Energy Technology OCEM AUGIER DIAM4200 Series Maintenance and service guide

46630
DIAM4200 2,5-20kVA
Sinusoidal Single-phase
Constant Current Regulator
Compliance with standards:
ICAO Aerodrom design manual, part 5
IEC 61822 et 61821
FAA (AC 150/5345-10F Spec.L828/L829)
AENA (PPT2 ed4(2004)
60 21642 Diam4200 (IM)
Installation & maintenance
Document available at http://www.augier.com/doc/6021642.pdf
Energy Technology srl
Operating office :
Via della Solidarieta 2/1
40056 Valsamoggia –Loc. Crespellano (BO) –Italy
Ph : + 39 051 6656 611 Fax : +39 051 6656 677
VAT Nr : IT 031 4821 1208
a division of Energy Technology srl

6021642 DIAM4200 2.5 to 20KVA rev 1-9.docx
I-2
RECORD OF CHANGES
Rev.
Pages
Description
From S/N
By
App.
Date
1.0
First issue
PS
RG-ED
01/01/2015
1.1
70
Nomenclature corrections
RG
RG
19/05/2016
1.2
Corrections
RG
RG
07/07/2016
1.3
64
Fuse modification
ED
RG
04/11/2016
1.4
2
Warranty modification
RG
RG
15/05/2017
1.5
Add 20KVA power
ED
RG
17/11/2017
1.6
Diagrams and schematics update
RG
RG
20/02/2018
1.7
10, and 68
USB note, and High T° warning
RG
RG
08/03/2018
1.8
New logo
RG
RG
23/05/2018
1.9
Add 2,5KVA nominal power CCR
Adding multi terminal inductance
Remove the remote control and cut out
pages
Notice 6021732 : Remote control notice
Notice 6021752 : Cut out notice
ED
RG
31/01/2019

DIAM4200 ©2018 AUGIER SA.
6021642 DIAM4200 2.5 to 20KVA rev 1-9.docx
I-3
WARRANTIES
Guarantee
AUGIER’s goods has been manufactured and will perform in accordance with applicable specifications, and
any defect in design, materials or workmanship which may occur during proper and normal use during a period
of 1 year from date of installation or 2 years from date of shipment will be corrected by repair or replacement by
the manufacturers f.o.b factory.
The guarantee covers repair, modification or replacement of parts or products recognised to be defective, in
the shortest possible time, at AUGIER’s cost, provided always that the goods have been properly handled and
stored prior installation, properly installed and properly operated after installation.
Unless otherwise specifically laid down in contract, the guarantee does not cover:
Costs of consignment to factory and re-consignment of defective goods to Buyer
Travelling & sojourn expenses of AUGIER’s personnel if goods have to be repaired on site; assembly
and dismantling of any goods other than those recognised to be defective; expenses incurred for
waiting times by AUGIER’s personnel on site for reasons independent of their will;
Unjustified travel expenses.
Guarantee shall not apply in the following cases:
Defects in materials supplied by Buyer or from any designs imposed by them;
Repairs or replacements due to normal wear and tear, or damages or accidents.
Repairs or replacements due to damages or accidents resulting from negligence or lack of due care,
inadequate supervision or maintenance, or erroneous use of the equipment or software;
Any other causes for which AUGIER shall not be held responsible, e.g. resulting from an case of Force
Majeure.
When Buyer has replaced AUGIER’s parts with other parts.
Buyer must inform AUGIER in writing and without delay of any defects in goods, giving all necessary
information and detailed description of how equipment has been utilised, together with purchase date. Buyer
undertakes not to have repairs carried out by third parties; any repairs carried out without AUGIER’s express
prior agreement shall invalidate the guarantee.
It is expressly agreed between the two parties that Buyer cannot avail himself of the beneficial dispositions
contained in the guarantee without having first satisfied payment conditions laid down in contract
Disclaimers
This manual could contain technical or typographical errors. AUGIER reserves the right to make changes and
revise this manual from time to time without obligation to notify any person or organisation of such changes or
revision.
Values and measurements given in this manual are average values and are not binding. AUGIER disclaims any
liability for damages suffered as a result of reliance on the information given in this manual, or the use of
equipment or processes which this manual refers.
No guarantee is made that the use of the products, equipment, processes or information to which this manual
refers will not infringe any third party’s patent or rights. Information given does not release the buyer from
making their own tests.

