PID TEMPERATURE CONTROL UNITS
ESM-XX20
ENVIRONMENTAL RATINGS and PHYSICAL SPECIFICATIONS
Operat�ng Temperature : 0...50°C
Hum�d�ty : 0-90%RH (none condens�ng)
Protect�on Class : IP65 at front, IP20 at rear
We�ght : ESM-4420 : 220 gr. , ESM-4920 : 240 gr.
ESM-7720 : 270 gr. , ESM-9420 : 230 gr.
ESM-9920 : 340 gr.
D�mens�on :
ESM-4420 : (48 x 48mm, Depth: 95mm)
ESM-4920 : (96 x 48mm, Depth: 94.5mm)
ESM-7720 : (72 x 72mm, Depth: 95.5mm)
ESM-9420 : (48 x 96mm, Depth: 94.5mm)
ESM-9920 : (96 x 96mm, Depth: 96mm)
Panel CutOut :
ESM-4420 : (46 x 46mm)
ESM-4920 : (92 x 46mm)
ESM-7720 : (69 x 69mm)
ESM-9420 : (46 x 92mm)
ESM-9920 : (92 x 92mm)
ESM-4920
Temperature Controller ESM - 4920
PS
AS1
AS2
PO
AO1
AO2
ESM-9420
°C
°F
PO
AO1
AO2
PS
AS1
AS2
Temperature
Controller
ESM-9420
Max�mum 15mm / 0.59 �nch
48 mm / 1.89 �nch
10.5 ± 1 mm / 0.41 �nch 84 mm / 3.31 �nch
96 mm / 3.78 �nch
ESM-9420
Note-1: If process output �s SSR dr�ver output, pay attent�on to the
1-Before mount�ng the
dev�ce �n your panel,
make sure that the
cutout �s of the r�ght s�ze.
2-Check front panel
gasket pos�t�on
3-Insert the dev�ce
through the cutout. If the
mount�ng clamps are on
the un�t, put out them
before �nsert�ng the un�t
4-Insert the un�t �n the
panel cut-out from the
front s�de.
5- Insert the mount�ng
clamps to the holes that
located top and bottom
s�des of dev�ce and
screw up the f�x�ng
screws unt�l the un�t
completely �mmob�le
w�th�n the panel.
ESM-9920, ESM-9420, ESM-7720 , ESM-4920, ESM-4420
PID Temperature Control Un�ts
- 4 d�g�t process (PV) and 4 d�g�t set (SV) d�splay
- Process �nput (TC, RTD)
- Programmable ON/OFF, P, PI, PD and PID control forms
- Adaptat�on of PID Coeff�c�ents to the system w�th Self-Tune
and AUTO-Tune operat�ons
- Programmable Heat�ng or Cool�ng Funct�ons for Control
Output
- Selectable Alarm Funct�ons for Alarm Output
ESM ser�es temperature controllers are des�gned for measur�ng and
controll�ng a process value. They can be used �n many appl�cat�ons
w�th the�r TC and RTD temperature measurement �nput, mult�-
funct�on control outputs, selectable alarm funct�ons.
They are ma�nly used �n glass, plast�c, petro-chem�stry, text�le,
automot�ve and mach�ne product�on �ndustr�es. Accurate and
advanced controll�ng �s performed w�th selectable ON-OFF, P, PI,
PD, PID and Self Tune and Auto Tune PID funct�ons.
SPECIFICATIONS
Process Input : TC,RTD
Thermocouple (TC): J, K, R, S and T (IEC584.1)(ITS90)
Thermores�stance (RTD): PT-100 (IEC751)(ITS90)
Measurement Range : Please refer to Table-1 for select�on of �nput
type and scale.
Accuracy : ± 0.25% of scale for thermocouple and thermores�stance
Cold Junct�on Compensat�on : Automat�cally ±0.1°C/1°C
L�ne Compensat�on : Max�mum 10 Ohm
Sensor Break Protect�on : Upscale
Sampl�ng Cycle : 3 samples per second
Input F�lter : 1.0 second
Control Form : ON/OFF, P, PI, PD or PID (Control form can be
programmed by the user)
OUTPUT
Process Output : Relay (5A@250V at res�st�ve load) or SSR
Dr�ver Output (Max�mum 24mA, Max. 12V )
Alarm Output : Relay(5A@250V at res�st�ve load) or SSR Dr�ver
Output(Alarm Output - 2) (Max�mum 24mA, Max. 12V )
SUPPLY VOLTAGE
24V ( ±15% ) 50/60Hz - 3VA or 24V ( ±%15 ) - 3W
230V ( ±15% ) 50/60 Hz - 3VA
115V ( ±15% ) 50/60 Hz - 3VA
24V ( ±15% ) 50/60 Hz - 3VA
(It must be determ�ned �n order)
DISPLAY
Process D�splay :
ESM-4420 : 10.1 mm Red 4 d�g�t LED D�splay
ESM-4920 : 13.2 mm Red 4 d�g�t LED D�splay
ESM-7720 : 13.2 mm Red 4 d�g�t LED D�splay
ESM-9420 : 10.1 mm Red 4 d�g�t LED D�splay
ESM-9920 : 19 mm Red 4 d�g�t LED D�splay
Set Value D�splay :
ESM-4420 : 8 mm Green 4 d�g�ts LED D�splay
ESM-4920 : 8 mm Green 4 d�g�ts LED D�splay
ESM-7720 : 9.1 mm Green 4 d�g�ts LED D�splay
ESM-9420 : 8 mm Green 4 d�g�ts LED D�splay
ESM 9920 : 10.8 mm Green 4 d�g�ts LED D�splay
Leds : PS (Process Set Value), PO (Process Output Status Led) ,
