Pressurized ow centers and Grundfos UP series pumps
need a minimum of 3psi on the sucon side of the pump to
operate. Maximum operang pressure is 100 psi.
On ow center inial start up, the
pumps must be bled of air. Start the system and remove the
bleed screw from the back side of the pump(s). This allows
any trapped air to bleed out. It also oods the pump sha,
and keeps the pump(s) cool. Failure to do this could result in
premature pump failure.