Envertech EnverBridge Operation instructions

Zhejiang Envertech Corporation Ltd.
Tel:+86 579 8926 6326
Email:info@envertec.com
Add:24th Floor, Jintong Mansion,
Center of Headquarters,Yongkang City,
Zhejiang Province, China
User Operating Manual
Model Number: EnverBridge
This manual is an integral part of the unit. Please read the instruction
manual carefully before installation, operation or maintenance. Keep
this instruction manual for future reference. This document is not to
be reproduced in any manner, nor are the contents to be disclosed
to anyone, without the express authorization of Envertech.

Content
1. Read This First...............................................................................................
2 Symbols in the manual....................................................................
2.1 Safety symbols.................................................................................................
2.2 Other Symbols....................................................................................
2.3 Technical competence........................................................................
2.4 Safety Instructions..............................................................................
3 Packing and Feature........................................................................
3.1 Assembly parts...................................................................................
3.2 Structure of EnverBridge....................................................................
3.3 Main functions.....................................................................................
3.4 Technical Parameters.........................................................................
4 Installation.........................................................................................
4.1 Operating Condition............................................................................
4.2 System diagram..................................................................................
4.3 Installation Procedure.........................................................................
5 Operating Static................................................................................
5.1 Working Mode.....................................................................................
5.2 Grid-Connection..................................................................................
5.3 Grid Disconnect..................................................................................
5.4 Installation checklist............................................................................
5.5 Start-Up– Checks...............................................................................
6 LCD Abstracts...................................................................................
6.1 Brief introduction.................................................................................
6.1.1 Function of LCD..................................................................................
6.2 LCD 1602 interface.............................................................................
6.2.1 Start-up interface................................................................................
6.3 Monitoring interface............................................................................
6.4 Making-up network construction status..............................................
6.5 Fault display........................................................................................
6.5 Application..........................................................................................
7 Disconnecting a EnverBridge from the system.............................
8 Monitoring and Troubleshooting and Maintenance......................
8.1 Safety checks......................................................................................
8.2 Maintain periodically............................................................................
8.3 Internet WEB.......................................................................................
9 Contact...............................................................................................
1
1
1-2
2-3
3-4
4-5
6
6
6
7
7
7
7
7-8
8-9
9
9-10
10
11
11-12
12
12
12
12
12
12-13
14
14-15
15
16
16
16
16-17
17
18-19
20

Thank you for selecting Envertech– a leading supplier of micro-inverter products for
the solar PV market. Envertech’s new product “EnverBridge” acts as the power
interface (PI) to the utility grid. It is an information gateway for the Envertech
Microinverter. The data of real-time performance information of energy harvest for all
Envertech micro-inverter systems can be collected by EnverBridge, and be transmitted
to Envertech Monitoring Device called EnverPortal to achieve a global data
monitoring for PV power plant.
The user manual includes EnverBridge overview, installation, operation instruction and
technical parameters. To assure properly installation and operation, please carefully
read this user manual before installation, and pay attention to the caution symbol
affixed on the product.
Please hand the user manual to the end user.
2.Symbols in the manual
2.2 Other Symbols
!DANGER
1 2
1 Read This First
2.1 Safety symbols
Warnings and cautions tell you about the dangerous conditions that can occur if you
do not follow all instructions in this manual.
Please read following safety symbols to indicate dangerous conditions and important
safety instruction.
DANGER
The DANGER symbols in this manual and on the
EnverBridge.
Indicate a hazard with a high level of risk which if
not avoided, will result in death or serious injury.
CAUTION
The CAUTION symbols in this manual and on
EnverBridge indicate a hazard with a low level
of risk which if not avoided, could result in minor
or moderate injury.
NOTE
The NOTE symbols in this manual indicate the
important product information.
!CAUTION
Some Symbols replace words on the equipment, on a display, or in manuals.
SEEYES Trademark
No access for unauthorized personal
Caution, risk of danger
Symbol for the marking of electrical and electronics
devices according to Directive 2002/96/EC. Indicates that
the device, accessories and the packaging must not be
disposed as unsorted municipal waste and must be
collected separately at the end of the usage Please follow
Local Ordinances or Regulations for disposal or contact an
authorized representative of the manufacturer for
information concerning the decommissioning of equipment.
Direct curren
Alternating current
PE Protective conductor
Earth(ground)TERMINAL
Protective conductor Terminal
Fuse
Refer to the operating instructions
!WARNING
WARNING
The WARNING symbols in this manual and on the
EnverBridge indicate a hazard with a medium
level of risk which if not avoided, could result in
death or serious injury.