6021642 DIAM4200 2.5 to 20KVA rev 1-9.docx
I-4
SAFETY
Safety precautions
This equipment is normally used or connected to circuits that may employ dangerous and lethal voltages.
Extreme caution should be exercised by operating or maintenance people when working on or with this
equipment.
See IEC 61820 & 61821 standard (CCR type IEC), or FAA AC150/5340-26 advisory circular (CCR type FAA),
concerning safety rules and precautions. While practical safety precautions have been incorporated in this
equipment, the following rules must be strictly observed :
KEEP AWAY FROM LIVE CIRCUITS :
Operating and maintenance people must at all time observe all safety regulations. Do not change
components nor perform maintenance inside equipment with power ON or the lighting loop energised.
RESUSCITATION :
Operating and maintenance personnel should familiarise and keep themselves trained with resuscitation
techniques found in widely published manuals about first aid instructions.
ELECTROSTATIC DISCHARGE (ESD) :
Electronic sub-assemblies and boards should be touched only for unavoidable operation (replacement,
for example). Before to operate, maintenance people must first of all eliminate unwanted electronic
charges, discharging his own body while touching a conductive earthed object or part. Electronic boards
and components as power semiconductors must be stored and carried an conductive packing.
DESTRUCTION :
In case of dismantling, scrapping or placing out of service, the user must follow all the required
precautions for component, materials or equipment elimination, according the local rules.
EEC DIRECTIVES
This equipment complies with the requirements of EC directives :
89/336/EEC, 92/31/EEC and 93/68/EEC with regard of Electromagnetic
Compatibility
73/23/EEC with regard of Low Voltage Equipment

DIAM4200 ©2018 AUGIER SA.
6021642 DIAM4200 2.5 to 20KVA rev 1-9.docx
I-5
TABLE OF CONTENTS
RECORD OF CHANGE ……………………………………………………………………………………………… I-2
WARRANTIES …………………………………………………………………………………………………………… I-3
SAFETY ……………………………………………………………………………………………………………….….. I-4
TABLE OF CONTENTS ……………………………………………………………………………………………… I-5
IDESCRIPTION________________________________________________________I-9
I.1 OVERVIEW _______________________________________________________________________ I-9
I.2 MECHANICAL DESCRIPTION_______________________________________________________ I-10
I.2.1 DESCRIPTION________________________________________________________________ I-10
I.2.2 GENERAL MECHANICAL FEATURES _____________________________________________ I-11
I.2.3 STORAGE CONDITIONS _______________________________________________________ I-12
I.2.4 DIMENSIONS_________________________________________________________________ I-12
I.3 ELECTRICAL DESCRIPTION _______________________________________________________ I-13
I.3.1 BLOCK DIAGRAMS____________________________________________________________ I-13
I.3.1.1 Overview: __________________________________________________________________ I-13
I.3.1.2 Electronics : ________________________________________________________________ I-13
I.3.2 GENERAL CIRCUIT DIAGRAMS _________________________________________________ I-13
I.3.3 GENERAL ELECTRICAL FEATURES______________________________________________ I-14
I.4 INSTRUCTIONS FOR USE__________________________________________________________ I-15
I.4.1 USER INTERFACE ____________________________________________________________ I-15
I.4.2 CONTROL ___________________________________________________________________ I-17
I.4.3 LOCAL INFORMATION FEEDBACK_______________________________________________ I-17
I.4.4 REMOTE INFORMATION FEEDBACK _____________________________________________ I-19
I.5 OPERATION _____________________________________________________________________ I-20
I.5.1 CONFIGURATION _____________________________________________________________ I-21
I.5.2 SETTING ____________________________________________________________________ I-21
I.5.2.1 Current range:_______________________________________________________________ I-21
I.5.3 PROTECTIONS _______________________________________________________________ I-21
I.5.3.1 LV power monitoring: _________________________________________________________ I-21
I.5.3.2 “Open circuit”: _______________________________________________________________ I-21
I.5.3.3 “Capacitive current detection”: __________________________________________________ I-21
I.5.3.4 “Overcurrent”: _______________________________________________________________ I-22
I.5.3.5 Cancelling “Open circuit” and “Overcurrent” faults: __________________________________ I-22
I.5.4 AUTOMATIC OPERATION:______________________________________________________ I-22
I.7 ACCESSORIES___________________________________________________________________ I-23
I.7.1 “ALIZE4100” SOFTWARE _______________________________________________________ I-23
I.8 OPTIONS________________________________________________________________________ I-23
I.8.1 CUT OUT (OPTION) ___________________________________________________________ I-23

