E+E Elektronik EE072 User manual

BA_EE072 // v2.0 // Modification rights reserved
User Manual
EE072
Humidity and Temperature Probe
with Digital Interface

E+E Elektronik Ges.m.b.H. doesn‘t accept warranty and liability claims neither upon this publication nor in case of
improper treatment of the described products.
The document may contain technical inaccuracies and typographical errors. The content will be revised on a
regular basis. These changes will be implemented in later versions. The described products can be improved and
changed at any time without prior notice.
© Copyright E+E Elektronik Ges.m.b.H. All rights reserved.
EMC note USA (FCC):
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15
of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when
the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio
frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful
interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful
interference in which case the user will be required to correct the interference at his own expense.
EMC note Canada (ICES-003):
CAN ICES-3 (A) / NMB-3 (A)

CONTENT
1 General .................................................................................................................................................4
1.1 Explanation of Symbols.................................................................................................................................4
1.2 Safety Instructions.........................................................................................................................................4
1.2.1 General Safety Instructions..................................................................................................................................4
1.2.2 Intended Use........................................................................................................................................................4
1.2.3 Mounting, Start-up and Operation........................................................................................................................4
1.3 Environmental Aspects..................................................................................................................................5
2 Scope of Supply ..................................................................................................................................5
3 Product Description ............................................................................................................................5
3.1 General..........................................................................................................................................................5
3.2 Dimensions....................................................................................................................................................6
3.3 Electrical Connection.....................................................................................................................................6
3.3.1 Modbus Version ...................................................................................................................................................6
3.3.2 CANopen Version ................................................................................................................................................7
3.4 Specification of the CAN Lines......................................................................................................................7
4 Installation ...........................................................................................................................................7
4.1 Wall and Ceiling Mount..................................................................................................................................7
4.2 Duct Mount ....................................................................................................................................................8
4.3 Recommendations for accurate Humidity and Temperature
Measurement ................................................................................................................................................8
5 Modbus.................................................................................................................................................9
5.1 Modbus Setup ...............................................................................................................................................9
5.2 Modbus Register Map .................................................................................................................................10
5.3 Modbus RTU Example ................................................................................................................................11
6 CANopen ............................................................................................................................................12
6.1 CANopen Setup ..........................................................................................................................................12
6.2 Function overview .......................................................................................................................................12
6.3 Electronic Datasheet (EDS) ........................................................................................................................13
6.4 Layer Setting Services (LSS) ......................................................................................................................13
7 Maintenance and Service .................................................................................................................13
7.1 Cleaning ......................................................................................................................................................13
7.2 Filter Cap Replacement...............................................................................................................................13
7.3 Protection during Site Cleaning Operations ................................................................................................14
7.4 Repairs ........................................................................................................................................................14
7.5 Configuration Interface ................................................................................................................................14
7.6 RH / T Adjustment and Calibration ..............................................................................................................14
7.7 Spare Parts .................................................................................................................................................15
8 Accessories .......................................................................................................................................15
9 Technical Data ...................................................................................................................................16

