ENDA ET1413A User manual

Technical Specifications
CONTROL
Control type Single-setpoint control
On-Off control
Control algorithm
Hysteresis 0.5°C.
ENVIRONMENTAL CONDITIONS
Height Max. 2000m
Ambient/storage temperature
Max. relative humidity
0 ... +50°C/-25 ... 70°C (with no icing)
Protection class According to EN 60529
Rare panel : IP20
Thank you for choosing ENDA ET1413A temperature controller
Connection Diagram
1/2
SÝSEL MÜHENDÝSLÝK ELEKTRONÝK SAN. VE TÝC. A.Þ.
Yukarý Dudullu Barbaros Cad. Kutup Sok. No:20 34775 - ÜMRANÝYE/ÝSTANBUL/TÜRKÝYE
Tel : +90 216 499 46 64 Pbx. Fax : +90 216 365 74 01
url : www.enda.com.tr
HOUSING
Housing type
Dimensions W77xH35xD71mm
Weight Approx.223g (After packing)
Enclosure material
ENDA ET1413A NTC FAN CONTROL THERMOSTAT
Order Code : ET1413A-NTC-     
1
Supply Voltage
230VAC...230V AC
24............24V AC/DC
12............12V AC/DC
* 35 x 77mm sized.
* 4 digits display.
* Decimal display feature.
* 3 contact outputs for the fan and air condition control.
* For air-condition,on-off cooling control.
* Fan and air-condition is done manually on the front
panel keys.
* CE marked according to European Norms.
Supply voltage 230V AC +%10 -%20, 50/60Hz or 24V AC/DC ±%10, or50/60Hz 12V AC/DC ±%10, 50/60Hz
Power consumption Max. 4.5VA
2.5mm²screw-terminal connections
4 digits, 12.5mm, 7 segment yellow LED
Connection
Scale
Sensitivity/Accuracy
Indicator
EMC
ELECTRICAL CHARACTERISTICS
-50 ... +110°C
0.1°C / ±1°C
Front panel : IP65
OUTPUTS
A/C (Air-condition output)
Fan 1
Life expectancy for relay
Relay: 250V AC, 8A (for resistive load), NO+NC; 1/2 HP 240V AC (for inductive load)CosF= 0.4
Without load 30.000.000 switching; 250V AC, 8A resistive load 100.000 switching.
Relay: 250V AC, 8A (for resistive load), NO; 1/2 HP 240V AC (for inductive load)CosF= 0.4
Relay: 250V AC, 8A (for resistive load), NO; 1/2 HP 240V AC (for inductive load)CosF= 0.4
Fan 2
Panel cut-out
Dimensions
71mm
29mm
Flush mounting
clamp
Flush mounting
clamp
1
35mm
77mm
SET
°C
SET
ET1413A
ENDA
ENDA
A/C
SET
°C
SET
ET1413A
A/C
NTC SENSOR
10 11 12
SN: XXXXXXXXX
ET1413A-NTC-24
DIGITAL THERMOSTAT
ENDA INDUSTRIAL ELECTRONICS
24V AC +10% -20%
50/60Hz 4.5VA
FAN1
250V AC 8A
RESISTIVE LOAD
FAN2
250V AC 8A
RESISTIVE LOAD
NTC SENSOR
A/C
250V AC 8A
RESISTIVE LOAD
1 2 3 4 5 6 7 8 9 10 11 12
SN: XXXXXXXXX
ET1413A-NTC-12
DIGITAL THERMOSTAT
ENDA INDUSTRIAL ELECTRONICS
12V AC +10% -20%
50/60Hz 4.5VA
FAN1
250V AC 8A
RESISTIVE LOAD
FAN2
250V AC 8A
RESISTIVE LOAD
NTC SENSOR
A/C
250V AC 8A
RESISTIVE LOAD
1 2 3 4 5 6 7 8 9 10 11 12
SN: XXXXXXXXX
ET1413A-NTC-230VAC
DIGITAL THERMOSTAT
ENDA INDUSTRIAL ELECTRONICS
230V AC +10% -20%
50/60Hz 4.5VA
FAN1
250V AC 8A
RESISTIVE LOAD
FAN2
250V AC 8A
RESISTIVE LOAD
NTC SENSOR
A/C
250V AC 8A
RESISTIVE LOAD
1 2 3 4 5 6 7 8 9 10 11 12
Please read this document carefully before using this product. The guarantee will be
invalidated if the device is damaged by not following instructions detailed in the
manual. The company shall not be responsible for any damage or losses however
caused, which may be experienced as a result of the installation or use of this product.
ENDA ET1413A is intended for installation in control panels. Make sure that the device is used
only for intended purpose. The electrical connections must be carried out by a qualified staff
and must be according to the relevant locally applicable regulations. During an installation, all of
the cables that are connected to the device must be free of electrical power. The device must be
protected against inadmissible humidity, vibrations, severe soiling and make sure that the
operation temperature is not exceeded. The cables should not be close to the power cables or
components.
Holding screw
0.4-0.5Nm.
Equipment is protected throughout
by DOUBLE INSULATION
Neutral
230V AC
Supply
Switch
Note:
Cable size: 1,5mm²
Fuse
F 100 mA
250V AC
Fuse should
be connected
