Endress+Hauser ControlCare SPC150 User manual

ControlCare SPC150
BA045S/04/en/03.06
Version 1.00.xx
70103679
Operating Instructions
ControlCare SPC150
12" Panel PC as P View Web-client


ControlCare Panel PC SPC150 Table of Contents
Endress+Hauser 1
Table of Contents
Revision History . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Registered Trademarks . . . . . . . . . . . . . . . . . . . . . . 2
1 Safety . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.1 Designated used . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.2 Installation, commissioning and operation . . . . . . . . 3
1.3 Operational safety . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.4 Declaration of conformity . . . . . . . . . . . . . . . . . . . . 3
1.5 Technical improvement . . . . . . . . . . . . . . . . . . . . . . 3
1.6 Conventions and icons . . . . . . . . . . . . . . . . . . . . . . 4
2 Identification . . . . . . . . . . . . . . . . . . . . 5
2.1 Unpacking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.1.1 Visual check . . . . . . . . . . . . . . . . . . . . . . . . 5
2.1.2 Scope of delivery . . . . . . . . . . . . . . . . . . . . . 5
2.1.3 Storage and transport . . . . . . . . . . . . . . . . . . 5
2.2 Device name . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3 Function and System Design . . . . . . . . 7
3.1 Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.2 System design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
4 Mechanical Installation . . . . . . . . . . . . 8
4.1 Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
4.1.1 Temperature . . . . . . . . . . . . . . . . . . . . . . . . 8
4.1.2 Ventilation . . . . . . . . . . . . . . . . . . . . . . . . . 8
4.1.3 Cut-out . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
4.1.4 Fastening and sealing . . . . . . . . . . . . . . . . . . 9
5 Electrical Installation . . . . . . . . . . . . . 10
5.1 General precautions . . . . . . . . . . . . . . . . . . . . . . . . 10
5.2 Power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
5.2.1 24 VDC power supply . . . . . . . . . . . . . . . . 11
5.2.2 Plug connector . . . . . . . . . . . . . . . . . . . . . 11
5.2.3 Option: ventilator kit . . . . . . . . . . . . . . . . . 11
5.3 Peripherals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
5.3.1 Access . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
5.3.2 Keyboard . . . . . . . . . . . . . . . . . . . . . . . . . . 12
5.3.3 Mouse . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
5.3.4 Monitor . . . . . . . . . . . . . . . . . . . . . . . . . . 13
5.3.5 Ethernet network . . . . . . . . . . . . . . . . . . . 13
5.3.6 Compact flash . . . . . . . . . . . . . . . . . . . . . . 13
5.4 External interfaces . . . . . . . . . . . . . . . . . . . . . . . . . 14
5.4.1 Serial port COM1 [RS-232] . . . . . . . . . . . . 14
5.4.2 Ethernet ports . . . . . . . . . . . . . . . . . . . . . . 14
5.4.3 USB ports . . . . . . . . . . . . . . . . . . . . . . . . . 14
5.4.4 VGA port . . . . . . . . . . . . . . . . . . . . . . . . . 15
5.4.5 PS/2 keyboard port . . . . . . . . . . . . . . . . . . 15
6 Commissioning and Operation . . . . . 16
6.1 Start-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
6.2 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
7 Maintenance . . . . . . . . . . . . . . . . . . . 17
7.1 General precautions . . . . . . . . . . . . . . . . . . . . . . . . 17
7.2 Housing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
7.2.1 Construction . . . . . . . . . . . . . . . . . . . . . . . 17
7.2.2 Opening the housing . . . . . . . . . . . . . . . . . 18
7.3 Back-up battery . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
7.3.1 Exchanging the battery . . . . . . . . . . . . . . . 19
7.4 Display backlights . . . . . . . . . . . . . . . . . . . . . . . . . 20
8 Technical Data . . . . . . . . . . . . . . . . . 21
8.1 Panel PC specification . . . . . . . . . . . . . . . . . . . . . . 21
8.2 Operating conditions . . . . . . . . . . . . . . . . . . . . . . . 22
8.3 Mechanical construction . . . . . . . . . . . . . . . . . . . . 22
8.4 Certificates and approvals . . . . . . . . . . . . . . . . . . . 23
Index . . . . . . . . . . . . . . . . . . . . . . . . . 24