4User Manual EE072 Humidity and Temperature Probe with Digital Interface
1 General
This user manual serves for ensuring proper handling and optimal functioning of the device. The user
manual shall be read before commissioning the equipment and it shall be provided to all staff involved
in transport, installation, operation, maintenance and repair. The user manual may not be used for the
purposes of competition without the written consent of E+E Elektronik® and may not be forwarded to
third parties. Copies may be made for internal purposes. All information, technical data and diagrams
included in these instructions are based on the information available at the time of writing.
1.1 Explanation of Symbols
This symbol indicates safety information.
It is essential that all safety information is strictly observed. Failure to comply with this information can
lead to personal injuries or damage to property. E+E Elektronik® assumes no liability if this happens.
This symbol indicates instructions.
The instructions shall be observed in order to reach optimal performance of the device.
1.2 Safety Instructions
1.2.1 General Safety Instructions
■ Avoid any unnecessary mechanical stress and inappropriate use.
■ When replacing the filter cap make sure not to touch the sensing elements.
■ The device must be operated with the filter cap on at all times.
■ Installation, electrical connection, maintenance and commissioning shall be performed by qualified
personnel only.
■ Use the EE072 only as intended and observe all technical specifications.
■ Do not use EE072 in explosive atmosphere or for measurement of aggressive gases.
■ Do not apply the nominal voltage to the data lines.
1.2.2 Intended Use
The EE072 is intended for highly accurate humidity (RH) and temperature (T) measurement in
demanding process applications. The measured values and the calculated parameters are availabe on
Modbus RTU or CANopen.
The use of the EE072 in any other way than described in this manual bears a safety risk for people and
the entire measurement installation and is therefore not allowed.
The manufacturer cannot be hold responsible for damages as a result of incorrect handling, installation,
and maintenance of the equipment.
In order to avoid damage to the instrument or health hazards, the measuring equipment must never be
manipulated with tools that are not specifically described in this manual.
The sensor may only be utilized in accordance with the conditions defined in the technical data.
Otherwise, measurement inaccuracies will occur and equipment failures cannot be ruled out.
The steps recommended by the manufacturer for installation, inspections and maintenance work must
be observed and carried out for the safety of the user and for the functionality of the equipment.
Unauthorized product modification leads to loss of all warranty claims. This may be accomplished only
with an explicit permission of E+E Elektronik®!
1.2.3 Mounting, Start-up and Operation
The EE072 humidity and temperature probe has been produced under state of the art manufacturing
conditions, has been thoroughly tested and has left the factory fulfilling all safety criteria. The
manufacturer has taken all precautions to ensure safe operation of the device. The user must ensure

5
User Manual EE072 Humidity and Temperature Probe with Digital Interface
that the device is set up and installed in a manner that does not have a negative effect on its safe
use. The user is responsible for observing all applicable safety guidelines, local and international, with
respect to safe installation and operation on the device. This user manual contains information and
warnings that must be observed by the user in order to ensure safe operation.
■ Mounting, start-up, operation and maintenance of the device may be performed by qualified staff
only. Such staff must be authorized by the plant operator to carry out the mentioned activities.
■ The qualified staff must have read and understood this user manual and must follow the
instructions contained within.
■ All process and electrical connections shall be thoroughly checked by authorized staff before putting
the device into operation.
■ Do not install or start-up a device supposed to be faulty. Make sure that such devices are not
accidentally used by marking them clearly as faulty.
■ A faulty device may only be investigated and possibly repaired by qualified, trained and authorized
staff. If the fault cannot be fixed, the device shall be removed from the process.
■ Service operations other than described in this user manual may only be performed by the
manufacturer.
Disclaimer of Liability
The manufacturer or their delegated representative is only liable in case of intent or gross negligence.
The accountability is limited to the value of the order issued at the time to the manufacturer. The
manufacturer is not liable for damages, originated from disregarding the safety instructions or violating
the instructions of the manual or operating conditions. Consequential damages are excluded from any
liability.
1.3 Environmental Aspects
Products from E+E Elektronik® are developed and manufactured observing of all relevant requirements
with respect to environment protection. Please observe local regulations for the device disposal.
For disposal, the individual components of the device must be separated according to local recycling
regulations. The electronics shall be disposed of correctly as electronics waste.
2 Scope of Supply
■ EE072 – Humidity and Temperature Probe with Digital Interface according to ordering code
■ Inspection certificate according to DIN EN 10204-3.1
■ Quick guide (for Modbus version only)
3 Product Description
3.1 General
The EE072 is a robust probe for relative humidity and temperature measurement. Its IP65 rating and
the E+E proprietary protective sensor coating make it ideal for highest requirements. This is also
underlined by the wide humidity and temperature working ranges of 0...100 %RH and -40...80 °C.
The EE072 is typically implemented in demanding process and climate control applications like in
agriculture, life stock, food, pharma or clean rooms. A wide choice of filter caps allow for versatile
options in challenging industrial applications. Installation is simplified by various mounting options which
are supported by E+E accessories.
The EE072 is available with two different interface versions, either with CANopen/CAN or with Modbus
RTU over RS485. The M12x1 connector links the probe to the digital infrastructure.

