ENERVEX RSV Installation instructions

3000775 12.12 Installation & Operating Manual
USA
CAN
RSV Chimney Fan
ENERVEX Inc.
1685 Bluegrass Lakes Pkwy.
Alpharetta, GA 30004
P: 770.587.3238
F: 770.587.4731
T: 800.255.2923
www.enervex.com
Job Name:
Installer:
Installation Date:
Product Information
Mechanical Installation
Electrical Installation
Start Up and Conguration
Maintenance and Troubleshooting
........................ Chapter 1 + 2
......................... Chapter 3
............................. Chapter 4
.................. Chapter 5
...... Chapter 6
READ AND SAVE THESE INSTRUCTIONS!

2
3000775 12.12
5. This unit must be grounded.
How to use this manual
This installation manual does not contain any system design
documentation. System design documentation is available from any
authorized EXHAUSTO representative.
Accessories, fans and variable frequency drives are not covered by
this manual. Please refer to these component’s individual manuals.
1. Product Information
1.1 Function .....................................................................................................3
1.2 Components...............................................................................................3
1.3 Shipping .....................................................................................................4
1.4 Warranty.....................................................................................................4
2. Specications
2.1 Dimensions & Capacities ...........................................................................4
3. Mechanical Installation
3.1 Transport Safety Device............................................................................. 5
3.2 Single Fan on Steel Chimney..................................................................... 5
3.3 Singel Fan on Roof Curb............................................................................ 5
3.4 Single Fan on Brick Chimney.....................................................................6
3.5 Side-Wall Mounting of Chimney Fan..........................................................6
3.6 Multiple Fan Installations............................................................................ 7
3.7 Installation for High Temperatures .............................................................7
3.8 Installation of Proven Draft Switch (PDS) ..................................................7
4. Electrical Installation
4.1 Electrical Requirements .............................................................................8
4.3 Wiring Diagram for RSV 400-450............................................................... 9
5. Startup & Conguration
5.1 System Testing.........................................................................................10
5.2 Adjusting Fan Speed ................................................................................ 10
5.3 Testing Safety System ............................................................................. 10
6. Maintenance & Troubleshooting
6.1 Maintenance Intervals .............................................................................. 11
6.2 Cleaning ................................................................................................... 11
TO REDUCE THE RISK OF FIRE, ELECTRICAL SHOCK OR INJURY TO PERSONS,
OBSERVE THE FOLLOWING:
Caution: Indicates an imminent hazardous situation
which, if not avoided, may result in personal injury or
property damage.
Symbol Legend:
The following terms are used throughout this manual to bring attention
to the presence of potential hazards or to important information
concerning the product.
Danger: Indicates an imminent hazardous situation
which, if not avoided, will result in death, serious injury or
substantial property damage.
1. Use this unit in the manner intended by the manufacturer. If
you have questions, contact the manufacturer at the address or
telephone number listed on the front of the manual.
2. Before servicing or cleaning the unit, switch off at service panel
and lock service panel to prevent power from being switched on
accidentally.
3. Installationworkandelectricalwiringmustbedonebyaqualied
person(s) in accordance with applicable codes and standards.
4. Follow the appliance manufacturer’s guidelines and safety
standards such as those published by the National Fire Protection
Association (NFPA), and the American Society for Heating,
Refrigeration and Air Conditioning Engineers (ASHRAE), and the
local code authorities.

3
3000775 12.12
Fig. 1
The RSV 200-450 Chimney Fan consists of the following
components:
a. Top section f. Locking hinge
b. Bottom section g. Bird screen
c. Motor h. Carrying handle
d. Centrifugal impeller i. Wiring conduit
e. Inlet for impeller
Max. 575°F (300°C)
1. Product Information
1.1 Function
The RSV chimney fan is intended for use as part of a chimney, stack or venting system. The
fan is designed to withstand the high temperatures associated with combustion, and can be used with natural gas,
LP-gasandoil-redheatingappliancesystemswhereuegasesdonotexceed575oF (300oC) for intermittent
operation and 482oF(250oC) for continuous operation. It is approved for use with category I, II, III and IV appliances.
The RSV fan may be installed on a traditional vertical chimney system, or as part of a side-wall vented system.
Always install the fan at the chimney termination point.
The use of a chimney fan is not restricted to any type of chimney, because the fan creates a
negative pressure (below atmospheric) in the chimney system. However, always follow the heating appliance
manufacturer’sinstructionsregardingspecicventingrequirements.
The fan is designed to prevent draft problems by creating mechanical draft in chimney and stack systems. It can
alsobeusedtoincreasethecapacityandefciencyofsuchasystem.
The fan housing is made of heavy cast aluminum and can be opened for easy cleaning. The RSV 200-450 have a
backward inclined impeller. It is made of cast aluminum and has permanently attached balancing weights.
The motor is a direct drive, variable speed, class H insulated, high temperature motor. It has permanently
lubricated and sealed ball bearings and is maintenance free.
Installations must conform to the requirements of the authority having jurisdiction. Where required by the authority
having jurisdiction, the installation must also conform to the NFPA 31, 54 or 211.
All electrical wiring must be in accordance with the requirements of authority having jurisdiction or, in absence of
such requirements, with the National Electrical Code, NFPA 70.
RSV is tested and listed to UL Standard 378 for Draft Equipment and CAN3-B255-M81 for
Mechanical Flue-Gas Exhausters (ETL Report 514733).
The RSV Fan is a listed component in the CASV, Chimney Automation System. The fan is approved for
use in dryer venting systems as well.
1.2 Components
Use
Code
Compliance
Listing
Description