6021642 DIAM4200 2.5 to 20KVA rev 1-9.docx
I-6
I.8.2 EARTH FAULT DETECTOR (EFD)_________________________________________________I-23
I.8.3 OUTPUT LIGHTNING ARRESTORS _______________________________________________I-24
I.8.4 INPUT LIGHTNING ARRESTORS _________________________________________________I-24
I.8.5 CASTERS ____________________________________________________________________ I-24
I.8.6 BURNT LAMPS DETECTION: ____________________________________________________I-24
I.8.7 TIME METERS:________________________________________________________________I-25
I.8.8 BUZZER _____________________________________________________________________I-25
I.8.9 WIG WAG ____________________________________________________________________ I-26
I.8.10 OTHER OPTIONS______________________________________________________________I-27
II INSTALLATION _____________________________________________________ II-28
II.1 PREPARATION __________________________________________________________________ II-28
II.1.1 EQUIPMENT RECEPTION ______________________________________________________ II-28
II.1.1.1 Equipment delivered: _______________________________________________________ II-28
II.1.1.2 Checking the equipment: ____________________________________________________ II-28
II.1.2 DEVICE LOCATION ___________________________________________________________ II-28
II.1.3 CHECKING THE INSTALLATION_________________________________________________ II-29
II.1.3.1 Single phase power supply: __________________________________________________ II-29
II.1.3.2 LV Protection:_____________________________________________________________ II-29
II.1.3.3 Lighting loop: _____________________________________________________________ II-29
II.1.3.4 Management by remote control:_______________________________________________ II-29
II.2 CONNECTIONS __________________________________________________________________ II-30
II.2.1 POWER AND EARTH __________________________________________________________ II-30
II.2.1.1 LV supply:________________________________________________________________ II-30
II.2.1.2 Earthing _________________________________________________________________ II-30
II.2.1.3 Lighting loop: _____________________________________________________________ II-31
II.2.2 REMOTE CONTROL CONNECTIONS_____________________________________________ II-32
II.2.3 CIRCUIT SELECTOR:__________________________________________________________ II-33
II.3 ADJUSTING THE CCR ____________________________________________________________ II-34
II.3.1 MULTI TERMINAL INDUCTANCE ________________________________________________ II-34
II.3.2 PARAMETER MODIFICATION___________________________________________________ II-35
II.3.2.1 Preferred configuration values: _______________________________________________ II-35
II.3.2.2 Brightness values: _________________________________________________________ II-35
II.3.2.3 Value of “Open Circuit” protection level:_________________________________________ II-36
II.3.2.4 Value of “Overcurrent” protection levels: ________________________________________ II-36
II.4 REMOTE CONTROL ______________________________________________________________ II-37
III COMMISSIONING__________________________________________________III-38
III.1 PROCEDURE____________________________________________________________________III-38
III.2 TESTS__________________________________________________________________________ III-39
III.2.1 SHORT-CIRCUIT TESTS _______________________________________________________III-39
III.2.2 OVERLOAD TESTS ___________________________________________________________III-39