AS1, AS2 (Alarm Set Values), AO1, AO2 (Alarm Output Status
Electr�cal W�r�ngs
Introduct�on Brochure. ENG ESM-XX20 01 V14 10/19
: Process �nput type select�on ; (Default: )
: J type (Fe,Cu,N�) Thermocouple , -200ºC,900ºC ; -328ºF,1652ºF
: K type (N�,Cr,N�) Thermocouple , -200ºC,1300ºC ; -328ºF,2372ºF
: R type (Pt13%RhPt) Thermocouple , 0ºC,1700ºC ; 32ºF,3092ºF
: S type (Pt10%RhPt) Thermocouple , 0ºC,1700ºC ; 32ºF,3092ºF
: T type (Cu,Cu,N�) Thermocouple , -200ºC,400ºC ; -328ºF,752ºF
: Pt - 100 , -200ºC,650ºC ; -328ºF,1202ºF
: Pt - 100 , -199.9ºC,650.0ºC ; -199.9ºF,999.9ºF
: Un�t Select�on. or can be chosen. (Default )
: Operat�on Scale m�n�mum (Low L�m�t) value. It changes
accord�ng to the process �nput type and scale. (Default: -200)
: Operat�on Scale max�mum (H�gh L�m�t) value. It changes
accord�ng to the process �nput type and scale. (Default: 900)
: Process Set value Low L�m�t. M�n�mum set value �s def�ned w�th
th�s parameter. It changes accord�ng to the process �nput type and
scale. (Default: -200)
: Process Set value H�gh L�m�t. Max�mum set value �s def�ned w�th
th�s parameter. It changes accord�ng to the process �nput type and scale.
(Default: 900)
: D�splay offset for process value. It can be adjusted from -10% of
scale to 10% of scale. It �s added to the process d�splay value.
(Default: 0)
Ma�n Screen
Press PSET
Button.
Press �ncrement
or decrement
button to change
Process Set value.
Ma�n Screen
Press ASET/OK Button
to save new Process
set value and return
the ma�n screen.
Press
ASET/OK
Button.
Press �ncrement or
decrement button
to change Alarm1
Set value.
Press ASET/OK
Button to save
new Alarm set
value and return
the ma�n screen.
Press �ncrement
or decrement
button to change
Alarm2 Set value.
Press ASET/OK
Button to save
new Alarm set
value and return
the ma�n screen.
Ma�n Screen
Ma�n Screen After 5 sec. Password Screen
To enter Program menu
press button for 5
seconds.
Press ASET/OK
Button to access
Password Screen.
Enter Password w�th
�ncrement or
decrement buttons.
Approve
password w�th
ASET/OK Button.
Çalışma Ekranı
To enter the Sensor
Break Output Value,
press ASET/OK
button for 5 seconds.
Change the Sensor
Break Output Value
w�th �ncrement and
decrement buttons.
Press PSET button to ex�t
w�thout sav�ng the value.
Press ASET/OK button to ex�t and save.
Start�ng the Tune operat�on
1-Enter to the programm�ng sect�on
2-Select or , parameter �n menu. Press ASET/OK
button for sav�ng the parameter and turn to the ma�n operat�on screen.
3-Observe that “ ” bl�nks �n set d�splay.
Note- For start�ng the Self Tune operat�on.
Heat�ng Tune Operat�on: Process value must be lower than process set
value at least 5% of full scale.
Cool�ng Tune Operat�on: Process value must be greater than process
set value at least 5%of the full scale . If th�s cond�t�on �s not okay,
Bl�nks on the screen for 10 seconds.
Cancel�ng Tune operat�on :
1-If sensor breaks;
2-If Tune operat�on can not be completed �n 8 hours;
3-Wh�le heat�ng Tune �s runn�ng, �f process value becomes greater than
Process Set value;
4-Wh�le cool�ng Tune �s runn�ng, �f process value becomes less than
Process Set value;
5-Wh�le Tune operat�on �s runn�ng, �f user changes the process set
value;
Then Tune operat�on �s canceled, dev�ce cont�nues to run w�th former
PID parameters w�thout chang�ng PID parameters.
: Th�s parameter determ�nes, wh�ch output w�ll be Process control
output. If �s chosen, process output �s relay output, �f �s chosen,
process output �s SSR output. (Default: )
: Process Type Select�on. It can be or . (Default: )
: Process Control Type Select�on. It can be or .
(Default: )
: If tune parameter �s set to , dev�ce start to Self Tune to
calculate PID parameters automat�cally. If tune parameter �s set to ,