4
3000775 12.12
1.3 Shipping
The fan is shipped in a corrugated cardboard box. A transport securing device may be attached to the bottom
of the fan to hold the motor and impeller in place. Do not remove the device until the fan is at the installation point.
Do not remove the transport securing device until the fan is being installed on the duct or the roof
curb. The motor shaft could be damaged.
NOTE: All single phase fans are shipped with a capacitor and junction box connected via conduit.
The capacitor is located INSIDE the junction box. Please do not discard.
1.4 Warranty
Complete warranty conditions are available from ENERVEX.
2. Specications
2.1 Dimensions & Capacities
Model RSV 200 RSV 250 RSV 315 RSV 400 RSV 450
Discharge Vertical
Fan Type Centrifugal Impeller
Max. Discharge Velocity FPM 1,729 2,222 2,771 2,752 4,134
Actual Discharge Velocity FPM 2.9 x CFM 1.9 x CFM 1.2 x CFM 5.9 x CFM 1.03 x CFM
Voltage VAC 1 x 120 3 x 200-240 / 3 x 400-480
RPM 1600 1720
Amps A 1.4 2.9 5.8 3.5 / 1.8 6.5 / 3.6
Motor Output hp 0.1 0.2 0.5 1.0 2.0
kW 0.10 0.16 0.35 0.75 1.5
Weight lbs 47 60 88 127 155
kg 18 26 35 58 70
Dimensions Ain 11.03 13.20 14.97 16.94 23.23
mm 280 335 380 430 590
B x B in 15.37 19.11 22.85 25.61 25.61
mm 390 485 580 650 650
C x C in 12.22 15.17 18.32 20.69 20.69
mm 310 385 465 525 525
D Ø in 7.88 9.85 12.41 15.76 15.76
mm 200 250 315 400 400
Ein 3.15 3.94 4.53 5.12 8.54
mm 80 100 115 130 217
Motor starter required No No No Yes 1) Yes 1)
Variable speed motor Yes Yes Yes Yes Yes
Temperature Rating Interm 575°F/300°C
Cont. 482°F/250°C
1) Not required if using a VFD

5
3000775 12.12
3. Mechanical Installation
The code requirements for a mechanical draft system are different than those for a gravity venting system used with
gasoroil-redapplications.Generally,themechanicaldraftsystemmustbeinstalledaminimumof3feetaway
from any forced air inlet located within 10 feet and a minimum of 4 feet away from any door or window. For complete
information, consult ENERVEX or your local building codes.
3.1 Transport Safety Device
Before mounting the fan make sure the transport safety
brackets have been removed (RSV315, 400 and 450 only).
3.2 Single Fan on Steel Chimney
Insert the steel chimney adapter (SCA) into the chimney/stack.
The long collar engagement ensures safe anchoring (See Fig. 3).
If necessary, the adapter can be secured by means of long
self-tapping stainless steel screws into the side of the collar
through the chimney wall.
Place high-temperature silicone on top of the adapter.
Remove the transport securing device (if present) holding the
motor shaft and impeller in place.
Center the fan over the cutout and place on the silicone.
Open the fan housing and secure onto the adapter through
the pre-drilled holes in the bottom of each corner. Use lag bolts
or self-tapping sheet metal screws.
Do not block the (4) drain holes.
3.3 Single Fan on Roof Curb
If the fan is installed on a curb cap, secure the roof curb with
self-tapping sheet metal screws (see Fig. 4).
Place high-temperature silicone on the top of the curb cap
around the curb cap opening.
Remove the transport securing device (if present) holding the
motor shaft and impeller in place.
Center the fan on the curb cap and place the fan on the silicone.
Open the fan housing and secure onto the roof curb through
the pre-drilled holes in the bottom of each corner. Use lag bolts
or self-tapping sheet metal screws.
Do not block the (4) drain holes.
Fig. 4
Caution: Never place hands or ngers on top of fan
base when closing
Fig. 3
Fig. 2