ControlCare Panel PC SPC150
2Endress+Hauser
Revision History
Registered Trademarks
PROFIBUS®
Registered trademark of the PROFIBUS User Organisation, Karlsruhe Germany.
FOUNDATIONTM Fieldbus
Trademark of the Fieldbus Foundation, Austin, TX 78759, USA
HART®
Registered trademark of the HART Communication Foundation, Houston, USA
Microsoft®, Windows® , Windows 2000®,Windows XP® and the Microsoft logo are registered
trademarks of the Microsoft Corporation.
Acrobat Reader®is a registered trade mark of the Adobe Systems Incorporated.
All other brand and product names are trademarks or registered trademarks of the companies and
organisations in question
Product
version
Manual Changes Remarks
1.00.xx BA045S/04/en/03.06 Original

ControlCare Panel PC SPC150 1Safety
Endress+Hauser 3
1Safety
1.1 Designated used
ControlCare Panel PC SPC150 is an industrial computer with integrated 12" touchscreen as well as
preinstalled P View Web-client. The Panel PC may be used only as described in this manual and
only with the components recommended by Endress+Hauser, which where necessary must have
appropriate certification.
1.2 Installation, commissioning and operation
ControlCare Panel PC SPC150 must be installed, connected, operated and maintained according to
the instructions in this manual: personnel must be authorised and suitably qualified.
Prerequisites for proper and safe operation of the product are its correct transport, correct storage,
installation and mounting as well as careful operation and maintenance.
1.3 Operational safety
Operational environment ControlCare Panel PC SPC150 fulfils the harmonised, European standards (EN) for the various
environments in which is designed to operate. The permissible operating conditions as described in
the technical data must be upheld.
Explosion hazardous areas The device may not be installed in explosion hazardous areas.
Repair Do not open the device housing. It contains no components that need be maintained or can be
repaired by the user. In the event of a fault or defect, return the device to the manufacturer. Opening
the device housing invalidates the guarantee.
1.4 Declaration of conformity
CE Mark ControlCare Panel PC SPC350 fulfils the requirements of the EU Directive 89/336/EEC
"Electromagnetic Combatibility" (EMC Directive).
• Interference emmision: EN 50022:1998 Classe A (Product standard ITE)
EN 50011:1998 Group 1 Classe A (Product standard ISM)
• Interference Immunity: IEC 61000-6-2: 1999
Interference Immunity: Industrial Environment
4A declaration in accordance with the above-mention standards has been issued and can be acquired
from Endress+Hauser Process Solutions AG.
1.5 Technical improvement
Endress+Hauser reserves the right to make technical improvements to its software and equipment
at any time and without prior notification. Where such improvements have no effect on the
operation of the equipment, they are not documentated. If the improvements effect operation, a
new version of the operating instructions is normally issued.

1Safety ControlCare Panel PC SPC150
4Endress+Hauser
1.6 Conventions and icons
In order to highlight safety relevant or alternative operating procedures in the manual, the following
conventions have been used, each indicated by a corresponding icon in the margin.
Safety conventions
Explosion protection .
Electrical symbols .
Icon Meaning
A note highlights actions or procedures which, if not performed correctly, may indirectly affect operation
or may lead to an instrument response which is not planned
Caution!
Caution highlights actions or procedures which, if not performed correctly, may lead to personal injury or
incorrect functioning of the instrument
Warning!
A warning highlights actions or procedures which, if not performed correctly, will lead to personal injury,
a safety hazard or destruction of the instrument
Icon Meaning
Device certified for use in explosion hazardous area
If the device has this symbol embossed on its name plate it can be installed in an explosion hazardous area
in accordance with the specifications in the certificate or in a safe area
Explosion hazardous area
Symbol used in drawings to indicate explosion hazardous areas. Devices located in and wiring entering
areas with the designation “explosion hazardous areas” must conform with the stated type of protection
Safe area (non-explosion hazardous area)
Symbol used in drawings to indicate, if necessary, non-explosion hazardous areas. Devices located in safe
areas stiill require a certificate if their outputs run into explosion hazardous areas.
Icon Meaning
Direct voltage
A terminal to which or from which a direct current or voltage may be applied or supplied
Alternating voltage
A terminal to which or from which an alternating (sine-wave) current or voltage may be applied or
supplied
Grounded terminal
A grounded terminal, which as far as the operator is concerned, is already grounded by means of an earth
grounding system
Protective grounding (earth) terminal
A terminal which must be connected to earth ground prior to making any other connection to the
equipment
Equipotential connection (earth bonding)
A connection made to the plant grounding system which may be of type e.g. neutral star or equipotential
line according to national or company practice