6User Manual EE072 Humidity and Temperature Probe with Digital Interface
3.2 Dimensions
L
101.5 (4)
99.5 (3.92)
M12x1
11
(0.43)
Ø12 (0.47)
L = Filter length; refer to data sheet "Accessories"
Fig. 1 Dimensions of EE072 in mm (inch)
5
1.5
20 Ø5
20
1.5
122
Ø105
174
44
94
Fig. 2 Dimensions of optional radiation shield (ordering code HA010502) in mm
3.3 Electrical Connection
The relations of electrical potential between a bus system and an EE072 humidity/temperature sensor
are characterized by the following properties:
■ The bus connection is not electrically isolated from the supply connection
■ The individual EE072 node is not electrically isolated from the supply voltage
■ Each EE072 humidity/temperature sensor can be supplied separately
3.3.1 Modbus RTU Version
Pin number Function Wire colors for accessories:
- Coupling flange HA010705
- Connection cable HA010819/820/821
1Supply voltage brown
2B RS485 (D-) white
3GND blue
4A RS485 (D+) black
front view
M12 device plug
front view
1 2
34
5
front view
1 2
34
Tab. 1 Connection to the EE072 Modbus RTU version

7
User Manual EE072 Humidity and Temperature Probe with Digital Interface
3.3.2 CANopen Version
Pin number Function Wire colors according to ISO 11898:
1CAN_SHLD Not in use
2CAN_V+ brown
3CAN_GND white
4CAN_H green
5CAN_L yellow
front view
M12 device plug
front view
1 2
34
5
front view
1 2
34
Tab. 2 Connection to the EE072 CANopen version, in accordance with CiA-303-1
In order to ensure a stable CANopen communication, the supply voltage must exceed the lower supply
voltage limit of 10 V DC within two seconds after power-on.
The EE072 triggers an alarm message if the supply voltage is outside the supply limits. The lowest
detectable voltage is 9 V and the highest 35 V.
3.4 Specification of the CAN Lines
The cables used for connecting the CAN bus nodes must comply with ISO 11898. Therefore, the lines
must have the following characteristics:
Bus system overall length
Parameter
< 300 m < 1000 m
Cable type LIYCY 2 x 2 x 0.5 mm2
twisted pair with shielding
CYPIMF 2 x 2 x 0.5 mm2
twisted pair with shielding
Line resistance 40Ω/km 40Ω/km
Line capacitance 130 nF/km 60 nF/km
Connection Pair 1 (white / brown): CAN_GND and CAN_V+
Pair 2 (green / yellow): CAN_H and CAN_L
Tab. 3 CAN cable specification
■ Only use cables that have an additional pair of wires for CAN_GND.
■ Trouble-free operation of the CAN bus is only possible with correctly connected CAN_GND.
■ Connectthebusterminationresistors.A120Ωterminatingresistormustbeconnectedateach
physical end of the bus system (main trunk).
4 Installation
4.1 Wall and Ceiling Mount
Best measurement performance is achieved when the entire probe is located inside the environment to
be monitored.
In such a case, the EE072 may be for instance fixed onto a wall with the mounting clip HA010211 (not
included in the scope of supply, see data sheet “Accessories”), or freely hang from the ceiling on the
connection cable.
Fig. 3 Optional wall and ceiling mount (ordering code HA010211)

8User Manual EE072 Humidity and Temperature Probe with Digital Interface
4.2 Duct Mount
The probe also can be installed into a duct using the plastic flange HA010202 or the stainless steel
flange HA010201 (not included in the scope of supply, see data sheet “Accessories”).
Fig. 4 Optional plastic flange (ordering code
HA010202)
Fig. 5 Optional stainless steel flange
(ordering code HA010201)
4.3 Recommendations for accurate Humidity and Temperature
Measurement
■ In case the EE072 probe is not entirely located in the environment to be monitored, large
temperature differences along the probe will lead to temperature gradients. These will have an
influence on the accuracy. Therefore, it is of paramount importance to minimize the temperature
gradients. The biggest part of the probe shall be located in the target environment and the rest shall
be thermally well insulated.
■ For outdoor applications the EE072 shall be equipped with a radiation shield (HA010502) which
provides protection from rain, snow and ice. This also causes a natural ventilation which largely
prevents overheating of the probe in the sun and thus a distortion of the measured values.
■ For highest accuracy of the measured humidity and the calculated parameters (e.g. wet bulb
temperature, dew point and others), the user can set the barometric pressure at the operating point,
using the EE-PCS Product Configuration Software (see „7.5 Configuration Interface“), via Modbus
protocol (see „5.1 Modbus Setup“) or via CANopen protocol. The factory setting is 1013.25 mbar.
■ Best accuracy is achieved with a velocity of min. 0.2 m/s of the air surrounding the probe. Depending
on the installation position, flow direction and flow velocity, the accuracy may decline. The following
table gives a concise overview. Please note that the vertical positioning with the sensing element
upside is the most sensitive one concerning accuracy. Because of possible self heating due to the
sensor electronics, it is crucial to have the indicated air flow velocity.
Flow direction of medium
> 0.2 m/s > 0.2 m/s
Polycarbonate > 0.2 m/s
Stainless steel > 2 m/s > 0.2 m/s
> 0.2 m/s Polycarbonate > 0.2 m/s
Stainless steel > 2 m/s
> 0.2 m/s > 0.2 m/s
Tab. 4 Mounting position, air velocity and accuracy

