Earth wire
Neutral wire
Live wire
RESET
LOGON
BACK
HEALTHY
FAU LT
SYS FAULT
RF1 RF2
Operating
temperature -10 to +55 °C
Storage
temperature 5 to 30 °C
Humidity 0 to 95% non-condensing
IP rating IP54
Battery backup 1 x 6V 4Ah Yuasa NP4-6 (sold separately)
For information on routine battery changes, refer to the Universal PSU
instructions (TSD042)
Power requirements Mains powered 220 to 240 VAC, 50 Hz
Current consumption 44 mA (normal operation)
55.5 mA (with mains disconnected)
Battery standby time 72 hours*
*Typical 5 year battery life based on normal usage.
Note; if 72 hours battery standby is required, it is recommended that the
battery is replaced every 3 years.
Operating frequency 868 MHz
Output transmitter
power Auto adjusting 0 to 14 dBm (0 to 25 mW)
Dimensions (W x H x D) 270 x 205 x 75 mm
Weight 1.9 kg (including battery)
1.15 kg (excluding battery)
Location Type A: For indoor use
2012/19/EU (WEEE directive):
Products marked with this symbol cannot be
disposed of as unsorted municipal waste in the
European Union. For proper recycling, return this
product to your local supplier upon purchase of
equivalent new equipment, or dispose of it at
designated collection points. For more information
see www.recyclethis.info
Dispose of your batteries in an environmentally
friendly manner according to your local regulations.
European Union
directives
EMS declares that this device is in compliance with
Directive 2014/53/EU. The full text of the EU
declaration of conformity is available at the following
internet address: www.emsgroup.co.uk
Approved to EN54-4:1998 Incorporating Amendments Nos. 1 and
2. Fire detection and fire alarm systems.
Part 4: Power supply equipment.
EN54-18:2005. Fire detection and fire alarm
systems. Part 18: Input/output devices.
EN54-25:2008. Incorporating corrigenda September
2010 and March 2012. Fire detection and fire alarm
systems. Part 25: Components using radio links.
Certification
Certification body
CPR DoP 0359-CPR-0046
9 Configuration
The RCC’s programming and loop address are configured within
the menu structure of the radio hub.
8 Applying power
Connect the 6V 4Ah battery (sold separately) and apply power to
the RCC. The normal LED states for the RCC are as below:
10 Close RCC
Healthy LED - green LED will be on.
Fault LED - yellow LED will be off.
Sys fault LED - yellow LED will be off.
The RCC is powered from a 220 to 240 VAC supply and requires
a 5 A protection device.
Power cables should only be passed via the access points
available.
Flame retardant cable glands must be used.
DO NOT leave excess cable in the RCC.
Cable should have a minimum cross section of 1.5 mm2
An all-pole mains switch should be provided as part of the
building installation.
RADIO CLUSTER COMMUNICATOR
POWER
FAU LT
Refer to the programming manual (MK98) for full programming
information.
Free to download from
www.emsgroup.co.uk
0905
10
Ensure that the RCC PCB is correctly inserted and the PCB
retaining screws are refitted.
Refit the RCC lid, ensuring LEDs are not damaged by the light
pipe when refitting.
Manufacturer Carrier Manufacturing Polska Sp. Z o.o. Ul.
Kolejowa 24. 39-100 Ropczyce, Poland
Year of
manufacture See devices serial number label
Regulatory informationSpecification
EN54-4 UNIVERSAL PSU
FC-60-1000
INPUT: 220-240VAC, 50Hz, 0.3A
OUTPUT: 5.0-8.5VDC, 0.8A MAX
STATUS
FAULT
MAINS / CHARGER FAIL
BATTERY LOW
BATTERY FAIL
START
INPUT
L N E
For additional information refer to TSD042
0359-CPR-00267
15 0905
7 Connection wiring
©2021 EMS Ltd. All rights reserved Page 2 of 2 TSD053-99 Iss 26 15/12/2021 AJM