or attempted by anyone not having such qualifications.
Compliance with safety regulations depends upon installing and configuring system correctly,
including using the specified wirings. Only professional assemblers who are familiar with
requirements for safety, Photovoltaic system and EMC must install the system.The assembler is
responsible for ensuring that the end system complies with all the relevant laws in the country
where it is to be used.Envertech require using only genuine replacement parts, manufactured
or sold by Envertech for all repair parts replacements.
Compliance with safety regulations depends upon installing and configuring system correctly,
including using the specified wirings. Only professional assemblers who are familiar with
requirements for safety, Photovoltaic system and EMC must install the system.The assembler is
responsible for ensuring that the end system complies with all the relevant laws in the country
where it is to be used.Envertech require using only genuine replacement parts, manufactured
or sold by Envertech for all repair parts replacements.
Read completely through each step in every procedure before starting the procedure; any
exceptions may result in a failure to properly and safely complete the attempted procedure.
Servicing of this product in accordance with this manual should never be undertaken in the
absence of proper tools,test equipment and the most recent revision to this manual, which is
clearly and thoroughly understood.
This chapter contains the safety instructions that you must follow when installing,operating and
servicing the unit. If ignored, physical injury or death may follow, or damage may occur to the unit.
Read the safety instructions before you commence work on the unit.If you are unable to
understand the Dangers,Warnings,Cautions or Instructions, contact the manufacturer or an
authorized service dealer before installing, operating and servicing the unit.
To ensure your personal safety and the proper use of EnverBridge,please carefully read this manual
before installation.If the product is damaged when installation not comply with this manual,
Envertech do not respond for any quality assurance and other risks.
For Envertech EnverBridge Warranty Terms and Conditions, see the appendix of this manual.
3 4
PV
PCS
+
_
Caution, risk of electric shock
CE mark is attached to the solar EnverBridge to verify that
the unit follows the provisions of the European Low Voltage
and EMC Directives
Photovoltaic
DC terminal, indicating the polarity of the connections,
positive, all positive connections shall be made with
Redinsulated wire
DC terminal, indicating the polarity of the connections,
negative, all negative connections with black insulated
wires
Power conversion equipment, hereby is our DC/AC inverter
SERVICE PERSONNEL
A person having appropriate technical training and
experience necessary to be aware of hazards to which that
person may be exposed in performing a task and of
measures to minimize risks to that person or other persons
Qualified personnel
Person adequately advised or supervised by an electrically
skilled person to enable him or her to perceive risks and to
avoid hazards which electricity can create. For the purpose
of the safety information of this manual, a "qualified person"
is someone who is familiar with requirements for safety,
refrigeration system and EMC and is authorized to energize,
ground, and tag equipment, systems, and circuits in
accordance with established safety procedures. The
EnverBridge and endues system may only be commissioned
and operated by qualified personnel.
DVC Decisive voltage class
Closed Electrical
Operating Area
Room or location for electrical equipment to which access is
restricted to skilled or instructed persons by the opening of
a door or the removal of a barrier by the use of a key or tool
and which is clearly marked by appropriate warning signs
2.3 Technical competence
The procedures described in this manual should be performed by trained and authorized personnel
only. Maintenance should only be undertaken by competent individuals who havea general
knowledge of and experience with devices of this nature.No repairs should ever be undertaken
2.4 Safety Instructions
• Be aware that only qualified personnel should install and /or replace Envertech EnverBridge.
• Perform all electrical installations in accordance with all local electrical codes.
• Comply the rules of correctly use of tools and personal protective equipment (PPE) for insuring