9
User Manual EE072 Humidity and Temperature Probe with Digital Interface
5 Modbus
5.1 Modbus Setup
Factory settings Selectable values (via EE-PCS)
Baud rate 9600 9600, 19200, 38400, 57600, 76800, 115200
Data bits 8 8
Parity Even None, odd, even
Stop bits 1 1, 2
Slave address 234 1...247
Tab. 5 Modbus default settings
Device address, baud rate, parity and stop bits can be set via:
1. EE-PCS, Product Configuration Software and the Modbus configuration adapter HA011018.
The EE-PCS can be downloaded free of charge from www.epluse.com/configurator
2. Modbus protocol in the register 60001 (0x00) and 60002 (0x01).
See Application Note Modbus AN0103 (available on www.epluse.com/EE072)
The serial number as ASCII-code is located at read register address 30001-30008 (16 bits per address).
The firmware version is located at register address 30009 (bit 15...8 = major release; bit 7...0 = minor
release). The sensor name is located at register address 30010.
Please note: When reading the serial number or the sensor name, it is always necessary to read all 8
registers, even if the desired information requires less.
Please note: For obtaining the correct floating point values, both registers have to be read within
the same reading cycle. The measured value can change between two Modbus requests, therefore
exponent and mantissa may get inconsistent.
Communication settings (INTEGER 16 bit)
Parameter Register number1) [DEC] Protocol address2) [HEX]
Write register: function code 0x06
Slave-ID Modbus address 0001 0x00
Modbus protocol settings3) 0002 0x01
1) Register number starts from 1.
2) Protocol address starts from 0.
3) For Modbus protocol settings see Application Note Modbus AN0103 (available on www.epluse.com/EE072).
INFO (read register)
Parameter Register number1) [DEC] Protocol address2) [HEX]
Read register: function code 0x03 / 0x04
Serial number (as ASCII) 0001 0x00
Firmware version 0009 0x08
Sensor Name 0010 0x09
1) Register number starts from 1.
2) Protocol address starts from 0.
Air pressure
Parameter Register number1) [DEC] Register address2) [HEX]
Read and write register: function code 0x03 / 0x10
Air pressure3) 5001 0x1388
1) Register number starts from 1
2) Register address starts from 0
3) Ambient pressure in mbar, with 2 decimal digits (e.g. 1008.25), (Default value 1013.25 mbar)