dev�ce start to Auto Tune to calculate PID parameters automat�cally.
Th�s parameter �s shown �f = .
(Default: )
: Proport�onal band. It can be adjusted from %1 to %100.
�f = , then th�s parameter can be observed. (Default: 10.0)
: Integral T�me. It can be adjusted from 0 to 3600 second.
�f = , then th�s parameter can be observed. (Default: 100)
: Der�vat�ve T�me. It can be adjusted from 0.0 to 999.9 second.
�f = , then th�s parameter can be observed. (Default: 25.0)
: Output Control Per�od. It can be adjusted from 1 to 150 second.
�f = , then th�s parameter can be observed. (Default: 10)
: Hysteres�s value. It can be adjusted from %0 to %50 of the
Scale ( - ). If = , then th�s parameter can be
observed. (Default: 3)
: Sensor Break Output Value. It can be adjusted from %0 to %100.
(Default: 0.0)
: Soft Start Set value. Dev�ce operates �n Soft Start mode, unt�l the
temperature reaches Soft Start set value. (Default: )
: Soft Start Control Output. Th�s parameter determ�nes soft start
mode control output percentage. (Default: 10.0)
: Soft Start Control T�me. Th�s parameter determ�nes soft start
mode control t�me. (Default: 1)
: Password for access�ng to the programm�ng sect�on. It can be adjusted from
0 to 9999.
If �s 0, password screen �s not observed. If �s d�fferent from 0 and user
enters to the menu pages w�thout enter�ng the password, all the menus can be
observed except protect�on menu . But dev�ce does not allow to do any
: Alarm Hysteres�s value. It can be adjusted from %0 to %50 of the Scale
( - ). (Default: 0)
: Alarm Type Select�on. (Default: )
: Alarm Set Low L�m�t parameter. It can be adjusted from Operat�on Scale
m�n�mum to Alarm Set H�gh L�m�t. (Default: 0)
: Alarm Set H�gh L�m�t parameter. It can be adjusted from Alarm Set Low
L�m�t to Operat�on Scale m�n�mum. (Default: 500)
: Alarm on Delay T�me. It can be adjusted from 0 to 9999 seconds.
(Default: 0)
: Alarm off Delay T�me. It can be adjusted from 0 to 9998 seconds. If �t �s
h�gher than 9998, �s seen on the screen and Alarm Latch�ng Output �s
selected. (Default: 0)
: Alarm Hysteres�s value. It can be adjusted from %0 to %50 of the Scale
( - ). (Default: 0)
: Alarm type select�on. (Default: )
: Alarm Set Low L�m�t parameter. It can be adjusted from Operat�on Scale
m�n�mum to Alarm Set H�gh L�m�t. (Default: 0)
: Alarm Set H�gh L�m�t parameter. It can be adjusted from Alarm Set Low
L�m�t to Operat�on Scale max�mum. (Default: 500)
: Alarm on Delay T�me. It can be adjusted from 0 to 9999 seconds.
(Default: 0)
: Alarm off Delay T�me. It can be adjusted from 0 to 9998 seconds. If �t �s
h�gher than 9998, �s seen on the screen and Alarm Latch�ng Output �s
selected. (Default: 0)
NOTE: Alarm-2 parameters( , , , , , ) are act�ve,
�f parameter �s set as .
Note: User can ex�t from Set Value sect�on w�thout sav�ng the
values by press�ng button.
If no operat�on for 120 seconds, dev�ce automat�cally ex�ts from
Set Value sect�on .
Note: If user does not do anyth�ng for 120 seconds wh�le dev�ce �s on programm�ng
sect�on, dev�ce turns to operat�on screen.
Note: If user does not do anyth�ng for 120 seconds wh�le dev�ce �s on th�s sect�on,
dev�ce turns to operat�on screen.
Note-2: Sensor Break Output Value can be adjusted on programm�ng sect�on too.
Access and Change Set Values Easy Access D�agram For Program Parameters
Easy Access D�agram For Sensor Break Output Value
Tune Operat�on
: Process Menu Parameters
: Control Menu Parameters
: Alarm Menu Parameters
: Protect�on Menu Parameter
Alarm Types
Note: If process �nput type select�on( ) �s changed, , ,
, , , , , , , , and
parameters may need to be updated accord�ng to the �nput type
select�on.
ESM-4420 ( 48x48 DIN 1/16 )
ESM-4920 ( 96x48 DIN 1/8 )
ESM-7720 ( 72x72 DIN S�ze )
ESM-9420 ( 48x96 DIN 1/8 )
ESM-9920 ( 96x96 DIN 1/4 )
1- Sensor fa�lure �n analog �nputs. Sensor