3 Packing and Feature
3.1 Assembly parts
3.2 Structure of EnverBridge
Object Quantity Description
A 1
1B
the EnverBridge safe running.
5 6
!WARNING
WARNING: Be aware that the input AC voltage
of the Envertech EnverBridge shall not exceed
the rated voltage; higher voltage may cause
permanent damage to the device.It contains no
user serviceable and Envertech-EnverBridge
Warranty parts.
CAUTION: SAVE THESE INSTRUCTIONS– This
manual contains important instructions for
EnverBridge that shall be followed during
installation and maintenance.
!CAUTION
• Connection of any photovoltaic system to the electrical utility grid should only commence after
receiving prior approval from the utility company.
• The EnverBridge MUST be installed and debugged complying with this manual by the professional
authorized by Envertech.
• All electrical installation MUST meet the local standard.
• To assure the safe running, must comply with the relative standard for using the tool properly and
Personal Protective Equipment (PPE). Away from the chemical and reagent.
• The EnverBridge must installed environments suitable for it’s IP rating.
• CAUTION! The device is intended for fixed installation, Located on a part that is not removable
without impairing the operation of the unit.
• CAUTION! Visible and legible to the operator during the normal operation of the device.
• WARNINGS - Risk of electric shock- Do not open cover. No user serviceable parts inside. Servicing
limited to qualified service personnel.
• WARNINGS - The printed circuit boards contain components sensitive to electrostatic discharge.
Wear a grounding wrist band when handling the boards.Do not touch the boards unnecessarily.
• WARNINGS - Do not operate any device which is damaged, lacking parts or dented. Failure to
observe this warning may result in an electric shock, injury, fire or accident.
• WARNINGS - Before installing the unit, agree with the customer the site.
• WARNINGS - The output connection with AC grid shall be protected by a max. 20A circuit breaker.
• The EnverBridge shall be connected with the Envertech EVT248 or EVT500 inverter as a system. It
cannot operate as a stand-alone unit or in case of AC grid disruption
Warning:
Only authorized persons can be allowed for installation
of inverter
EnverBridge
Screw
Object Description
1
2
3
4
5
Cover
LCD Screen
Cable gland
AC Cable
Frame

3.3 Main functions
4 Installation
3.4 Technical Parameters
Model
Interface
Power Line Communication
LCD
Ethernet
Capacity
Numbers of devices connected
Power Requirements
AC Supply
Power Comsumption
Dimensions
Weight
Ambient Temperature Range
Enclosure Environment Rating
Features
Compliance
Warranty
Mechanical Data
Cooling
EnverBridge
Envertech Proprietary
LCD Screen
RJ45
Monitor up to 20 units of EVT248
(or 10 units of EVT500)
220V/230V/240V;50Hz/60Hz
225mm*50mm*107mm
3W
700g
Natural convection- no fans
-40℃~65℃
IP65
CE
5 Years
7 8
Use the Power Line Carrier Communication (PLCC) technology within Photovoltaic power
plant
By PLCC technology, EnverBridge collects generation data from the PV power plant, and
transmits to the EnverPortal database by its built in EnverBridge.
4.1 Operating Condition
Operating Temperature Ambient temperature: -40℃~65℃
Operating Humidity Air Relative Humidity <=90%
Rated Input AC230V/50Hz
4.2 System diagram
Figure 4.2 System diagram
4.3 Installation Procedure
Dimension See below Figure 4.3.1.
Figure 4.3.1 Dimension of EnverBridge
Figure 4.3.2 Installation Diagram
Installation Diagram
See below Figure 4.3.2.