ControlCare Panel PC SPC150 2 Identification
Endress+Hauser 5
2 Identification
2.1 Unpacking
2.1.1 Visual check
When unpacking:
• Check the packaging of the ControlCare Panel PC SPC150 for visible transport damage
• To avoid damage when unpacking, remove the packing material with care
• Keep the original packing for any further transport of the ControlCare Panel PC SPC150
• Store the accompanying documents in a safe place
If you find that the Panel PC has been damaged in any way, do not put it into operation. In this case,
contact your Endress+Hauser Sales Center. Return the device, where possible in the original
packing, to us.
2.1.2 Scope of delivery
Before installing the device, please check that the delivery is complete and undamaged. The scope
of delivery comprises:
• ControlCare Panel PC SPC150 with preinstalled P View Web-client
• CD-ROM with operating instructions
Options:
• Keyboard with trackball
• Keyboard and mouse
2.1.3 Storage and transport
Although ControlCare Panel PC SPC150 is of robust construction, some of its components are
sensitive to heavy vibrations and shocks. For this reason, the ControlCare Panel PC SPC150 must
be protected against excessive mechanical loads.
The device may only be transported in its original packing, complete with shock-absorbing
components. Make sure that no condensation can form on or within the device when it is
transported in cold weather or is subject to extreme temperature differences.

2 Identification ControlCare Panel PC SPC150
6Endress+Hauser
2.2 Device name
The device name and order code are to be found on the nameplate, which is located at the rear of
the housing.
The device type can be derived from the product code by using the table below:
SPC150 ControlCare Panel PC as P View Web-Client
Monitor
12 12"
Memory extension
A
B
256 MB
512 MB
Compact Flash
1
2
512 MB
1024 MB
Keyboard
A
C
M
No keyboard
Compact keyboard with trackball
Keyboard with optical mouse
Hardware extension
ANone
Options
1None
SPC150
Name
Device information
Technical data
Barcode

ControlCare Panel PC SPC150 3 Function and System Design
Endress+Hauser 7
3 Function and System Design
3.1 Function
ControlCare SPC150 is an industrial PC with preinstalled operating system, Internet Explorer and
P View Web-client. It is supplied as part of a packaged solution that also includes a P View SCADA
application installed on a second computer.
The P View SCADA application acquires process data from the system network via OPC server. The
data is then visualized in various HMI pages that are designed according to customer specifications.
Since P View supports a client-server architecture, the HMI pages can be viewed in every P View
client connected to the system.
The P View Web-client and the P View server communicate via Ethernet in Intranet/Internet,
which can be protected with firewalls or other safety mechanisms. This allows safe, local and
worldwide access to the HMI pages of the P View server. The connection is established by entering
the P View server URL in Internet Explorer - just as in Internet.
Depending upon user requirements, the P View client is automatically started and the connection
to the server established when the Panel PC is switched on. It is also possible to select the HMI
pages that are to be displayed at a particular client. Operation and navigation is via the touchscreen.
3.2 System design
Fig. 3-1 shows a monitoring system with the 19" ControlCare Panel PC acting as P View server.
Process values are collected from the system and made available to the P View Web-clients running
in the ControlCare Panel PC SPC150. The Web-client can be installed in an internal or external
network.
Fig. 3-1: Example for system design with P View Web-server und Web-client
19" ControlCare Panel PC SPC350
as P View server
e.g. in the control room
ControlCare Panel PC SPC150
as P View Web-client
local, e.g. in a cabinet or console
Ethernet
System
ControlCare SPC150
ControlCare SPC350
ControlCare Panel PC SPC150
as P View Web-client
e.g. in an external network
ControlCare SPC150
Network connection

4 Mechanical Installation ControlCare Panel PC SPC150
8Endress+Hauser
4 Mechanical Installation
4.1 Location
ControlCare Panel PCs are designed for use in industrial environments and can be mounted in
racks, cabinets, cabinet doors, consoles or control panels. They are approved for use in closed rooms.
When installing, please observe the specifications in Chapter 8, Technical Data.
4.1.1 Temperature
The Panel PC may not be subjected to direct sunlight or other source of light.
Before installing or commissioning:
• Allow the device enough time to adapt to room temperature.
• If there is any danger of condensation, make sure that the device is absolutely dry before
switching it on.
4.1.2 Ventilation
The temperature of the surrounding air during operation may not exceed +45°C (110°F). It is
important that the device does not overheat during operation.
• Ventilation slits at the top and bottom of the housing allow air to circulate and cool the device
during operation. Ensure that these slits are always free.
• Ensure that there is sufficient volume for the exchange of air within cabinets or consoles. The
clearance around the sides of the Panel PC must be min. 50 mm (2"), at the back min. 20 mm
(0.8").
• In the case of closed industrial housings, care should be taken that the air inside can circulate.
!Note!
• In order to ensure proper ventilation in closed industrial housings, a ventilator kit, which is
mounted on the back of the housing, can be offered as an option.
• If the Panel PC is not mounted vertically, care must be taken that air can circulate properly via
the ventilation slits.
Fig. 4-1: Ventilation
Cooling fins to dissipate the heat
generated by the CPU to the
surrounding air
Ventilator kit (Option)
The rear wall is prepared for
the mounting of a ventilator

