eoltec HC-6K-230V-M User manual

HC6K_V02a_eng - subject to possible technical modifications - www.eoltec.com updated 11-2004 1/7
6 KW Heater Controller
With optimal power point tracking for Scirocco wind turbine
Description :
Our 6kW Heater Controller provides a simple and economic way to realize direct heating
applications with our 6kW Scirocco wind turbine.
It is intended to directly works with standard 230Vac heater resistors, and thus can easily adapt to
existing installation.
Features :
•6000W rated output with 5kW to 7.5kW (@ 230Vac) rated resistors.
•Possibility to connect 2kW to 9kW rated resistors (with derating).
•All working parameters and settings are displayed on a unique and large LCD display with keypad,
and there is no need for any additional metering or display device.
•Total produced energy is internally recorded and can be displayed.
•Programmable maximum voltage-current-power allows to perfectly tune the installation in case of
re-employ of existing heaters.
•Digital input for remote control ( output ramp up/ ramp down).
•Internally self powered by the wind turbine generator. No need for any other power source.
•Noise free DC output (PWM converter, 20khz IGBT switch) doesn’t generate any mechanical noise
in the heater resistor.
•Specifically designed to work with Scirocco Wind Turbine, variable speed management and our
unique DSP controlled Maximum Power Point Tracking system ensures maximized wind power
extraction, even in low wind conditions, and low noise.
Eoltec’s power electronics are manufactured and developed in exclusive cooperation with leading innovative
inverter manufacturer, MLT Drives CC (South Africa – www.mltdrives.com - info@mltdrives.com )

HC6K_V02a_eng - subject to possible technical modifications - www.eoltec.com updated 11-2004 2/7
– 6 kW Heater Controller Specification Sheet –
Model HC- 6K-230V-M
Connection 1 - WT generator input
Input voltage range ( 3 phases input) 60V to 270V AC
Input voltage frequency 15 to 55 hz
Maximum input current (continuous, per phase) 16 A
Maximum input power (continuous) 6300 W
Connection 2 – Heater resistor
Nominal output voltage 230V dc
Maximum output voltage (adjustable) 250V dc
Maximum output current (adjustable) 30A dc
Maximum output power (adjustable) 6000 W
Maximum heater resistance 30.0 Ω
Minimum heater resistance 5.5 Ω
Connection 3 – Remote control digital input
Input open voltage 5V dc
Input closed sink current (0V) 4 mA
Input logic NO or NC (adjustable)
Power up-down ramp time 1 s
User interface
Main display LCD, 2 lines of 16 characters
Alarm display Main LCD display + Led
Parameters input and scrolling Keypad
Displayed parameters
Output voltage/current/power
Wind turbine rpm
Totalized produced energy
Error messages
Displayed user settings
Maximum current limit
Maximum voltage limit
Maximum power limit
Remote control input logic (NO/NC)
Firmware version
Housing
Dimensions (DxWxH) mm 300x468x215mm
Weight (kg) 16 kg
IP protection index IP53
Input & output connections Internal screw connectors
Fixing Wall mount
Miscellaneous
Operating temperature range -10 to +45°C
Maximum efficiency 95%
Over voltage protection Output voltage
Over temperature protection yes
Over current protection Electronic control and circuit breaker
Cooling Natural cooling
Mean time between failure (MTBF) >25000 hours (at 100% output power)
Warranty 2 years

HC6K_V02a_eng - subject to possible technical modifications - www.eoltec.com updated 11-2004 3/7
Output power versus heater resistor characteristics :
Different limits are implemented in the device (adjustable in user menu settings):
Maximum output power : 6000W
Maximum output voltage : 250Vdc
Maximum output current : 30 Amp. dc
load impedance : 5 to 30Ω
Due to these limits, the maximum achievable output power is depending of the resistance of the load connected to
the output :
0
1 000
2 000
3 000
4 000
5 000
6 000
0 1 000 2 000 3 000 4 000 5 000 6 000 7 000 8 000 9 000
Heater resistor Nominal Power (Watts at 230Vac)
Maximum effective Power output
(Watts)
Dimensions and fixing :
Note : The device must be vertical for correct cooling

