.2.6 Outputs
Min Default Unit
CONF. OUTPUT-1 (Outputs->Conf. output-1)Max
010
1220 43
Polarity
Function
0- Normally Open (Close To Activate)
1- Normally Close (Open To Activate)
0-NOT USED
1-AIR FLAP CONTROL
2-ALARM RESET
3-AUDIBLE ALARM
4-AUTO START INHIBIT
5-AUXILIARY MAINS FAILURE
6-BATTERY HIGH VOLTAGE
7-BATTERY LOW VOLTAGE
8-CALLING FOR SCHEDULED RUN(EXERCISE)
9-CAN ECU POWER (only available at Trans-MiniAMF.CAN)
10-CAN ECU STOP (only available at Trans-MiniAMF.CAN)
11-CHARGE ALTERNATOR FAILURE
12-COMMON ALARM
13-COMMON ELECTRICAL TRIP ALARM
14-COMMON SHUTDOWN ALARM
15-COMMON WARNING ALARM
16-COOLING FAN AFTER START
17-COOLING FAN AFTER STOP
18-COOLANT TEMPERATURE HIGH PRE-ALARM
19-COOLANT TEMPERATURE HIGH SHUTDOWN
20-COOLING DOWN TIMER IN PROGRESS
21-CRANK RELAY ENERGISED
22-DELAYED ALARMS ACTIVE
23-DIGITAL INPUT1 ALARM
24-DIGITAL INPUT2 ALARM
25-DIGITAL INPUT3 ALARM
26-RESERVED
27-RESERVED
28-RESERVED
29-RESERVED
30-RESERVED
31-RESERVED
32-RESERVED
33-RESERVED
34-RESERVED
35-RESERVED
36-RESERVED
37-RESERVED
38-RESERVED
39-EMERGENCY STOP
40-FAIL TO START ALARM
41-FAIL TO STOP ALARM
42-CONFIGURABLE ANALOG INPUT CONTROL
43-FUEL RELAY ENERGISED
44-GAS ENGINE IGNITION OUTPUT
45-GENERATOR AT REST
46-GENERATOR AVAILABLE
47-GENERATOR CLOSED AUXILIARY
48-GENERATOR FAILED TO CLOSE
49-GENERATOR FAILED TO OPEN
50-GENERATOR HIGH FREQUENCY PRE-ALARM
51-GENERATOR HIGH FREQUENCY SHUTDOWN
52-GENERATOR HIGH VOLTAGE PRE-ALARM
53-GENERATOR HIGH VOLTAGE SHUTDOWN
54-GENERATOR LOAD INHIBIT
55-GENERATOR LOW FREQUENCY PRE-ALARM
56-GENERATOR LOW FREQUENCY SHUTDOWN
57-GENERATOR LOW VOLTAGE PRE-ALARM
58-GENERATOR LOW VOLTAGE SHUTDOWN
59-GENERATOR STOPPING
60-GENERATOR OPEN BREAKER
61-HORN OUTPUT LATCHED
62-HORN OUTPUT PULSED
63-LAMP TEST
64-RESERVED
65-LOSS OF MAGNETIC PICK-UP SPEED SIGNAL (only available at Trans-MiniAMF.MPU)
66-LOW TEMPERATURE
67-MAINTENANCE DUE ALARM
68-MAINS CLOSED AUXILIARY
69-MAINS FAILED TO CLOSE
70-MAINS FAILED TO OPEN
71-MAINS FAILURE
72-MAINS HIGH FREQUENCY
73-MAINS HIGH VOLTAGE
74-MAINS LOAD INHIBIT
75-MAINS LOW FREQUENCY
76-MAINS LOW VOLTAGE
77-MAINS OPEN BREAKER
78-NO LOADING COMMAND
79-OIL PRESSURE LOW PRE-ALARM
80-OIL PRESSURE LOW SHUTDOWN
81-CONFIGURABLE ANALOG INPUT HIGH PREALARM
82-CONFIGURABLE ANALOG INPUT HIGH SHUTDOWN
83-OVER CURRENT PRE-ALARM
84-OVER CURRENT
85-OVER POWER PRE-ALARM
86-OVER POWER SHUTDOWN
87-OVERSPEED PRE-ALARM
88-OVERSPEED SHUTDOWN
89-PANEL LOCK
90-PRE-HEAT(during preheat timer)
91-PRE-HEAT(until end of cranking)
92-PRE-HEAT(until end of warming)
93-PRE-HEAT(until end safety on)
94-REMOTE START PRESENT
95-REMOTE STOP DELAY IN PROGRESS
96-SHORT CIRCUIT
97-SMOKE LIMITING
98-STARTING ALARM
99-STARTING ALARMS ARMED
100-STOP RELAY ENERGISED
101-SYSTEM IN AUTO MODE
102-SYSTEM IN MANUAL MODE
103-SYSTEM IN STOP MODE
104-SYSTEM IN TEST MODE
105-UNDER CURRENT PRE-ALARM
106-UNDER CURRENT
107-UNDER POWER PRE-ALARM
108-UNDER POWER SHUTDOWN
109-UNDERSPEED PRE-ALARM
110-UNDERSPEED SHUTDOWN
111-WAITING FOR GENERATOR
112-REVERSE POWER
113-LOAD SUPPLY FROM GENERATOR
114-LOAD SUPPLY FROM MAINS
115-CONFIGURABLE ANALOG INPUT LOW PRE-ALARM
116-CONFIGURABLE ANALOG INPUT LOW SHUTDOWN