10 User Manual EE072 Humidity and Temperature Probe with Digital Interface
5.2 Modbus Register Map
The measured data is saved as a 32 bit floating point values (data type FLOAT) and as 16 bit signed
integer values (data type INTEGER).
FLOAT (read register):
Parameter Unit Register number1) [Dec] Register address2) [HEX]
Read register: function code 0x03 / 0x04
Temperature T
°C 1003 0x3EA
°F 1005 0x3EC
°K 1009 0x3F0
Relative humidity RH, Uw % RH 1021 0x3FC
Water vapour partial pressure e mbar 1101 0x44C
psi 1103 0x44E
Dew point temperature Td
°C 1105 0x450
°F 1107 0x452
°K 1147 0x47A
Wet bulb temperature Tw
°C 1109 0x454
°F 1111 0x456
°K 1145 0x478
Absolute humidity dv g/m³ 1113 0x458
gr/ft³ 1115 0x45A
Mixing ratio r g/kg 1121 0x460
gr/lb 1123 0x462
Specific enthalpy h
kJ/kg 1125 0x464
ft lbf/lb 1127 0x466
BTU/lb 1129 0x468
Frost point temperature Tf
°C 1131 0x46A
°F 1133 0x46C
°K 1149 0x47C
Ice bulb temperature Ti
°C 1237 0x4D4
°F 1239 0x4D6
°K 1241 0x4D8
1) Register number starts from 1
2) Register address starts from 0
INTEGER (read register):
Parameter Unit Scale3) Register number1) [Dec] Register address2) [HEX]
Read register: function code 0x03 / 0x04
Temperature T
°C 100 4002 0xFA1
°F 50 4003 0xFA2
°K 50 4005 0xFA4
Relative humidity RH, Uw % RH 100 4011 0xFAA
Water vapour partial pressure e mbar 10 4051 0xFD2
psi 1000 4052 0xFD3
Dew point temperature Td
°C 100 4053 0xFD4
°F 100 4054 0xFD5
°K 100 4074 0xFE9
Wet bulb temperature Tw
°C 100 4055 0xFD6
°F 100 4056 0xFD7
°K 100 4073 0xFE8
Absolute humidity dv g/m³ 10 4057 0xFD8
gr/ft³ 10 4058 0xFD9
Mixing ratio r g/kg 10 4061 0xFDC
gr/lb 10 4062 0xFDD
Specific enthalpy h
kJ/kg 1 4063 0xFDE
ft lbf/lb 1 4064 0xFDF
BTU/lb 1 4065 0xFE0
Frost point temperature Tf
°C 100 4066 0xFE1
°F 100 4067 0xFE2
°K 100 4075 0xFEA
Ice bulb temperature Ti
°C 100 4119 0x1016
°F 100 4120 0x1017
°K 50 4121 0x1018
1) Register number starts from 1
2) Register address starts from 0
3) Examples: For scale 100, the reading of 2550 means a value of 25.5. For scale 50, the reading of 2550 means a value of 51.

11
User Manual EE072 Humidity and Temperature Probe with Digital Interface
5.3 Modbus RTU Example
Example of MODBUS RTU command for reading the temperature (float value) T = 26,953624 °C
from the register 0x3EA
■ Device EE072; slave ID 234 [0xEA]
Reference document, chapter 6.3: www.modbus.org/docs/Modbus_Application_Protocol_V1_1b.pdf
■ See Application Note Modbus AN0103 (available on www.epluse.com/EE072)
Modbus ID
address
Function
code
Starting
address Hi
Starting
address Lo
No. of
register Hi
No. of
register Lo CRC
Request [Hex]: EA 03 03 EA 00 02 F2 A0
Modbus ID
address
Function
code
Byte
count
Register 1
value Hi
Register 1
value Lo
Register 2
value Hi
Register 2
value Lo CRC
Response Hex]: EA 03 04 A1 06 41 D7 12 CE
Decoding of oating point values:
Floating point values are stored according IEEE754 standard. The byte pairs 1, 2 and 3, 4 are inverted
as follows:
MMMMMMMM MMMMMMMM SEEEEEEE EMMMMMMM
Byte 3 Byte 4 Byte 1 Byte 2
Example:
Response [Hex] Value in
decimal
Byte 1 (Register 2 - Hi) Byte 2 (Register 2 - Lo) Byte 3 (Register 1 - Hi) Byte 4 (Register 1 - Lo)
41 D7 A1 06 26.953624