connect�on �s wrong or there �s no sensor
connect�on.
2- If value that �s read from the analog �nput �s
lower than process set low l�m�t parameter
, value on the top d�splay starts to bl�nk
l�ke on the p�cture.
3- If value that �s read from the analog �nput �s
h�gher than process set h�gh l�m�t parameter
value , value on the top d�splay starts to
bl�nk l�ke on the p�cture.
4- If programm�ng sect�on enter�ng password
�s d�fferent from “0” and user accesses to the
parameter by ASET/OK button w�thout
enter�ng the password and wants to change a
parameter, the warn�ng message �s shown on
the bottom d�splay as shown on the left.
Dev�ce does not allow to do any changes
w�thout enter�ng the password correctly.
5- In programm�ng sect�on, when Tune
operat�on �s selected , �f warn�ng wh�ch �s
shown on the left bl�nks �n operat�on screen
for 10 seconds, �t means that start cond�t�ons
�s not okay for Tune operat�on.
Before beg�nn�ng �nstallat�on of th�s product, please
read the �nstruct�on manual and warn�ngs below
In package ,
-One p�ece un�t
-Two p�eces mount�ng clamp
-One p�ece �nstruct�on manual
A v�sual �nspect�on of th�s product for poss�ble damage occured
dur�ng sh�pment �s recommended before �nstallat�on. It �s your
respons�b�l�ty to ensure that qual�f�ed mechan�cal and electr�cal
techn�c�ans �nstall th�s product.
If there �s danger of ser�ous acc�dent result�ng from a fa�lure or
defect �n th�s un�t, power off the system and the electr�cal
connect�on of the dev�ce from the system.
The un�t �s normally suppl�ed w�thout a power sw�tch or a fuse. Use
power sw�tch and fuse as requ�red.
Be sure to use the rated power supply voltage to protect the un�t
aga�nst damage and to prevent fa�lure.
Keep the power off unt�l all of the w�r�ng �s completed so that
electr�c shock and trouble w�th the un�t can be prevented.
Never attempt to d�sassemble, mod�fy or repa�r th�s un�t.
Tamper�ng w�th the un�t may results �n malfunct�on, electr�c shock
or f�re.
Do not use the un�t �n combust�ble or explos�ve gaseous
atmospheres. Dur�ng the equ�pment �s putted �n hole on the metal
panel wh�le mechan�cal �nstallat�on some metal burrs can cause
�njury on hands, you must be careful.
Montage of the product on a system must be done w�th �t’s
mount�ng clamp. Do not do the montage of the dev�ce w�th
�nappropr�ate mount�ng clamp. Be sure that dev�ce w�ll not fall
wh�le do�ng the montage.
It �s your respons�b�l�ty �f th�s equ�pment �s used �n a manner not
spec�f�ed �n th�s �nstruct�on manual.
EMKO Elektron�k warrants that the equ�pment del�vered �s free
from defects �n mater�al and workmansh�p. Th�s warranty �s
prov�ded for a per�od of two years. The warranty per�od starts from
the del�very date.
Th�s warranty �s �n force �f duty and respons�b�l�t�es wh�ch are
determ�ned �n warranty document and �nstruct�on manual performs
Repa�rs should only be performed by tra�ned and spec�al�zed
personnel. Cut power to the dev�ce before access�ng �nternal parts.
Do not clean the case w�th hydrocarbon-based solvents (Petrol,
Tr�chlorethylene etc.). Use of these solvents can reduce the
mechan�cal rel�ab�l�ty of the dev�ce. Use a cloth dampened �n ethyl
alcohol or water to clean the external plast�c case.
Manufacturer Informat�on:
Emko Elektron�k Sanay�ve T�caret A.Ş.
Dem�rtaşOrgan�ze Sanay�Bölges�Karanf�l Sk. No:6 16369
BURSA/TURKEY
Phone : +90 224 261 1900
Fax : +90 224 261 1912
Repa�r and Ma�ntenance Serv�ce Informat�on:
Emko Elektron�k Sanay�ve T�caret A.Ş.
Dem�rtaşOrgan�ze Sanay�Bölges�Karanf�l Sk. No:6 16369
BURSA/TURKEY
Phone : +90 224 261 1900
Fax : +90 224 261 1912
Thank you very much for your preference to
use Emko Elektron�k products, please v�s�t our
web page to download deta�led user manual.
Error Messages
Installat�on
Warranty
Ma�ntenance
Other Informat�ons
Order�ng Informat�on