117-RESERVED
118-RESERVED
119-RESERVED
120-RESERVED
121-CHOKE ACTIVE
122-REMOTE CONTROL ACTIVE

19
Min
Min
Min
Min
Min
Default
Default
Default
Default
Default
Unit
Unit
Unit
Unit
Unit
Max
Max
Max
Max
Max
0
0
0
0
0
1
1
1
1
1
0
0
0
0
0
122
122
122
122
122
0
0
0
0
0
21
62
12
13
14
The same as Configurable Output-1 options
The same as Configurable Output-1 options
The same as Configurable Output-1 options
The same as Configurable Output-1 options
The same as Configurable Output-1 options
CONF. OUTPUT-2 (Outputs->Conf. output-2)
CONF. OUTPUT-3 (Outputs->Conf. output-3)
CONF. OUTPUT-4 (Outputs->Conf. output-4)
CONF. OUTPUT-5 (Outputs->Conf. output-5)
CONF. OUTPUT-6 (Outputs->Conf. output-6)
Polarity
Polarity
Polarity
Polarity
Polarity
Function
Function
Function
Function
Function
0- Normally Open (Close To Activate)
1- Normally Close (Open To Activate)
0- Normally Open (Close To Activate)
1- Normally Close (Open To Activate)
0- Normally Open (Close To Activate)
1- Normally Close (Open To Activate)
0- Normally Open (Close To Activate)
1- Normally Close (Open To Activate)
0- Normally Open (Close To Activate)
1- Normally Close (Open To Activate)
Min Default
START TIMERS (Timers->Start timers)Max
Mains Transient Delay
Remote Start Delay
Pre-Heat
2.0
Pre-Heat Bypass
0.0 20.0
4
0 3600
3
0 250
0
0 250
Safety On Delay 5
0 99
Horn Duration 60
0 (dis) 999
Charge Excitation Time 15
0 99(cont)
Cooling Fan Time 180
0 250
Remote start delay
Pre-heat
Pre-heat bypass
Safety on delay
Horn duration
Chg. excitation time
Cooling fan time
Mains transient delay
Mains Fail Start Delay 0
0 9999
Mains fail start dely
Unit
Sec
Min
Sec
Sec
Sec
Sec
Sec
Sec
Sec
Idle Mode Time (Smoke Limiting) dis
3600
Idle mode time
Idle Mode Time Off (Smoke Limiting Off)
Idle mode time off
Sec
Sec
0 (dis)
0 250 5
4.2.7 Timers
Warmup Time
3
0 250
Warming up time Sec
Min Default
STOPPING TIMERS (Timers->Stopping timers)Max
Remote Stop Delay
Cooling Time
4
0 250
60
0 (dis) 3600
Fail To Stop Time 30
15 99
Remote stop delay
Cooling time
Fail to stop delay
Unit
Sec
Sec
Sec
Mains Return Delay 5
0 3600
Mains return delay Sec
Note: dis = disable cont = continuous

20
4.2.8 User Adjustment
Min Default Unit
MAINS VOLTAGE OFFSET (User adjustment->Mains voltage offset)Max
0
0
0
-20
-20
-20
Mains V1 offset
Mains V2offset
Mains V3offset
Mains V1 Offset
Mains V2Offset
Mains V3Offset
20
20
20
VV
VV
VV
Min Default Unit
GEN. VOLTAGE OFFSET (User adjustment->Gen. voltage offset)Max
0-20
Gen. V1 offset
Generator V1 Offset
20
VV
Min Default Unit
CURRENT OFFSET (User adjustment->Current offset)Max
0-20
Current I1 offset
Current I1 Offset
20
AV
Min Default Unit
BATTERY&CHRG GEN.VOL (User adjustment->Battery&chrg gen.vol)Max
0
0
-5.0
-5.0
Batt.volt offset
Gen.chg.volt offset
Battery Voltage Offset
Charge Generator Voltage Offset
5.0
5.0
VZ
VZ
Min Default Unit
SENDER INPUTS OFFSET (User adjustment->Sender inputs offset)Max
0.0
0
0
-2.0
-20
-200
Oil Pressure offset
Temperature offset
Conf. AI offset
Oil Pressure Offset
Coolant Temperature Offset
Configurable Analog Input Offset
2.0
20
200
BAR
ºC
%
Table of contents
Other EMKO Industrial Equipment manuals