ControlCare Panel PC SPC150 4 Mechanical Installation
Endress+Hauser 9
4.1.3 Cut-out
The cut-out for installation should be selected such that it is stabilized by the bracing in the cabinet
or panel. If necessary, bracing must be installed.
• Degree of protection IP 65 is attained only for plate thickness of 2 mm (0.1") or greater.
• It must also be insured that the panel is correctly installed by skilled personnel using the screw
clamps provided and that the rubber gasket is properly seated.
• Check that there is enough clearance to remove the panel from the cut-out.
Fig. 4-2 shows the dimensions in mm (in) for the cut-out
Fig. 4-2: Dimensions in mm (in) for the cut-out
4.1.4 Fastening and sealing
Screw clamps are used to fasten the Panel PC in the cut-out. They are seated in the openings
provided for them in the housing.
• Insert the ControlCare Panel PC SPC150 into the cut-out and hold in position.
• Seat the screw clamps in the openings provided for them.
• Fasten the Panel PC in the cut-out by tightening the screws.
Fig. 4-3: Fastening and sealing
252 (9.92)
314 (12.4)
Cellular rubber gasket
Seal
Fastening
Screw clamp
screw clamp

5 Electrical Installation ControlCare Panel PC SPC150
10 Endress+Hauser
5 Electrical Installation
ControlCare Panel PC SPC150 is an "IT system" in accordance with EN 60950, with supply voltage
of 24 VDC.
5.1 General precautions
Connections for interference free operation:
• The EMC approval requires that signal connections are made with shielded cables and metal
connectors only.
• To ensure optimal electrical shielding, all plugged connections are to be screwed or locked into
position.
• Signal cables may not be laid in the same cable trays as power cables.
• Before commissioning the system, check all cable connections.
• Ensure that the permissible values for voltages and signals are upheld.
Safe discharge of electrical disturbances:
• Connect the Panel PC and cabinet by the shortest possible route to a central earth.
• Ensure good electrical connection between Panel PC and cabinet (low-impedance).
• Use an earth connection conductor of minimum 2.5 mm² (0.1 in2) diameter.
Special precautions for 24 VDC devices:
• The panel PC may be connected to a safety extra low voltage (SELV) circuit only.
• The circuit transformer must fulfil the pertinent standards.

ControlCare Panel PC SPC150 5 Electrical Installation
Endress+Hauser 11
5.2 Power supply
Before connecting up:
• Check that the power supply has the correct voltage.
• Protective earth: Connect the grounding point on the housing to the cabinet earth.
A M4x10 grounding point is to be found on the bottom of the housing, see Fig. 5-1.
View from housing side:
Fig. 5-1: Connection the power supply
5.2.1 24 VDC power supply
ControlCare Panel PC SPC150 requires a 24 VDC (18–36 VDC) power supply. The power supply
must fulfil the requirements of a safely extra low voltage (SELV) circuit to EN 60950.
5.2.2 Plug connector
The 24 VDC socket for the plug connector is to be found on the righthand side of the housing.
Tab. 5-1: Plug connector for 24 VDC
To prepare the Panel PC for operation:
• Connect a 2-core cable to the plug supplied and insert it into socket in the Panel PC housing.
Note the polarity.
• Connect the other end of the cable to a 24 VDC power supply that fulfils the requirements of
a safely extra low voltage (SELV) circuit to EN 60950.
5.2.3 Option: ventilator kit
If a ventilator is used, a separate 24 VDC power supply is required.
Socket PC 4/2-G-7,62
2-pole, pitch: 7.62 mm
Phoenix Contact
Plug PC 4/2-ST-7,62
2-pole, pitch: 7.62 mm
Phoenix Contact
Grounding point
Power supply
M4x10
24 VDC:
PC 4/2-G-7,62
Caution:
Pin assignment
Warnung
+–