12 User Manual EE072 Humidity and Temperature Probe with Digital Interface
6 CANopen
6.1 CANopen Setup
Factory settings Selectable parameters Configurable via
Baud rate 125 kBit/s 125 kBit/s, 250 kBit/s, 500 kBit/s, 800
kBit/s, 1MBit/s
EE-PCS or LSS
Node ID 64 1...127 EE-PCS or LSS
TPDO 1 T in [°C], Uw in [%] T, Uw, e, Td, Tw, dv, r, h, Tf, Ti CAN SDO
TPDO 2 e in [mbar],Td in [°C] T, Uw, e, Td, Tw, dv, r, h, Tf, Ti CAN SDO
TPDO 3 r in [g/kg], h in [kJ/kg] T, Uw, e, Td, Tw, dv, r, h, Tf, Ti CAN SDO
TPDO 4 Tf in [°C], Ti in [°C] T, Uw, e, Td, Tw, dv, r, h, Tf, Ti CAN SDO
TPDO data type REAL32 REAL32, INTEGER16 CAN SDO
Abbreviations: TPDO Transceive Process Data Object
EE-PCS E+EProductCongurationSoftware(seechapter7.5CongurationInterface)
LSS Layer Setting Services (see chapter 6.4 Layer Setting Services (LSS))
CAN SDO Service Data Object
Tab. 6 CANopen default settings
Parameter Symbol Condition Units
Temperature T [°C, °F, K]
Relative humidity Uw, RH [%]
Water vapour partial pressure e [mbar, psi]
Dew point temperature Td [°C, °F, K]
Wetbulb temperature Tw Tw 0 C [°C, °F, K]
Water vapour density
(absolute humidity)
dv [g/m³]
Mixing ratio r [g/kg]
Specific enthalpy h [kJ/kg]
Frost point temperature Tf Tf 0 °C [°C, °F, K]
Ice bulb temperature Ti Ti 0 °C [°C, °F, K]
Tab. 7 Selectable parameters
6.2 Function overview
The EE072 humidity/temperature probes have a standardised CANopen interface according to
CiA DS-301 and a device profile according to CiA DSP-404. All measured values and parameters
are accessible via the object directory (OD). The individual configuration can be saved in the internal
permanent memory (EEPROM).
The following CANopen functions are available:
■ Transceive Process Data Objects (TPDO1 - 4) in four possible operating modes:
– individual query via Remote Transmit Request (RTR)
– cyclic transmission by interval time
– event-controlled transmission on measurand change
– synchronized transmission after receipt of a SYNC telegram
■ Service Data Object (standard SDO)
■ Error messages via Emergency Object (EMCY) with support:
– the general error register (Error Register)
– the manufacturer-specific status register (Manufacturer Status)
– the error list (Pre-defined Error Field)
– supply range alarm
■ Monitoring mechanisms Heartbeat and Nodeguarding/Lifeguarding
■ Save and restore function for all parameters (Store and Load Parameter Field)
■ Setting the Node ID and the baud rate via LSS
■ In addition to the CiA DS-301 functionality, there are further manufacturer or profile specific features:
– Setting of pressure compensation parameter (object 2205h- default value 1013.25 mbar)
– Supply voltage monitoring
– Read calibration date (factory and customer)

13
User Manual EE072 Humidity and Temperature Probe with Digital Interface
6.3 Electronic Datasheet (EDS)
An electronic data sheet (EDS) is available for the EE072 CANopen (download free of charge at E+E‘s
EE072 webpage) .
It contains a complete description of the object dictionary and facilitates a convenient integration into a
CANopen engineering software.
6.4 Layer Setting Services (LSS)
In order to use the LSS functionality, LSS data is required which clearly identifies the sensor. This is the
Identity Object (Index 1018h).
Designation Object Sub-Index Value for EE072
Vendor ID 1018h01h000004C8h
Product code 1018h02h0x00h
Revision number 1018h03h0x00h
CANopen serial number 1018h04hdevice specific (LLS – 04h: 0x….)
The sensor specific identifier (LLS – 04h) is printed on each EE072.
Example of sensor labeling including LSS data:
EE072 TT2
CANopen / LSS – 04h: 0x20220503
Supply: 10 - 28 V DC
7 Maintenance and Service
EE072 does not require any special maintenance, nevertheless for high accurate measurements espe-
cially over wide RH and T ranges it is recommended to calibrate the probe every 12 months. If needed,
the enclosure may be cleaned and the device may be re-adjusted as described below.
7.1 Cleaning
Use a damp soft cloth to remove deposits of dust or dirt from the exterior of the probe. Do not use any
solvents or abrasive cleaning agents.
In case of dusty, oily and polluted environment:
■ Use a damp soft cloth to remove deposits of dust or dirt from the exterior of the probe. Do not use
any solvents or abrasive cleaning agents.
■ The filter cap shall be replaced once in a while with an E+E original one (see below).
■ If needed, the sensing element of the humidity probe can be cleaned by the user (see cleaning inst-
ruction - www.epluse.com/cleaning-instructions)
7.2 Filter Cap Replacement
In a dusty or polluted environment it might be necessary to replace the filter cap once in a while. In most
of the cases, a clogged filter shows visible contamination or dirt. Longer response time of the humidity
measurement also indicates a clogged filter cap. In such cases, replace the filter by a new, original one,
see „7.7 Spare Parts“.
Procedure
■ Turn the filter cap counter-clockwise for removing it.
■ Install the new filter cap finger tight by turning it clockwise.
While replacing the filter cap take very good care to not touch or rub the sensing element.