HC6K_V02a_eng - subject to possible technical modifications - www.eoltec.com updated 11-2004 4/7
- Installation and operation -
Cautions and Warnings
WARNING
THE HC- 6K HEATER CONTROLER GENERATES
HIGH VOLTAGES AND CURRENTS.
INCORRECT USE MAY CAUSE ELECTRICAL SHOCK AND DEATH.
•This manual is only for use with the HC- 6K Heater controller.
•The HC- 6K Heater controller contains sophisticated electronic equipment and must be installed by a qualified
electrical technician. Any queries must be referred to the appropriate service provider.
•Any work performed on the HC- 6K Heater controller and the installation of the HC- 6K Heater controller must comply
with local and national electrical regulations.
•All precautions relating to the installation and operation of mains voltage equipment must be observed when installing
the HC- 6K Heater controller. This includes considerations to insulation of cabling, access to bare conductors,
grounding, protection from moisture etc.
•Do not operate the HC- 6K Heater controller with any panels or covers removed. Do not operate the HC- 6K Heater
controller if it is not properly installed.
•After being disconnected, the HC- 6K Heater controller may still contain high voltages in the capacitors. Ensure that
these have been fully discharged before working on the HC- 6K Heater controller.
•Do not use the HC- 6K Heater controller outside the permissible ambient conditions.
•Do not short the inputs or outputs of the HC- 6K Heater controller while the HC- 6K Heater controller is running, as
this can cause damage to the HC- 6K Heater controller.
Warranty
•Warranty is for two years from date of purchase.
•No liability is accepted for any damages occurring through use, manipulation, working situations and handling which
are not explicitly mentioned in these operating instructions.
•The following cases are not covered by the warranty:
oReverse polarity on Battery connections (+/- reversed)
oConnection to incorrect load
oDamage due to condensation in the appliance
oDefects caused by transport damage, force, physical or mechanical means
oAny unauthorised changes to the system
oDamage from any over-voltages (over input voltage, lightning, etc)
Features
The HC- 6K Heater controller has numerous advanced features, including.
•Simple installation and configuration
•Fully dedicated and tuned for use with Eoltec’s Scirocco wind turbine
•State-of-the-art Digital Signal processor system
•Easy connection to heater resistor / wind turbine
•Output enable/disable remote control with programmable NO/NC logic
•Silent operation
•Maintenance free

HC6K_V02a_eng - subject to possible technical modifications - www.eoltec.com updated 11-2004 5/7
Operator interface
•Enable/disable output with ON key
•Scroll the displayed parameter (+and -key)
•accessing and modifying the adjustable setup parameters (Menu , Enter,+ / - keys).
Parameters display :
•Once the WT is running, the display is enabled.
•Scroll the displayed parameters with +and -keys.
0 RPM
Power out : 0W
Vout : 0V
Iout : 0.0A
+/-
Total energy :
000000.00 kWh
+/-
Heatsink : 20 C°
Load : 8.5 Ohms
+/-
Display list
(scroll with +/-)
PIC 877 WTHC_V3
DSP2407A WTHC_V3
+/-

HC6K_V02a_eng - subject to possible technical modifications - www.eoltec.com updated 11-2004 6/7
Parameters setting :
4 parameters can be set :
•Maximum output current (10.0 to 30.0A, default 30.0A)
•Maximum output voltage (200 to 250Vdc, default 250Vdc)
•Maximum output power (2000 to 6050W, default 6050W)
•Remote input logic (NO or NC, default is NO with output enabled)
Imax. Out :
30.0A
Pmax. Out :
6050 W
Enter
Umax. Out :
250 V
Enter
Remote logic
NO
Enter
Parameters
setting
Press reset to
update settings !
Enter
Change User
Settings Enter
Menu and +
adjust with +/-
then press Enter
adjust with +/-
then press Enter
adjust with +/-
then press Enter
adjust with +/-
then press Enter
Press Reset to update
Or wait a few second and the display will
automatically go back to parameters
Site selection
The heater controller must be installed indoors, in a dry, shady, clean environment. Easy access to the cabling terminals
must be available.
At least 150mm clearance must be provided with sides and top box for correct cooling.
Wiring :
Load
Remote
control
switch
Thermal
breaker
(17A)
PMG

HC6K_V02a_eng - subject to possible technical modifications - www.eoltec.com updated 11-2004 7/7
Connection to Load output :
Ensure that all breakers are “OFF”.
Connect the single-phase cabling from the load to Gnd and V+ terminals.
Connect ground wire to ground terminal.
Cabling should be of at least 6mm2core cable (for 6kW heater resistor).
Connection to Scirocco generator :
Ensure that all breakers are “OFF”.
A 3 phases motor thermal breaker must be used to protect the wind turbine generator. Thermal current threshold must
be set to 17A.
Connect the three-phases cabling from the wind turbine generator to the breaker, then from the breaker to the U/ V/ W
terminals.
Cabling should be of at least 4mm2core cable.
Connection to remote control switch :
You can connect a normally open or normally close switch to the remote control input.
Set the “remote logic” to NO or NC according to your need.
Input open voltage is +5V, short circuit current is 4mA.tect the wind turbine generator.
Table of contents
Popular Controllers manuals by other brands

Siemens
Siemens OpenAir GDE Series Technical instructions

Fusion
Fusion Aquapower quick start guide

Regulus
Regulus uREG user manual

Honeywell
Honeywell CN05 Series manual

Homematic IP
Homematic IP HmIPW-FALMOT-C12 Installation instructions and operating manual

Kutai electronics
Kutai electronics EA125-8 Operation manual