9 10
Step 1:Use the screwdriver to open on the right side of the cover plate
Step 2:Get through the cable to the connector
Step 3: And then plug the RJ45 on the PCB
Step 4: fasten the cable on the casing of Translate
Installation diagram
5 Operating Static
Monitoring Device EnverBridge is the core component created by Envertech, it realizes
the connection between solar power plant and internet.As an intelligent
communication gateway, EnverBridge uses Envertech’s Power Line Communication
(PLC) technology to continuously monitor the data of energy harvest of solar power
plant such as power, voltage, current and frequency; it can also transmit the real-time
data of energy harvest to EnverPortal to realize the monitoring around the world.
Set aside a minimum functionality of the EnverBridge module, you can optional this
EnverBridge modules to achieve the connection between PV power plant and the
Internet. RJ45 cable should be simultaneously matching with EnverBridge module.
5.1 Working Mode
The working modes of an Envertech EnverBridge are:
Start up
Active
Fault
Standby
The detailed working mode descriptions are as below:
Start up
Start up mode is for a newly installed EnverBridge.This startup mode must base on the
proper AC, micro-inverter, Ethernet cables connecting.
Active
When the EnverBridge is in normal operation process, this insures that the power
available from micro-inverter array is exported to the utility grid.
Fault
If the system does not operate correctly, Envertech EnverBridge will stop automatically
and enter into Disable mode.The Envertech EnverBridge system keeps detecting the
disable information, it will be in disable mode until fault release. If the inoperative
EnverBridge has been repaired and match to the electrical utility grid, the whole system
would enter operation mode after 60 seconds to 5 minutes. Be aware that only qualified
personnel should maintain the ENVERTECH Micro-Inverters.
Standby
When the EnverBridge is in operation process but keeps with low voltage and current in
micro-inverter side for a certain time.The EnverBridge manages transition from“Active”
to“Standby”. In “standby”mode, Micro- Inverters keep detecting the energy output of
each micro-inverter. When the output energy
reaches the power generation conditions, the inverter would enter into“Active”from the
“Standby” state.
• The equipment maintenance only can be carried through
by service department of Envertech, or the service centre
or professional authorized by Envertech. Maintenance
personnel should be familiar with all the warnings in this
manual and the proposed steps.
• Must be sure to disconnect the input and output power
before removalof equipment for maintenance.
5.2 Grid-Connection
EnverBridge system connects grid automatically. It detects and monitors the
performance of each PV module through each micro-inverter. When the output energy
reaches the power generation conditions, the EnverBridge system begin to collect the
data from Microinverters.

If the state grid cannot match the following situations (table 5.3.1), it bring the Envertech
EnverBridge to the rest mode.
Checklist
Check the mechanical and electrical installation of the unit before startup. Go through
the checklist below together with another person. Read the Safety instructions and EC
directives on the previous pages of this manual before you work on the unit.
Mechanical Installation
Check screw connections on the EnverBridge for tightness. The ambient operating
conditions are allowed. (See Technical parameter); The unit is fixed properly on a
nonflammable wall or the combiner box or the rack. (See Mechanical installation.) The
cooling air will flow freely. The unit is fixed tightly and support is enough. (See Mechani-
cal installation.)
Electrical Installation
Check all screws of the connection terminals in the installation system before and after
the EnverBridge for tightness.
The AC input voltage matches the unit nominal voltage. Assure EnverBridge AC cable’s
connections and their tightening torques are OK.There are no tools, foreign objects or
dust from drilling inside the unit. Unit, connection box and other covers are in place.The
Ethernet cable connections are OK. The external cords and cables are fixed tightly, and
strain relief clamp is provided for external accessible cords and cables. Cord and cable
inlets are sealed completely after cord/cable installation.
The device has been checked at the factory and adjusted so that it can be commissioned
immediately after being installed.
Following Section Installation checklist, for your personal safety and to avoid damage,
the following safety checks should be performed before start by a qualified person who
has adequate training, knowledge, and practical experience to perform these tests. The
data should be recorded in an equipment log. If the device is not operating properly or
fails any test,the device has to be repaired.
1.Inspect the equipment and accessories for mechanical and functional damage.
2.Inspect the safety relevant labels for legibility.
3.Inspect the fuse to verify compliance with rated current and breaking characteristics.
4.Measurement of insulation resistance
5.Measurement of earth resistance
6.Mounting structures: Verify tightness and integrity of bolts and other fastening
devices, also check if there is significant corrosion.
The purpose of the manual for LCD of EnverBridge is to help users to know the function
quickly and guide them to use LCD to perform how it works.
Monitoring the system and Showing the real-time working status
Helping installation personnel to confirm the system operation status
Making the system failure checking up more convenient for the maintenance and
debugging personnel
The start-up logo shows on the LCD screen interface once the power of EnverBridge
equipment is on and starts to work. The first line shows the company name Envertech
and the second line shows the company website www.envertec.com (as shown below).
6 LCD Abstracts
5.3 Grid Disconnect
11 12
WARNING
Connect the EnverBridge to the electrical utility
grid only after receiving prior approval from the
utility company.
WARNING
Only qualified personnel could connect
Envertech EnverBridge to the electrical utility
grid.
Type
Voltage
Frequency
Rated
230V
50Hz
Variation Range
205V - 265V
47Hz – 51Hz
Table 5.3.1 Parameter of European state power grid
Start EnverBridge after checking all below steps:
5.4 Installation checklist
To ensure the safe operation of the devices,they may be installed and commissioned only
by qualified personnel in full compliance with the warnings referred to in this manual.
5.5 Start-Up– Checks
6.1Brief introduction
6.1.1 Function of LCD
6.2 LCD 1602 interface
6.2.1Start-up interface