5 Electrical Installation ControlCare Panel PC SPC150
12 Endress+Hauser
5.3 Peripherals
ControlCare Panel PC SPC150 offers a number of ports to which peripherals can be connected.
• When using commercial peripherals (USB, PS/2 etc.), it should be noted that their immunity
to electromagnetic interference is normally sufficient for an office environment only.
• Commercial peripherals are suitable for use during commissioning and service. If an external
mouse and keyboard are required during operation, care should be taken that they have a EMC
approval (CE mark) for use in an industrial environment.
• An external keyboard and the touchscreen can be used in parallel.
5.3.1 Access
The ports for peripherals and the external compact flash receptacle are on the bottom of the housing,
see Fig. 5-2:
Fig. 5-2: Connections for peripheral devices
5.3.2 Keyboard
Various keyboard types can be connected to the ControlCare Panel PC SPC150:
• PS/2 keyboard
connected to the PS/2 keyboard socket.
• USB keyboard
connected to the USB port:
for first-time use it is usually necessary to install a USB keyboard driver.
5.3.3 Mouse
Various mouse types can be connected to the ControlCare Panel PC SPC150:
• Serial mouse
connected to the COM1 interface: the corresponding mouse driver must be installed and
configured.
• USB mouse
connected to the USB port:
for first-time use it is usually necessary to install a USB mouse driver.
External Compact Flash
Power supply
Ethernet
VGA monitor port
PS/2 keyboard
USB Port 0
USB Port 1
COM1 serial interface RS-232

ControlCare Panel PC SPC150 5 Electrical Installation
Endress+Hauser 13
5.3.4 Monitor
An external monitor or various other display types can be connected to the VGA interface.
!Note
• It is possible that the use of an external monitor cause an loss of touchscreen picture quality.
• We recommend that external monitors are used for service and diagnosis only.
5.3.5 Ethernet network
ControlCare Panel PC SPC150 is connected to an Ethernet network via the RJ-45 socket.
• For computer-computer connections, use a crossed Ethernet cable.
• For computer-switch connections, use a standard Ethernet cable.
5.3.6 Compact flash
Controlcare Panel PC SPC150 is equipped with an internal compact flash card on which the system
software is stored.
In order to store user data and programs, an external compact flash card is available as an option.
The card receptacle is located at the bottom of the housing and is easily accessible.
Fig. 5-3: Access to the external compact flash card (option)
!Note
• The external card must not be removed during operation.
• Do not "rescue" data to the compact flash card when there is a power failure. A battery-buffered
SDRAM is provided for this purpose.
• An unstable power supply may lead to uncontrolled writing to the storage medium and files can
be overwritten and lost. In order to prevent data loss, a variable voltage an uninetrruptable power
supply should be used.
Exchange of
Compact flash cards

5 Electrical Installation ControlCare Panel PC SPC150
14 Endress+Hauser
5.4 External interfaces
5.4.1 Serial port COM1 [RS-232]
ControlCare Panel PC SPC150 has a serial port (RS-232, V24) with a 9-pin Sub-D male connector
labelled "COM 1".
Tab. 5-1: COM1 (RS-232 serial port)
5.4.2 Ethernet ports
ControlCare Panel PC SPC150 has an Ethernet port with RJ-45 10Base-T female connector labelled
"Ethernet". The controller supports transmission rates of 10 MBit/s and 100 MBit/s.
Tab. 5-2: Ethernet
5.4.3 USB ports
ControlCare Panel PC SPC150 has two Type A 4-pin USB receptacles (double-decker) labelled
"USB A" and "USB B",
Tab. 5-3: USB [double]
Sub-D male connector
9-pin
Pin Signal Description Input/
Output
1 DCD Data Carrier Detect I
2RxD ReceiveData I
3TxD TransmitData O
4 DTR Data Terminal Ready O
5 GND Signal Ground ---
6 DSR Data Set Ready I
7 RTS Request to Send O
8CTS CleartoSend I
9 RI Ring Indicator I
10Base-T
RJ-45 CAT5
Pin Signal Description Input/Output
1 TxD+ 10Base-T Transmit Differential Output
2 TxD- 10Base-T Transmit Differential Output
3 RxD+ 10Base-T Receive Differential Input
4 N.C. not connected ---
5 N.C. not connectedt ---
6 RxD- 10Base-T Receive Differential Input
7 N.C. not connected ---
8 N.C. not connected ---
LED green Link
LED yellow Activity
USB Type A
4-pin
USB A USB B Description
1VCC1VCCPower(+5V/0,5A)
2USB0-2USB1-Data
3USB0+3USB1+Data
4GND4GNDGround
6
7
8
9
1
2
3
4
5
1
8
1
2
3
4

