Quick Guide CDS201 | HTS201 | TES201
Modbus Setup
Factory settings User selectable values (via PCS10)
Baud rate acc. to ordering code 9 600, 19 200, 38 400, 57 600, 76 800, 115 200
Data bits 8 8
Parity Even None, odd, even
Stop bits 11, 2
Modbus address 45 1...247
Modbus Protocol
The recommended settings for multiple devices in a Modbus RTU network are 9600, 8, Even, 1. The room sensor represents 1 unit
load in a Modbus network.
Device address, baud rate, parity and stop bits can be set via:
▪PCS10 Product Configuration Software and the the appropriate configuration cable HA011018.
The PCS10 can be downloaded free of charge from www.epluse.com/pcs10.
▪Modbus protocol in the register 1 (0x00) and 2 (0x01).
See Application Note Modbus AN0103 (available at the according product website).
The serial number in ASCII format is located in read-only register 1 - 8 (16 bits per register). The firmware version is located in
register 9 (bit 15...8 = major release; bit 7...0 = minor release). The sensor name is located in registers 10 - 17 (16 bits per register).
Communication settings (INT16)
Parameter Register number1) [Dec] Register address2) [Hex]
Write register: function code 0x06
Modbus address 10x00
Modbus protocol settings3) 20x01
Device information (INT16)
Parameter Register number1) [Dec] Register address2) [Hex]
Read register: function code 0x03 / 0x04
Serial number (as ASCII) 1 0x00
Firmware version 9 0x08
Sensor name 10 0x09
Device status (bit decoded) 602 0x259
1) Register number starts from 1.
2) Protocol address starts from 0.
3) For Modbus protocol settings see Application Note Modbus AN0103 (available at the according product website).
Modbus Register Map
FLOAT32 INT16
Parameter Unit Register1) Address2) Register1) Address2) Scale CDS201 HTS201 TES201
Read register: function code 0x03 / 0x04
Temperature
°C 1003 0x3EA 4002 0xFA1 100
°F 1005 0x3EC 4003 0xFA2 50
°K 1009 0x3F0 4005 0xFA4 50
Relative humidity RH, Uw %RH 1021 0x3FC 4011 0xFAA 100
CO2averaged ppm 1061 0x424 4031 0xFBE 1
CO2non-averaged ppm 1063 0x426 4032 0xFBF 1
Dew point temperature Td
°C 1105 0x450 4053 0xFD4 100
°F 1107 0x452 4054 0xFD5 100
°K 1147 0x47A 4074 0xFE9 100
1) Register number starts from 1 and is expressed as decimal number.
2) Protocol address starts from 0 and is expressed as hexadecimal number.
It is possible to map measured value/status registers arbitrarily in a block with up to 20 registers provided for this purpose
(registers 3001...3020). Please find detailed information in the manual at the according product website.
QG_Roomsensors | Version v1.0 | 04-2023 | Modification rights reserved | 195234