Then the network unlocking starts and on the screen of LCD “All MI LID clear” shows
on the first line and “...”on the second line, which indicates the overall network
unlocking process is taking place (as shown below).
Upon the completion of the overall network unlocking the network construction
between EnverBridge and MI starts. On the first line of the LCD 1602 screen “MI
connecting” indicates the connection to MI has started and“x MI connected” on the
second line shows how many MI units have been connected with x indicating the
numbers of MI units connected.
EnverBridge gets into monitoring working status following the starting-up of Enver-
Bridge. The monitoring information will be displayed on LCD, which includes four
parts,namely,IP address, the current power, power production and the numbers of MI
units (as shown below).
IP address shows on the first line of LCD screen. For example, 192.168.0.201 indicates
a normal network connection and 192.160.0.254 indicates an abnormal network
connection.
The figure of power efficiency which shows at the beginning of the second line
indicates the real-time power efficiency. For example,4895W.
The figure of power generation output which shows at the middle of the second line
indicates the overall amount of power generation. For example, 184KWh or 100MWh
The power generation output is calculated to the accuracy of KWh. If the output rises
up to MWh ,the number displayed is rounded off automatically. (Please refer to the
long distance or local server to get a detailed information.)
After the completion of network construction the EnverBridge start-up process
finishes and EnverBridge is in normal monitoring working status. It will take a
relatively long period of time before the monitoring interface information shows up
on the LCD screen. EnverBridge will unlock and construct the network again
automatically if there is a failure of network construction.
13 14
6.3 Monitoring interface
6.4 Making-up network construction status