This manual suits for next models

5

Other EMKO Measuring Instrument manuals

EMKO ERM-3770 User manual

EMKO

EMKO ERM-3770 User manual

EMKO EDA-3700 User manual

EMKO

EMKO EDA-3700 User manual

EMKO RS Pro ESM- 00 Series User manual

EMKO

EMKO RS Pro ESM- 00 Series User manual

Popular Measuring Instrument manuals by other brands

Keysight Technologies U4164A Service guide

Keysight Technologies

Keysight Technologies U4164A Service guide

Inficon CMS5000 instruction sheet

Inficon

Inficon CMS5000 instruction sheet

Velleman EMDIN02 manual

Velleman

Velleman EMDIN02 manual

Momento DELTA SIGMA Operator's manual

Momento

Momento DELTA SIGMA Operator's manual

Datum DTR80R operating instructions

Datum

Datum DTR80R operating instructions

Sonel MIC-2510 operating manual

Sonel

Sonel MIC-2510 operating manual

Dini Argeo DFWIECEX Technical manual

Dini Argeo

Dini Argeo DFWIECEX Technical manual

T4W TW-6 Operation manual

T4W

T4W TW-6 Operation manual

Milwaukee CALIBRATION 2238-20 Operator's manual

Milwaukee

Milwaukee CALIBRATION 2238-20 Operator's manual

Trotec BZ06 manual

Trotec

Trotec BZ06 manual

Cerlic MultiTracker manual

Cerlic

Cerlic MultiTracker manual

Siemens Pointek CLS200 operating instructions

Siemens

Siemens Pointek CLS200 operating instructions

Teracom TST300v2 user manual

Teracom

Teracom TST300v2 user manual

PP Systems EGM-5 Operation manuals

PP Systems

PP Systems EGM-5 Operation manuals

HEIDENHAIN LC 182 Mounting instructions

HEIDENHAIN

HEIDENHAIN LC 182 Mounting instructions

Velleman DVM030 user manual

Velleman

Velleman DVM030 user manual

Salter Labs RO2 check quick start guide

Salter Labs

Salter Labs RO2 check quick start guide

Hanna Instruments pH 300 instruction manual

Hanna Instruments

Hanna Instruments pH 300 instruction manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.