6
3000775 12.12
3.4 Single Fan on Brick Chimney
Theinstallationprocedureisthesameforroundandsquareues.
Ifaclayuelinerisinstalledandextendsbeyondthechimney,
cut it back so it extends no more than 1/2 inch above the chimney
crown.
Apply a bead of high-temperature silicone around the edges
oftheuetile.Placethefanovertheueandmakesurethefan
is completely sealed to the clay tile.
Open the top of the fan housing and secure with anchor bolts
through the pre-drilled mounting holes.
3.5 Side-Wall Mounting the Fan
Makesuretheventterminatesushwiththewall.Insertthesteel
chimney adapter (SCA) and secure it safely to the wall.
Sealaroundtheedgesoftheadapterange.
Mark the locations of the wall anchors and predrill holes for them.
Turn the fan upside-down and apply a bead of high-temperature
silicone on the base of the housing, close to the outer edge.
Orient the fan so the motor terminal box is pointed upwards. The
hinges on the housing should be on the left-hand side of the
installer as shown in Fig. 6.
Open the fan and secure it onto the adapter with wall anchors,
through the predrilled holes in the bottom. Make sure the conduit
is located on one of the sides, never on the upside or downside.
Seal around the fan base to make sure it is watertight and no
water can slip in between the fan and the adapter.
Do not block the (4) drain holes.
Do not side-wall mount the RSV450.
Caution: Never place hands or ngers on top of
fan base when closing
Fig. 5
Fig. 6

7
3000775 12.12
Fig. 8
If possible, the distance “A” should be equal to 3 times
the diameter of the chimney. This will improve accuracy.
3.6 Multiple Fan Installations
It is possible to install multiple fans in parallel. For details, please contact ENERVEX. The fans must be placed so
they can be opened for maintenance and chimney access.
Fig. 8 shows optimal placement.
3.7 Installation for High Temperatures
Ifthefanisusedforapplicationswheretheuegastemperaturesexceed482°Fattheueexit,dilutionairisrequired.
Dilutionairallowscoolairtodilutethewarmuegases.Thebestwaytointroducedilutionairisthroughabarometric
damper or draft hood mounted in the chimney system between the appliance outlet and the fan outlet. When
introducing dilution air, the fan capacity is reduced and a larger fan may be required.
3.8 Installation of Proven Draft Switch (PDS)
A safety system must be interlocked with the appliance(s). The safety system could utilize a Proven Draft Switch, a
thermalswitchoraowswitch.
Thedevicemustbeinterlockedwiththeheatingappliancesoitshutsdownincaseofinsufcientdraft,fanfailure
or power failure. Please refer to the PDS-1 Installation Manual if this control is used. For more information on
alternative safety systems, please contact ENERVEX, Inc. Fig. 8 shows the location of the stack probe used with
the PDS-1. The stack probe should be installed in a location where there is at least 0.05” WC.
A safety device that prevents the heating appliance operation, in case of a power failure or
inadequate draft situation, must be installed.
Fig. 7

8
3000775 12.12
4. Electrical Installation
4.1 Electrical Requirements
Power requirements depend on the fan size and they can be found on page 4.
Danger: Turn off electrical power before servicing. Contact with live electric components can
cause shock or death.
Notice: If any of the original wire supplied with the system must be replaced, use similar wire
of the same temperature rating. Otherwise, insulation may melt or degrade, exposing bare
wire.
4.2 Wiring Diagram for RSV 200-315
The connection diagram below shows a single-phase fan connected to a fan speed control and the power
source (see Fig. 9).
Use2-conductorwireofminimum14AWGwithground.Wiringmustberunoutsidethechimney/stackinexibleor
rigid metal conduit.
Fig. 9

9
3000775 12.12
4.3 Wiring Diagram for RSV 400-450
The wiring diagrams below shows a three-phase fan connected to the power source (see Fig. 10).
Usea3-conductorwireofminimum14AWGwithground.Wiringmustberunoutsidethechimney/stackinexibleor
rigid metal conduit.
Where variable speed is required, the fan is connected to a variable frequency drive (VFD). Wire according to Fig. 10
for systems using the ABB ACH550 series VFD.
Fig. 10