The monitoring status can be seen by users through LCD screen.
The installation is completed once the monitoring interface shows up on LCD screen.
According to what shows on the LCD screen, the maintenance personnel can see
where the problem comes from when they are fixing the equipment.
1.If the LCD screen stays at the interface of unlocking and constructing network,it
means the network construction fails. Then MI should be checked to make sure it is
connected properly and the MI power is on.
2.If it shows on LCD screen for a long time that the the number of MI units is less than
that of MI units connected to EnverBridge, it’s time to check whether there is a failure
on a certain MI equipment.(As to which one is not working, please get information
form long-distance or local server.)
3.According to the displaying interface of failure, maintenance personnel can locate
the failure and start the maintenance work.
Safety checks should be performed at least every 12 months by manufacturer’s
qualified person who has adequate training, knowledge, and practical experience to
perform these checks.The data should be recorded in an equipment log.If the device
is not functioning properly or fails any of tests, the device has to be repaired.
To ensure safe disconnection of the EnverBridge from the solar power plant, it must
NOT be carried out under load conditions. Ensure the following disconnection steps
are carried out in the order shown:
1. Disconnect the AC by isolating the branch via the circuit breaker.
Or Disconnect the plug from the wall socket.
2. Disconnect the Ethernet cable.
3. Remove the EnverBridge from the system.
Only trained and authorized professional personnel WHO ARE FAMILIAR WITH THE
REQUIREMENTS OF SAFETY is allowed to perform servicing and maintenance work.
6.5 Application
6.5 Fault display
20 minutes after data collection, a making-up network construction will take place in
case there is any missing connection of MI.“MI connecting” which shows on the first
line of LCD 1602 screen indicates the connection to MI is taking place and “x MI
connected” on the second line indicates how many MI units have been connected
with x referring to the numbers of MI units connected.
If there is a system malfunction, FAILURE shows on the displaying interface. The ID
number(s) of failed MI can be seen on the first line of the interface with the informa-
tion of failure following it. Please refer to 2.5 to get a detailed explanation of failure.
What shows on the second line of LCD interface is the same as the monitoring
interface of LCD.
categories failure identification
symbols Explanation of failure
M
M
M
M
0
1
failure-free
the original boundary malfunction
inverter failure
ailure caused by over voltage or
under voltage of power grid
2
3
4
5
6
0
1
2
3
4
M
M
M
M
S
S
S
S
failure caused by over frequency or
under frequency of power grid
inner communication failure
other failures
malfunction-free
malfunction caused by over voltage
or under voltage of power grid
malfunction caused by over
frequency or under frequency of
power grid
phase-locked failure
other failures
7 Disconnecting a EnverBridge from the system
8 Monitoring and Troubleshooting and Maintenance
!WARNING
No use-serviceable parts inside, if the
EnverBridge has any malfunctions, send it
to authoriz ed representative or
manufacturer. Never open and try to
repair it by yourself
8.1 Safety checks
15 16

For safety check details, refer to this manual, section 3 Safety instruction and EC
Directives.
Only qualified person can carry out the following works.
During the process of using the EnverBridge, the manage person shall examine and
maintain the machine regularly. The concrete operations are as follow.
1. Check the EnverPortal website to confirm if the screen in the EnverBridge is normal
or not.This check should be performed at least every 6 months.
2. Check if the cables are damaged or aged.This check should be performed at least
every 6 months.
3. Check for dust or debris. It there’s dust and or debris on EnverBridge, clean it lightly
by brush or vacuum the unit to remove dust particles, which may cause components
inside overheat.
Before cleaning the EnverBridge:
Wear gloves and safety glasses.
Disconnect the EnverBridge from the Grid – Isolating device.
Clean the EnverBridge with wet cloth carefully.
Introduction
Use the monitoring website EnverPortal developed by Envertech to monitor the
statistics information of the energy harvest for all Envertech micro-inverter system
and monitor per-module’s performance which is integrated into the Envertech
micro-inverter system.
Register address:http://www.envertecportal.com/LoginPage.aspx
Account Registration
Register Successfully, enter into the page below:
8.3 Internet WEB
8.2 Maintain periodically
NOTE
The NOTE symbols in this manual indicate the
important product information.
WARNING
Be aware that only qualified personnel should
troubleshoot the PV array or the Envertech
Micro-Inverter.
WARNING
Never disconnect the DC wire connectors
under load. Ensure that no current is flowing
in the DC wires prior to disconnecting and turn
off the AC breaker.
17 18

click“settings”,and enter into the page below:
click“device”
At the last part of the page, click“add”, fill the EnverBridge serial Number in the blank
space, for example:“90000001”, click “OK”and finish the registration.
19 20
9.Contact
Zhejiang Envertech Corporation Ltd.
Tel:+86 579 8926 6326
Email:info@envertec.com
Add:24th Floor, Jintong Mansion, Center of Headquarters,Yongkang City,
Zhejiang Province, China
Table of contents
Popular Gateway manuals by other brands

Fortinet
Fortinet FortiGate 80C-LENC quick start guide

LevelOne
LevelOne WHG-1000 user manual

Philio
Philio PSC05 quick start guide

ZyXEL Communications
ZyXEL Communications VSG-1200 V2 user guide

Projectek Networking Electronics
Projectek Networking Electronics BESTip ATA GSM user manual

CarpeStar
CarpeStar SMG Series user manual