Before to start using the UPS please read carefully this manual, so to ensure the best usage and the maximum life
duration of the machine. The main features of this Uninterruptible Power Supply (UPS) are listed below:
Microprocessor control that guarantees high reliability
Built-in enhanced boost & buck AVR
DC start function
Auto restart during AC recovery
Modem and phoneline surge protection
Built-in USB communication port
Compact size, light weight
This manual contains important safety instructions. Please read and follow all instructions carefully during installation
and operation of the unit. Read this manual thoroughly before attempting to unpack, install, or operate your UPS.
CAUTION! To prevent the risk of fire or electric shock, install in a temperature and humidity controlled indoor area free
of conductive contaminants. (See the specifications for the acceptable temperature and humidity range.)
CAUTION! To reduce the risk of overheating the UPS, do not cover the UPS cooling vents and avoid exposing the unit
to direct sunlight or installing the unit near heat emitting appliances such as space heaters or furnaces.
CAUTION! Do not attach non-computer-related items, such as medical equipment, life-support equipment, microwave
ovens, or vacuum cleaners to UPS.
CAUTION! Do not plug laser printers, scanners or aquariums into the UPS outlets because of their high start-up current.
CAUTION! This UPS could not be suitable for devices with Active PFC. Check preventively your power supply typology.
CAUTION! Do not allow liquids or any foreign object to enter the UPS. Do not place beverages or any other liquid-
containing vessels on or near the unit.
CAUTION! With the installation of the UPS, it should be prevented that the sum of (UPS and) the connected (load)
leakage current exceeds 3.5mA
CAUTION! In the event of an emergency, press the OFF button and disconnect the power cord from the AC power
supply to properly disable the UPS.
CAUTION! In the event of severe and/or prolonged atmospheric events (storms, lightning, etc..) disconnect the UPS
from the mains to avoid any damage risk to connected equipment.
CAUTION! The socket-outlet shall be installed near the equipment and easily accessible.
CAUTION! Internal battery voltage is 12V DC. Sealed, lead-acid, 6 cells battery
CAUTION! Do not dispose of batteries in a fire as they may explode
CAUTION! A battery can present a risk of electrical shock and high short circuit current. The following precautions
should be observed when working on batteries:
1) Remove watches, rings, or other metal objects from the hands.
2) Use tools with insulated handles.
3) Wear rubber gloves and boots.
4) Do not lay tools or metal parts on top of batteries.
5) Disconnect charging source prior to connecting or disconnecting battery terminal.
CAUTION! When replacing batteries, replace with the same number of the sealed lead-acid batteries.
CAUTION! Servicing of batteries should be performed by personnel knowledgeable of batteries and the required
precautions. Keep unauthorized personnel away from batteries.
CAUTION! Unplug the UPS prior to cleaning and do not use liquid or spray detergent.
IMPORTANT SAFETY INSTRUCTIONS
INTRODUCTION
CAUTION! This UPS utilizes voltages that may be hazardous. Do not attempt to disassemble the unit. The unit contains
no user replaceable parts. Only authorized service personnel may perform repairs.
CAUTION! Do not attach a power strip or surge suppressor with >1,5m wire to the UPS
CAUTION! Do not stick fingers into sockets.
CAUTION! The UPS cannot be transported by plane because it contains lead acid batteries.
Please follow the instructions to correctly position your UPS:
1. The UPS must be placed on a horizontal surface.
2. This UPS is projected for indoor use.
3. The UPS must not be exposed to direct sunlight or any heat source.
4. The air temperature must be between 0°C and 40°C (25°C is the ideal temperature).
5. Ambient humidity must be less than 90%.
6. The UPS must not be placed on dusty environments.
7. The UPS must be placed at least 15 cm. far from walls to ensure enough ventilation.
8. Do not obstruct or pour any liquid on ventilation holes.
9. Do not cover the UPS with any object.
10. Keep away liquids, flammable gases or corrosive substances.
INSTALLING YOUR UPS SYSTEM
UNPACKING
The box should contain the following: UPS Unit x1, USB cable x1.
HARDWARE INSTALLATION GUIDE
1. Your new UPS may be used immediately upon receipt. However, recharging the battery for at least 8 hours is
recommended to ensure that the battery's maximum charge capacity is achieved. Charge loss may occur during
shipping and storage. To recharge the battery, simply leave the unit plugged into an AC outlet. The unit will charge
in both the on and off position.
2. With the UPS unit off and unplugged, connect the computer, monitor, and any externally powered data storage
device (Zip drive, Jazz drive, Tape drive, etc.) into the battery power supplied outlets. DO NOT plug a laser printer,
copier, space heater, vacuum, paper shredder or other large electrical device into the battery power supplied outlets.
The power demands of these devices will overload and possibly damage the unit.
3. Plug the UPS into a 2 pole, 3 wire grounded receptacle (wall outlet). Make sure the wall branch outlet is protected
by a fuse or circuit breaker and does not service equipment with large electrical demands (e.g. air conditioner,
refrigerator, copier, etc). Avoid using extension cords.