DIAM4200 ©2018 AUGIER SA.
6021642 DIAM4200 2.5 to 20KVA rev 1-9.docx
I-7
III.2.3 OPEN-CIRCUIT TEST _________________________________________________________ III-39
IV MAINTENANCE __________________________________________________ IV-40
IV.1 FORMALISATION________________________________________________________________ IV-40
IV.2 PROCEDURE FOR INTERVENTION _________________________________________________ IV-40
IV.3 PREVENTIVE ___________________________________________________________________ IV-41
IV.3.1 FIRST MONTHS______________________________________________________________ IV-41
IV.3.2 ANNUAL PROCEDURE________________________________________________________ IV-41
IV.3.3 EVERY THREE YEARS________________________________________________________ IV-41
IV.4 CORRECTIVE ___________________________________________________________________ IV-42
IV.4.1 FUSES ON MOTHER BOARD___________________________________________________ IV-42
IV.4.2 FUSES ON INTERFACE BOARD ________________________________________________ IV-42
IV.4.3 FAULT DIAGNOSIS ___________________________________________________________ IV-43
IV.4.3.1 LV power fault: ___________________________________________________________ IV-43
IV.4.3.2 “Open Circuit” fault: ________________________________________________________ IV-43
IV.4.3.3 “Overcurrent” fault: ________________________________________________________ IV-43
IV.4.3.4 Module power fuse fault:____________________________________________________ IV-44
IV.4.4 OTHER FAULTS _____________________________________________________________ IV-45
IV.5 SPARE PARTS LIST _____________________________________________________________ IV-47
VAPPENDIX A: DIAGRAMS ____________________________________________ V-49

6021642 DIAM4200 2.5 to 20KVA rev 1-9.docx
I-8
ABBREVIATIONS
Abbreviation
Definition
A
Ampere
AC
Alternating Current
B
Brightness
CCR
Constant Current Regulator
DC
Direct Current
EFD
Earth Fault Detector
HV
High Voltage
IT
Injection Transformer
LFD
Lamp Fault Detector
LV
Low Voltage
OO
Out of order
V
Volt
VA
Volt-Ampere

DIAM4200 ©2018 AUGIER SA.
6021642 DIAM4200 2.5 to 20KVA rev 1-9.docx
I-9
I DESCRIPTION
I.1 OVERVIEW
DIAM4200 series CCRs are optimized static devices, controlled IGBT bridges, designed to maintain a
constant, pre-displayed and adjustable output current independently of load or power supply fluctuations. These
devices are specifically designed for visual aids supply, and particularly LED lights. They meet all international
standards. Control electronics of the DIAM4200 is characterized by an innovating architecture built around an
electronic board using a powerful DSP processor, associated with an internal CAN network connecting the
various parts.
An USB front socket allows the connection of a portable computer for parameter setting, this setting being
possible without live voltage. However, this link is not a hardened industrial link, such as the JBus, Ethernet or
Interbus communication ports of the CCR: all precautions must be taken not to introduce electrostatic or
electrical disturbances, which could disrupt the operation of the CCR, (using ESD protections).
The remote control interface of the CCR supports all the series networks, with or without redundancy, as
well as universal multiwire interfaces. DIAM4200 series CCRs are low costs fully static devices controlled by
high performance IGBT switches. They are designed to maintain a constant, pre-displayed and adjustable
output current independently of the load and power supply fluctuations.
These devices are specifically designed for airfield lighting on runways, taxiways, aprons. They meet both
national and international standards.
In order to do this, they use an adapted triggering and regulation mechanism that is not affected by external
interference and does not emit measurable interference in the Aviation Band between 100 and 400 MHz.
The output current remains constant with an accuracy of 100mA for mains voltage fluctuations of –5/+10%
(+/-10% for IEC type). At the rated load and the rated or higher voltage, accuracy of regulation is maintained for
all load between 0 and 100%, and for up to 30% of transformers with open secondary.
Here are some of its advantages:
Sinusoidal wave shape:
Thanks to its original power architecture, the CCR does not introduce any distortion or degradation of the
power-factor, which remains that of the load. The harmonic content rejected on the mains network is thus
particularly low, for all the range of output current and for any load. In particular, no tapping or adaptation at
load is necessary. The digital processing capability of the DSP processor allows to adapt its regulation to
any type of load (such as for example : signs). Like all the DIAM4XXX series regulators, an automatic
calibration avoids any analogical adjustments, during maintenance. In the same way, indications of alarm,
state of the CCR and all useful parameters are clearly displayed, through a simple and friendly HMI*.
Maintenance optimization:
Its internal CAN* architecture has been designed to minimize the number and the variety of the spare parts,
and to allow the best flexibility of possible modification of options. Software tools are proposed in order to
carry out fast parameter settings or diagnoses, without removing any parts.
Standards:
ICAO: Airport design manual, part 5
CENELEC: prENV 50231
FAA: AC150/5345-10 L828 & L829
AENA: PPT02-05/13 (2013)
IEC: 61822 (CCRs), 61821 (Maintenance)