1) Mains supply cords shall meet the requirements of
IEC 60227 or IEC 60245.
2) In accordance with the safety regulations, the power
supply switch shall bring the identification of the
relevant instrument and it should be easily
accessible by the operator.
80%, up to 31°C decreasing linearly 50% at 40°C
Do not use the device in locations subject to corrosive and flammable gasses.
Safety requirements
The device is designed to operate in controlled electromagnetic environment)
EN 61326-1: 1997, A1: 1998, A2: 2001 (Performance criterion B is satisfied for EMC tests.
EN 61010-1: 2001 (Pollution degree 2, overvoltage category II)
Suitable for flush-panel mounting.
Self extinguishing plastics
While cleaning the device, solvents (thinner, benzine, acid etc.) or corrosive materials must not be used.
For removing mounting clamps:
Push the flush-mounting
clamp in direction 1as shown
in the figure below. Then, pull
out the clamp in direction 2.
Note:
ET1413A-E-01
Depth
Panel
2
71mm 5mm
SN: XXXXXXXXX
ET1413A-NTC-230VAC
DIGITAL THERMOSTAT
ENDA INDUSTRIAL ELECTRONICS
230V AC +10% -20%
50/60Hz 4.5VA
FAN1
250V AC 8A
RESISTIVE LOAD
FAN2
250V AC 8A
RESISTIVE LOAD
A/C
250V AC 8A
RESISTIVE LOAD
1 2 3 4 5 6 7 8 9
7
8
SUPPLY:
NOTE:
184-253V AC
50/60Hz 4,5VA
Line
1) Panel thickness
should be maximum
7 mm.
2) If there is no 60mm
free space at the back
side of the device, it
would be difficult to
remove it from the
panel.
°C
ET1413A
ENDA
SET
A/C
FAN2
LED FAN1
LED Air-Condition LED (A/C) If air-condition is working,this LED lights up.
SET
In run mode,this button is pressed once,while no fan has been deactivated ;fan1 engaged,this
button is pressed again ;fan1 is switched off and the fan2 is engaged.
In programming mode; set the parameters for selecting parameters and values are constantly
increasing provides.This key is pressed,set the numerical value increases
rapidly.
Terms
In run mode, the key is pressed, the programming mode is entered, the parameter has been
selected;shows the value of parameters. To set the selected parameter; key held down while pressing
keys set the parameter values. In run mode,press the key once the air-condition (A/C) LED is
lights up and air-condition is engaged. key is pressed once again, A/C LED goes off and the air-condition
will be disabled.
SET
SET
SET
SET
Pressing this key once while in running mode;fan2 is switched off.Once again this button is
pressed;fan1 is deactivated.
In programming mode,reducing the value of selecting parameters and the set.If this key is pressed
continuously,set the numerical value decreases quickly.
-110-0and 110.0°C parameters can be
adjusted to the desired of the specified value.
Lol.I and upl.I parameters can be adjusted
to the desired value of the specified value.
Adjustable between 0-20°C.
Temperature
set value
The lower limit
of the setpoint
Measurement
temperature
SET
Programming Mode
Initial Value
Run Mode
SET
SET
SET
SET
If the key is pressd once,the
A/C LED turns on and air-condition
is activated.
If the key is pressed once,the A/C LED turns off
and air-condition will be disabled.
SET
A/C LED
If a key is pressed within 5 seconds,the mode of
operation will be resumed.
set
lol.ý
upl ý.
hy5.
The upper limit
of the setpoint
Hysteresis value
for the set value
15.0
22.0
.
22.0 22.0
.
-50.0°C and upl.I parameters can be adjusted
to the desired value of the specified value.
SET
50.0
110.0
5.0
key is pressed for 3 seconds, the programming
mode is entered.
The device when it receives power,air-condition output is
not active.
A/C output,begins in closed position To activate the A/C output;
the SET key must be pressed once.
HYS
Pfa
Means, thermostat probe is short-circuit.
PsC
Means,thermostat probe is broken.
Error Messages
Temperature value is higher than the scale.
Temperature value is lower than the scale.
ET1413A-E-01
2/2
Output Table
t
A/C Output (air-condition output)
SET +
SET
SET SET

