Fig. 5 (16pcs batteries connection)
2.2.2 After the battery installation and connection done, check if BAT+ to N & N to BAT- voltages
are correct with multimeter or other equipments. Install the cover if the voltages are correct.
NOTE: Battery “+” “-”poles cannot be reversed, also cannot short the battery “+” “-”
poles, otherwise batteries would be damaged or other accidents would happen. Don’t touch
the battery “+” “-”poles at the same time. It’s better only single man make the operation.
3.Battery pack accessories
A complete of 6-10kVA UPS battery pack includes below accessories.
Red wire 1015 10AWG 550mm 250TC+YI6
Black wire 1015 10AWG 600mm 250TC+YI6
Black wire 1015 10AWG 101mm 250TC*2
Black wire 1015 10AWG 650mm 250TC*2
Black wire 1015 10AWG 550mm 250TC*2
4wires Red 1015 12AWG 150mm*2/200*2 YI6+P30*4
4wires black 1015 12AWG 150mm*2/200*2 YI6+P30*4
4wires Blue 1015 10/12AWG 100*2/270/340/80*4mm
250TC*2+BN8+BN5.5*2+P30*4
NDB2Z-63 C63/2 2P 63A/440Vdc UL RoHS