6021642 DIAM4200 2.5 to 20KVA rev 1-9.docx
I-10
I.2 MECHANICAL
DESCRIPTION
I.2.1 DESCRIPTION
Each CCR is housed in a cabinet fitted with lifting rings.
The frame has three distinct parts: a low voltage converter stage, a low voltage compartment and a high voltage
compartment.
The Low voltage converter stage of the
CCR consist of one to three power modules,
situated in the upper section of the regulator.
The Low voltage unit contains all the
components connected to the power supply
with, for example, the main switch, the LV
protections, the electronics control
motherboard, the LV fuses and connection
terminals. It is located in the lower front part
of the CCR.
The High voltage unit, situated at the back
of the CCR, contains all the components
connected to the output loop such as the
power transformer, the lightning arrestors,
the CI-MALT (optional) and the HV part of the
insulation fault detection unit. The load
regulating plate and the load loop
connections are accessible from the front of
the device.
All these components are easily accessible from the front, the top or the back of the cabinet.

DIAM4200 ©2018 AUGIER SA.
6021642 DIAM4200 2.5 to 20KVA rev 1-9.docx
I-11
I.2.2 GENERAL MECHANICAL FEATURES
Regulators are contained in the same cabinet for all powers and input voltage. Taller cabinets could be
available when inside additional equipment is requested by customer, as Circuit selector. Both cabinets are
provided with hoisting eye rings, with or without casters, and can be located cuddled up to each other.
Standard cabinet : 2.5 to 15KVA: 500mm Wide x 750mm Deep x 1380mm High
20KVA: 500mm Wide x 750mm Deep x 1575mm High
Protection Index for the Casing: IP 21. (Contact us for other Protection Indices)
Distances inter-axes (if casters option) : 413 x 640 mm
Usage: Ambient temperature between –20°C to +55°C (IEC type), with maximum relative humidity of
95%. Forced air cooling.

6021642 DIAM4200 2.5 to 20KVA rev 1-9.docx
I-12
I.2.3 STORAGE CONDITIONS
The components are designed to be stored in a dry, airy location, sheltered from rain, water discharges
and chemical agents. We must be consulted if the components are to be stored outside, or in an ambient
temperature out of the range -40°C/+55°C.
I.2.4 DIMENSIONS
A (mm)
B (mm)
C (mm)
2.5 to 15 kVA
1375
500
750
20KVA
1575
500
750
Load
5kVA
7.5kVA
10kVA
15kVA
20kVA
Weight
127 kg
185 kg
195 kg
215 kg
315 kg
B
A
C

DIAM4200 ©2018 AUGIER SA.
6021642 DIAM4200 2.5 to 20KVA rev 1-9.docx
I-13
I.3 ELECTRICAL
DESCRIPTION
I.3.1 BLOCK DIAGRAMS
See paragraph I.5 for the device operating description
I.3.1.1Overview:
I.3.1.2Electronics :
I.3.2 GENERAL CIRCUIT DIAGRAMS
See APPENDIX A: DIAGRAMS
Input
circuits
Main
Contactor
Power
modules
LV/HV
Transformer
Output
circuits
Control &
Monitoring
Measuring
Board
Interfaces

6021642 DIAM4200 2.5 to 20KVA rev 1-9.docx
I-14
I.3.3 GENERAL ELECTRICAL FEATURES
Power supply voltage:
Single phase; 230Vac, 400Vac +10/-10%, 45 to 66 Hz
Maximum rated current: 6.6 A (other values available).
Number of Brightness Levels: maximum 8, adjustable.
Heating Brightness (“Black current”):
The CCR can produce “heating” level brightness at low current (1.8A preferred value), which is used to
remove condensation from the interior of the lamp lenses without lighting up their bulb. The symbol for
local setting is ‘B0’.
Remote Control: By voltage from 20V to 60V DC positive or negative, or dry contact, or 120Vac, serial
network, TCP/IP network (MODBUS TCP).
Remote indication:
Relays, 120VAC , 2A max, 10µA min., and/or serial network
Output power: 2.5, 5, 7.5, 10, 15, 20kVA
Power factor:
> 97% at nominal voltage and rated resistive load
Efficiency : > 80% at nominal voltage and rated resistive load.
Output Current Regulation:
Better than 100mA under the following conditions: Power supply voltage: 10% - Frequency: 45 to 66
Hz - Load: from 0 to 100%
Load adaptation:
The DIAM4200 CCR does not require load adaptation: the output voltage is purely sinusoidal at every
load and current step.
Protection:
The electronic circuitry is protected against fluctuations by the use of a Hall effect sensor for measuring
current. Electronic board manages all overcurrent, open circuit or mains under/over voltage.
LV Protection:
A set of high-power fuses (or optional circuit breaker), a set of fuses for the power supply to the
auxiliaries, and “glass” fuses on the circuit boards provide LV protection.
Lightning arrestors :
These regulators can be optionally provided with input and output lightning arrestors.