ControlCare Panel PC SPC150 5 Electrical Installation
Endress+Hauser 15
5.4.4 VGA port
ControlCare Panel PC SPC150 has a 15-pin HD-Sub-D port labelled "VGA".
Tab. 5-4: VGA [CRT]
5.4.5 PS/2 keyboard port
ControlCare Panel PC SPC150 has a 6-pin MiniDIN port labelled "PS/2 keyb" for the connection
of an external PS/2 keyboard.
Tab. 5-5: PS/2- keyboard
HD-Sub-D female
connector, 15-pin
Pin Signal Pin Signal Pin Signal
1 RED 6 GND 11 N.C.
2 GREEN 7 GND 12 DDC DAT
3BLUE 8GND 13HSYNC
4 N.C. 9 VCC_VGA (+5V) 14 VSYNC
5GND 10GND 15DDCCLK
MiniDIN female
connector, 6-pin
Pin Signal Description Input/
Output
1 KBDAT Keyboard Data I/O
2 N.C. Not connected ---
3 GND Ground ---
4 VCC-PS/2 (+5V) Power O
5 KBCLK Keyboard Clock I/O
6 N.C. Not connected ---
1
5
11
15
6
10
5
3
2
4
6

6 Commissioning and Operation ControlCare Panel PC SPC150
16 Endress+Hauser
6 Commissioning and Operation
6.1 Start-up
The operating system Microsoft Windows XP Embedded, Microsoft Internet Explorer and the
P View Web-client are preinstalled on the ControlCare Panel PC SPC150.
The P View server and Web-clients communicate via Ethernet using Internet Explorer. Depending
upon user specifications, the Web-client is started and the connection to the server established
automatically when the Panel PC is switched on. Alternatively, the Web-client connection is made,
as in Internet, by entering the P View server URL in Internet Explorer.
6.2 Operation
Operation and navigation is done with the touchscreen at the front of the Panel PC. Functions are
called and views changed by touching the corresponding buttons and menu bars on the graphical
user interface.
The function and operation of the HMI pages is described in an application-specific operating
manual that is supplied with the associated P View SCADA application.
"Caution
• Do not use metallic or pointed objects to operate the touchscreen - they will damage it.

ControlCare Panel PC SPC150 7 Maintenance
Endress+Hauser 17
7 Maintenance
Ventilator, display backlight and battery should be checked for correct function at regular intervals.
7.1 General precautions
"Caution
• The housing need only be opened to exchange the back-up battery. If the display backlight needs
to be replaced, send the unit back to Endress+Hauser.
• Electronic components are extremely sensitive to electrostatic discharge. For this reason they
must be handled with great care. Instructions on handling can be found in the ESD guidelines.
Should you need to remove the housing:
• Switch off the ControlCare Panel PC SPC150 and disconnect it from the power supply.
• Before working on the components, the electrostatic change on your body must be brought to
the same level as that of the ControlCare Panel PC SPC150 and its components. To this end,
touch the metal housing.
• Do the same for any tools you are using.
• Use a ground strap if you are working with electronic components.
• Do not unpack components and modules until they are really needed.
• Grip components and modules at their edges. Never touch connection pins and condictors.
• Never operate the ControlCare Panel PC SPC150 with open housing.
7.2 Housing
7.2.1 Construction
Fig. 7-1 shows how the housing is constructed:
Abb. 7-1: Housing contruction
Base The base is designed
• for the installation of the electronics:
basic board with associated electronics and possible extensions
• to fasten the other system components: display, front panel, hood.
Hood The hood is mounted and fastened from the rear, optionally with ventilator kit.
Front panel
Base
Ventilator kit (option)
Hood

7 Maintenance ControlCare Panel PC SPC150
18 Endress+Hauser
7.2.2 Opening the housing
"Caution
Before opening the housing:
• Shut down the Panel PC.
• Switch off the Panel PC.
• Disconnect it from the power supply.
• Remove all connection cables..
Fig. 7-2: Opening the housing
After the hood has been removed, the basic board with its various (covered) elements are visible.
Loosen the two screws on the back wall of the hood. Phillips screws M3x6
Slide the hood to the left (as seen from above) in its guide slots...
until the fixing lugs are free.
Pull off the hood.
Table of contents
Other Endress+Hauser Touch Panel manuals