14 User Manual EE072 Humidity and Temperature Probe with Digital Interface
7.3 Protection during Site Cleaning Operations
During site cleaning or sterilization process, if the EE072 remains on the measuring site the sensing
head can be protected with the optional protection cap for 12 mm (0.47") probe (HA010783, see
datasheet “Accessories”).
In case the probe is removed from the site, it is recommended to apply the protection cap for the M12
cable socket (HA010781) and the one for the EE072 M12 plug of (HA010782).
Fig. 6 Protection cap for
Ø12 mm (0.47") probe
(ordering code
HA010783)
Fig. 7 Protection cap M12
female connector
(ordering code
HA010781)
Fig. 8 Protection cap M12
female connector
(ordering code
HA010782)
7.4 Repairs
Repairs may be carried out by the manufacturer only. The attempt of unauthorized repair excludes any
warranty claims.
7.5 Configuration Interface
The EE072 is ready to use and does not require any configuration by the user. The user can change the
factory setup by using the configuration adapter (Modbus: HA011018 / CAN: HA011021) and the EE-
PCS Product Configuration Software.
With the EE-PCS, it is possible to change the digital communication settings and to perform a RH
and T adjustment in the form of an offset or as a 2-point adjustment. For the purpose of pressure
compensation, the barometric air pressure at the operating site may be set.
EE-PCS PRODUCT CONFIGURATION SOFTWARE
1. Download the EE-PCS Product Configuration Software from www.epluse.com/configurator and
install it on the PC.
2. Connect the E+E device to the PC using the appropriate configuration cable.
3. Start the EE-PCS software.
4. Follow the instructions on the EE-PCS opening page for scanning the ports and identifying the
connected device.
5. Click on the desired setup or adjustment mode from the main EE-PCS menu on the left and follow
the online instructions of the EE-PCS.
PC
HA011018/HA011021
7.6 RH / T Adjustment and Calibration
Definition
■ Adjustment
the specimen is brought in line with the reference.
■ Calibration
the specimen is compared with a reference and its deviation from the reference is documented.

15
User Manual EE072 Humidity and Temperature Probe with Digital Interface
Humidity calibration and adjustment
Depending on the application and the requirements of certain industries, there might arise the need for
periodical humidity calibration (comparison with a reference) or adjustment (bringing the device in line
with a reference).
Calibration and adjustment at E+E Elektronik
Calibration and/or adjustment can be performed in the E+E Elektronik calibration laboratory. For
information on the E+E capabilities in ISO or accredited calibration please see www.eplusecal.com.
Calibration and adjustment by the user
Depending on the level of accuracy required, the humidity reference can be:
■ Humidity calibrator (e.g. Humor 20), please see www.epluse.com/humor20.
■ Handheld device (e.g. Omniport 30), please see www.epluse.com/omniport30.
■ Humidity standards (e.g. Humidity Calibration Kit), please see www.epluse.com/EE072.
7.7 Spare Parts
Description Order code
Filter caps for probes with Ø 12 mm Please refer to the
datasheet “Accessories“
8 Accessories
General Order code
E+E Product Configuration Software (Download: www.epluse.com/configurator) EE-PCS
Protection cap for the M12 cable socket HA010781
Protection cap for the M12 plug of EE072 HA010782
Protection cap for 12 mm probe HA010783
Stainless steel mounting flange HA010201
Plastic mounting flange HA010202
T-coupler M12 - M12 HA030204
Wall mounting clip HA010211
Radiation shield for probes with Ø12mm HA010502
Drip water protection HA010503
Modbus Order code
M12 cable connector for self assembly, 4 pole HA010707
Modbus configuration adapter HA011018
Connection cable, 5 pole, M12x1 socket - free ends, PUR insulation
1.5 m (4.9 ft)
5 m (16.4 ft)
10 m (32.8 ft)
HA010819
HA010820
HA010821
CAN Order code
M12 cable connector for self assembly, 5 pole HA010708
CAN configuration adapter HA011021