Other ENDA Thermostat manuals

ENDA ETC1311 User manual

ENDA

ENDA ETC1311 User manual

ENDA EDT3423A User manual

ENDA

ENDA EDT3423A User manual

ENDA ET1412 User manual

ENDA

ENDA ET1412 User manual

ENDA ET1411 User manual

ENDA

ENDA ET1411 User manual

ENDA EDT2411A User manual

ENDA

ENDA EDT2411A User manual

ENDA ETC1311 User manual

ENDA

ENDA ETC1311 User manual

ENDA ATC9311 User manual

ENDA

ENDA ATC9311 User manual

ENDA ET1412 User manual

ENDA

ENDA ET1412 User manual

Popular Thermostat manuals by other brands

suntouch FloorStat 500600-120 manual

suntouch

suntouch FloorStat 500600-120 manual

Hunter 144860 Installation and operation manual

Hunter

Hunter 144860 Installation and operation manual

Venstar T1700 specification

Venstar

Venstar T1700 specification

Honeywell RTH7400 series installation guide

Honeywell

Honeywell RTH7400 series installation guide

Warmup UCCG Easy programming instructions

Warmup

Warmup UCCG Easy programming instructions

Carel thT user manual

Carel

Carel thT user manual

Vysal Vysa-Therm 3000 owner's manual

Vysal

Vysal Vysa-Therm 3000 owner's manual

Danfoss REP24CO installation instructions

Danfoss

Danfoss REP24CO installation instructions

Honeywell CM720 installation guide

Honeywell

Honeywell CM720 installation guide

Vive Comfort TP-N-631 installation manual

Vive Comfort

Vive Comfort TP-N-631 installation manual

MITS STN855W installation manual

MITS

MITS STN855W installation manual

Penn A19BAC installation instructions

Penn

Penn A19BAC installation instructions

White Rodgers 90 SERIES Installation &  configuration guide

White Rodgers

White Rodgers 90 SERIES Installation & configuration guide

Full Gauge Microsol E manual

Full Gauge

Full Gauge Microsol E manual

Verdant VX Series Installation guides

Verdant

Verdant VX Series Installation guides

TECH ST-450zPID user manual

TECH

TECH ST-450zPID user manual

Dimplex KRRV 003 user manual

Dimplex

Dimplex KRRV 003 user manual

HRW TLC-FCR-T manual

HRW

HRW TLC-FCR-T manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.