DIAM4200 ©2018 AUGIER SA.
6021642 DIAM4200 2.5 to 20KVA rev 1-9.docx
I-15
I.4 INSTRUCTIONS FOR USE
I.4.1 USER INTERFACE
Operating mode:
Stop mode :
Preferred information displayed: It can be changed by a long press on the “STOP” key, meanwhile the CCR is in
Stop mode. The choice can be :
Output current Io –Brightness state Bx (as seen in examples below and above)
Output current Io –Output power Po
Output current Io –Output voltage Uo
Local mode :
Access is given to B+ and B-, in order to increase / decrease the brightness.
Remote control mode :
“Auto” is highlighted, in order to indicate the current state.
Brightness selection in local mode:
:Decrease brightness in local mode Increase brightness in local mode
Io:0.00A STOP
stop local auto menu
Io:6.60A <B5>
stop B- B+ menu
Io:5.20A <B4>
stop local auto menu
Io:6.60A <B5>
stop B- B+ menu

6021642 DIAM4200 2.5 to 20KVA rev 1-9.docx
I-16
Menus:
Access to menu
To navigate in the menus
Alarms and Warnings:
Alarm (the CCR failed to supply the load); for example, the CCR is stopped by a loop open circuit :
Cancel fault(s)
Warning (the CCR doesn’t stop; warning is only indicative); for example the earth insulation fault level 1 is
detected :
USB link:
An USB socket (type B) is located in front of the CCR, in order to connect a lap-top computer
Rx: indicator Data reception on USB connection
Tx: indicator Data transmission on USB connection
Rx Tx
Alphanumeric display:
VFD Blue display (16 x 140 pts) :
- upper line: information datas),
- lower line :key definition.
Screen saver : The brightness decreases automatically or turn off after one hour if the keyboard is not used.
Turns on again instantly when a key is pressed. (Function user-definable)
Io:0.00A STOP
stop local auto menu
Monitoring
esc OK
ALARM: I<<Open Cir.
reset
Warning: :EFD Level1
stop local auto menu
Io:5.20A <B4>
stop local auto menu

DIAM4200 ©2018 AUGIER SA.
6021642 DIAM4200 2.5 to 20KVA rev 1-9.docx
I-17
I.4.2 CONTROL
The device is controlled by mean of a 4 buttons keypad which allows to change the operating mode: “Stop” –
Manual or “Local” mode –Remote or “Auto” control mode.
Stop mode:
In that mode, “Stop” is highlighted. The CCR stops, whatever the current brightness orders (remote control or
local selection).
Menus can then be accessed.
Local mode:
In that mode appears brightness controls : The brightness is chosen by pressing buttons B- and B+ (from B0 to
B7 maximum, according to the number of brightness levels configured).
Remote control mode:
In that mode, “Auto” is highlighted. Operation of the CCR is governed by remote control inputs on the CCR’s
motherboard. If remote control commands overlap, priority is given to the first choice of brightness. The remote
control is either of the multiwire type (20 to 60 DC positive or negative, or 120Vac), or the dry-contact type with
internal power supply, and/or given by the mean of a serial network.
See paragraph II.2.2 for configuring the remote control type.
See paragraph I.5.2 for adjusting brightness values and protection levels.
I.4.3 LOCAL INFORMATION FEEDBACK
Alphanumeric display:
The display shows the RMS current flowing in the loop and the selected brightness (preferably).
In the “Monitoring” menu, the following information are shown:
Uo: RMS output voltage in Vrms
Po: RMS output power in kVA
Ui: Mains power supply voltage in Vrms
Ii: Mains power current in Arms
If option “EFD” exists: Insulation resistance of the loop with respect to earth in KOhms
Load plate tap value from 0 to 100% (0 to 8/8 by increments of 1/8)
If option “LFD” exists: Number of burnt lamps, and VA drop if FAA type
The operating time (powered on and for each brightness) in Hours
Io:0.00A STOP
stop local auto menu
Io:6.60A <B5>
stop B- B+ menu
Io:0.00A <-->
stop local auto menu