16 User Manual EE072 Humidity and Temperature Probe with Digital Interface
9 Technical Data
Measurands
Relative humidity
Accuracy1) (incl. hysteresis, non-linearity and repeatability)
-15…40 °C (5…104 °F) ±(1.3+0.3%*mv)%RH forRH≤90%
± 2.3 % for RH >90 %
-40…80 °C (-40…176 °F) ± (1.5 + 1.5 % *mv) %RH mv = measured value
Response time < 15 s with stainless steel grid filter at 20 °C (68 °F) / t90
Resolution 0.01 %RH
Temperature
Accuracy1)
0.48
0.6
0.4
0.3
0.2
0.1
standard
high
Resolution 0.01 °C
General
Sensing element E+E HCT01 with E+E proprietary coating
Measuring interval 1 s
Supply 10 - 28 V DC
Current consumption, typ. 3 mA (RS485, without termination resistor)
8 mA (CAN)
Enclosure Polycarbonate RAL 7035 / Stainless steel 1.4404 / AISI 316
Protection class2) IP65
Electromagnetic compatibility EN 61326-1:2013 EN 61326-2-3:2013
Industrial Environment
Working range -40…80 °C (-40...176 °F) / 0…100 % RH
Storage conditions -40…80 °C (-40...176 °F) / 0…90 % RH, non-condensing
Configuration and adjustment EE-PCS (Product Configuration Software, free download) and
configuration adapter
Digital Communication
RS485
Protocol Modbus RTU
Connector M12x1, 4 poles
Default settings Baud rate 96003), parity even, 1 stop bit, slave ID 234
CAN
Protocol / Profile CANopen / device profile CiA 404
Connector M12x1, 5 poles, pin assignment according to CiA 303-1
Default settings Baud rate 125 kBit/s4), node ID 64
1) Traceable to international standards, administrated by NIST, PTB, BEV,... The accuracy statement includes the uncertainty of the factory calibration with an enhancement factor
k=2 (2-times standard deviation). The accuracy was calculated in accordance with EA-4/02 and with regard to GUM (Guide to the Expression of Uncertainty in Measurement).
For Modbus, the accuracy is defined at a 12 V DC supply, baud rate 9600, without termination resistor, a polling interval of >= 1 s and a flow velocity of > 0.2 m/s.
For CANopen, the accuracy is defined at a flow velocity of > 0.2 m/s.
2) The IP65 rating applies when plugged into an appropiate M12x1 female connector.
3) Supported baud rates: 9 600, 19 200, 38 400, 57 600, 76 800 and 115 200.
For more details about communication setting see User Manual and Modbus Application Note at www.epluse.com/ee072
4) Supported baud rates: 125 kBit/s, 250 kBit/s, 500 kBit/s, 800 kBit/s, 1 MBit/s.
For further information on the configuration see software instruction manual and the EDS file (Electronic Data Sheet).

HEADQUARTERS
E+E Elektronik Ges.m.b.H.
Langwiesen 7
4209 Engerwitzdorf
Austria
Tel.: +43 7235 605-0
E-mail: [email protected]
Web: www.epluse.com
SUBSIDIARIES
E+E Elektronik China
18F, Kaidi Financial Building,
No.1088 XiangYin Road
200433 Shanghai
Tel.: +86 21 6117 6129
E-mail: [email protected]
E+E Elektronik France
Le Norly III, 136 chemin du Moulin
69130 Ecully
Tel.: +33 4 74 72 35 82
E-mail: [email protected]
E+E Elektronik Germany
Schöne Aussicht 8 C
61348 Bad Homburg
Tel.: +49 6172 13881-0
E-mail: [email protected]
E+E Elektronik Italy
Via Alghero 17/19
20128 Milano (MI)
Tel.: +39 02 2707 86 36
E-mail: [email protected]
E+E Elektronik Korea
Suite 2001, Heungdeok IT
Valley Towerdong, 13,
Heungdeok 1-ro, Giheung-gu
16954 Yongin-si, Gyeonggi-do
Tel.: +82 31 732 6050
E-mail: [email protected]
E+E Elektronik USA
333 East State Parkway
Schaumburg, IL 60173
Tel.: +1 847 490 0520
E-mail: [email protected]
Other manuals for EE072
1
Table of contents