10
3000775 12.12
5. Startup and Conguration
5.1 System Testing
• Checkthelinevoltagewiththemotornameplaterating.
• Checkthatthetransportsecuringdeviceholdingthemotorshaftandimpellerinplacehasbeen
removed.
• Determineiftheaxialvaneorimpellerisrunningfreeandhasnotbeensubjecttomisalignmentin
shipping or installation.
• Applypowerandcheckthattheaxialvaneorimpellerisrotatinginthedirectionofthearrowontheside
of the top motor cover (RSV400/450 only). All RSV fans run in a clockwise direction when
viewed from the top.
• Switchinganytwophasesinthejunctionboxwillreversetherotation.
5.2 Adjusting Fan Speed
• Startallheatingappliancesconnectedtothechimneywiththefaninstalled.Setthefanspeedcontrol
to the speed where no spillage is experienced anywhere in the system.
5.3 Testing Safety System
• AdjustthesettingoftheProvenDraftSystemorotherdevice.
• Starttheheatingappliancesandthechimneyfantomakesurethesafetydeviceisfunctioning.Turn
the fan off. After less than 1-2 minutes all appliances should be shut down.
Make sure the fan is running in the correct direction; the fact that the fan blows is no
guarantee it is doing so. Running the fan in the wrong direction over a longer period of
time will damage the motor.
It is important that the installation, start-up and system testing procedures are followed.
Failure to do so may have a major negative impact on motor expectancy.
Fig. 11
The motor wiring terminals in Fig. 11 show default jumper
positions for 3x208-240VAC operation.
If the application requires 3x440-480VAC operation, the
jumper positions must be changed according to Fig. 12.
After wiring, make sure the motor is rotating in the proper
direction. This is marked on the motor end cover. If the
rotation is incorrect, swap the two wires going to the motor
terminals, U1 and W1.
Fig. 12
RSV 400-450 can operate at either 3x208-230 VAC (default) or 3x440-480 VAC.

11
3000775 12.12
6. Maintenance and Troubleshooting
6.1 Maintenance Intervals
• TheRSVChimneyFanisdesignedforcontinuoususe.
• Forgasapplications,noregularmaintenanceisrequired.
• Foroilapplications,inspecttheaxialvaneorimpellerafter(3)monthsandsetupaperiodicinspection
basedonthesendings.Cleanasrequired.
• Thefanmotorsareequippedwithpermanentlylubricatedsealedballbearings.Theydonotrequire
lubrication.
6.2 Cleaning
Warning: Do not open the motor housing unless power to the chimney fan has been
disconnected.
• LoosenthetwoPhillipsscrewsinthefrontoftheunit.
• Tiltthetopofthefanbyliftingthehinge.Makesurethe
locking arm holds the top of the fan before letting go.
• Ifnecessary,useascraperandabrushtocleantheimpeller
and the inside fan base (see Fig. 13).
6.3 Troubleshooting
Fig. 13
Caution: Never place hands or ngers on top of
fan base when closing
Problem Possible Cause What to do
The fan is not operating. No power to the fan. Check the power supply wires in the junction box by the fan.
Check the circuit breaker.
Check that the fan is actually turned ON.
The fan is not running
at full speed and/or is
humming.
The capacitor is improperly
connected or not connected at all
(single-phase fans only).
Check the connections inside the junction box. The capacitor
must be installed according to wiring diagram.
The fan is rotating
backwards (RSV 400/450
only).
Phase sequence in the power to
the fan is reversed.
Swap two phases in the junction box.
The fan is vibrating
vigorously.
The motor shaft is damaged. Turn the power off immediately. Open the fan and check if the
shaft is straight. If not, contact ENERVEX.
The fan is noisy. A transportation device has not
been removed.
Foreign matter is stuck in the fan.
A ball bearing is damaged.
Remove the transportation device.
Turn off the power and remove the foreign article.
Turn off the power. Wait for the motor to stop revolving. Spin
the wheel and listen for any grinding noise from the motor. If
necessary, replace bearing.
The fan stops in the
middleofaringcycle.
The motor is overheating. Checktheuegastemperaturebelowthefan.Thetemperature
should not exceed 482°F during continuous operation. Call
ENERVEX.

ENERVEX Inc.
1685 Bluegrass Lakes Pkwy.
Alpharetta, GA 30004
P: 770.587.3238
F: 770.587.4731
T: 800.255.2923
www.enervex.com
3000775 12.12
This manual suits for next models
6
Table of contents
Other ENERVEX Fan manuals