6021642 DIAM4200 2.5 to 20KVA rev 1-9.docx
I-18
Warning:
WARNING is an indicative message, which does not change regulation and supply function in connection with
the load. (Except for mains warning)
If any warning have been detected, the following message(s) can be shown on the display:
If option “EFD” exists:
"No EFD" (interface EFD board not present or faulty)
“No HV (500V) EFD” (no injection voltage : measurement of earth leakage cannot be done)
“R Level EFD1” (A leakage has been detected, with a resistance value lower than the level 1).
“R Level EFD2” (A leakage has been detected, with a resistance value lower than the level 2).
If option “Burnt lamps” exists:
“Level 1 Burnt lamps” (The current number of burnt lamps is greater than level 1)
“Level 2 Burnt lamps” (The current number of burnt lamps is greater than level 2)
“Power drop” (if FAA selected : the load was cut more than 10%, in VA)
Mains power supply outside limits (Input voltage lower or greater than +/-10%)
Regulation outside limits (as “error regulation” programmed values)
"BAD Interface" message (control and monitoring board not present or faulty)
Fault:
ALARM represents a major fault of the CCR or due to an external event, which have stopped the CCR (in order
to protect itself or the lighting loop).
In case of fault or damage, the display shows that the CCR stopped and one or more faults have been detected.
The following message(s) are shown on the display:
Overcurrent Level 1 (after a trial to restart, the CCR cannot contain the output current which had reach
the 1st level as programmed)
Overcurrent Level 2 (ditto, for 2nd level)
Overcurrent Level 3 (ditto, for 3rd level)
Peak Overcurrent (ditto, for a 4th level, not configurable)
Open circuit (the CCR detected an output current lower and during a greater time than the programmed
parameters)
In order to re-start (after having fixed the fault), cancel the ALARM pressing the RESET key.

DIAM4200 ©2018 AUGIER SA.
6021642 DIAM4200 2.5 to 20KVA rev 1-9.docx
I-19
I.4.4 REMOTE INFORMATION FEEDBACK
Dry contacts:
Information returned:
Selected brightness
Operating mode: Local/Remote control
“Open Circuit” fault
“Overcurrent” fault
If option “EFD” appears: EFD Level 1 and 2 warnings
If option “Burnt lamps” appears: Burnt lamps level 1 and 2 warnings
If option “Burnt lamps” and FAA type: Power drop
See the “Remote control terminal block” connection table in the appendix.
MODBUS TCP link or Insulated RS485 link:
A JBUS table is accessible via an ethernet interface, an insulated JBUS RS422/485 link or through the USB
socket (type B) in front of the CCR.
The values in the table are used to control and monitor the device remotely.
See the JBUS table in the Erreur ! Source du renvoi introuvable., for more details.

6021642 DIAM4200 2.5 to 20KVA rev 1-9.docx
I-20
I.5 OPERATION
The “Parameter Access” function must be activated before changing parameters, in order to
avoid unwanted changes.
Pressing the menu touch, the display shows:
then scroll through the top-level menu items using the and keys. When the “Options” item is shown
like:
press OK to go into the “Options” menu, then scroll through the items until the “Param. access: NO” item is
displayed:
Press modif in order to modify the parameter. When the "NO" displayed blinks, it is possible to change the
parameter : press <or >to in order to change “NO” to “YES” :
Save the modification by pressing OK .
Press esc twice to go back to the initial state.
ALL PARAMETERS ARE MODIFIED USING THE SAME PROCEDURE.
Monitoring
esc OK
Options
esc OK
Param. access: No
esc modif
Param. access: Yes
esc OK
Table of contents