4. Press the power switch to turn the unit on. The power on indicator light will illuminate and the unit will "beep".
5. If an overload is detected, an audible alarm will sound and the unit will emit one long beep. To correct this, turn the
UPS off and unplug at least one piece of equipment from the battery power supplied outlets. Wait 10 seconds. Make
sure the circuit breaker is depressed (only for Neon 1000) and then turn the UPS on.
6. To maintain optimal battery charge, leave the UPS plugged into an AC outlet at all times, in compliance with all
safety conditions.
7. To store your UPS for an extended period, cover it and store with the battery fully charged. Recharge the battery
every three months to ensure battery life.
650/850 VA
1000 VA
1. On/Off Button
To turn ON/OFF the UPS keep pressed the button for 2 seconds. Release the button after you hear an acoustic
signal and a “click”. A white light around the button will confirm you that the UPS is switched ON.
Alarm setting: The audible alarm can be turned OFF or ON by quickly pressing the POWER button twice. The
default setting is for the Alarm On. To turn the Alarm Off, quickly press the power button twice. You will hear two
short beeps when the Alarm is turned off. To turn the Alarm back on, quickly press the power button twice. You will
hear a single short beep when the Alarm is turned on.
2. Led Indicators
This LED is illuminated when the UPS is working.
3. Input Power Cord
Connect to utility power.
4.AC outlet
The UPS provides outlets for connected equipment to insure temporary uninterrupted operation during a power failure
and against surges and spikes.
5. Input Circuit Breaker
The circuit breaker provides overload protection.
6. USB COMM. Port
This port allows connection to the USB port on the computer, so to get access to remote monitoring and shutdown
operations through the UPS management software.
7. RJ45/11 Communication Protection Ports
Provide surge protection for any standard modem, fax, telephone line, or network cable. Using ports brings a 100
Mb/s speed limitation.
POSITIONING
INSTALLING YOUR UPS SYSTEM
3
4
7
6
4
3
5
6
7
1
2
1
2
BASIC FUNCTIONALITIES
The management software provides
a user-friendly interface for your
power systems. The graphic
interface is intuitive and displays
essential power information at a
glance.
Installation procedure:
1. Download Power Master software
from the internet website:
www.justepyc.com
2. Double-click the file and follow the
installation steps.
3. To access Power Master double-click on the software icon, or enter http://localhost:3052 adress on your web browser.
Before starting any cleaning operation, be sure that:
1. The AC Input Voltage for the UPS has been removed.
2. The UPS is OFF.
Use a cloth moisteened only with water to externally clean the UPS. Before restarting the UPS be sure it is completely
dry.
If the UPS works in an environmental unusually dusty or dirty, remove the dirty from the ventilation holes
If any liquid gets inside the UPS, do not start the unit and contact Technical Service immediately.
LED Alarm Condition
On Off Normal
Flash Beep 1 time In Every 30 Seconds Utility Failure - The UPS is providing battery power to outlets.
Flash Beep 1 time In Every 2 Seconds Utility Failure - The UPS is providing battery power. The rapid bee ps indicate the
battery will run out of power shortly.
Flash Beep 1 time In Every 0.5 Second Overload - Occurs when connected equipment exceeds the rating of the unit.
Turn the UPS off and unplug at least one piece of equipment from the UPS.
Model
650VA
850VA
1000VA
Capacity (VA/W) 650/360 850/480 1000/600
Input
Nominal Voltage
230VAC
NominalFrequency 50/60Hz
Output
On Battery Output Voltage 220–240VAC
On Battery Output Frequency 50 Hz+/-1%
Overload Protection Breaker / Fuse
Physical
Dimensions WxHxD (mm) 84x159x252 100x 189x325
Weight 3.8kg
4.2kg 6.9kg
Battery
Sealed Maintenance Free
Lead Acid Battery 1x 12V/5Ah 1x 12V/5.6Ah 2x 12V/5Ah
Typical Recharge Time 8 Hours
Warning Diagnostics
Indicators Power On/ Using Battery
Audible Alarms On Battery, Low Battery, Overload, Fault
Environmental
Operating Temperature 0°C to 40°C
Operating Relative Humidity 0 to 90%
Management
Auto-Charger Yes
Auto-Restart Yes
USB COMM.Port Yes
RJ45/11Communication
Protection Ports
Yes
Problem Possible Cause Solution
The UPS does not perform
expected runtime.
Batteries are not fully charged. Recharge the battery by leaving the UPS plugged in.
Battery is slightly worn out. Contact Technical Support for battery replacing.
The UPS will not turn on.
The unit is not connected to an
AC outlet.
The unit must be connected to a 220-240V outlet.
The battery is worn out. Contact Technical Support for battery replacing.
Mechanical problem. Contact Technical Support.
Outlets do not provide
power to equipment
Fuse is blown or breaker is
tripped due to overload.
Turn the UPS off and unplug at least one piece connected equipment.
Unplug the power cord of the UPS then replace the blown fuse with a
spare one (not included) or press the circuit breaker knob . Connect
power cord then turn the UPS on. Make sure that your spare fuse
meets the specification.
Batteries are discharged Allow the unit to recharge for at least 4 hours.
Power Guide Management
Software is inactive
The USB/serial cable is not
connected
Connect the USB/serial cable to the UPS unit and an open USB/serial port on
the back of the computer. You must use the cable that came with the unit.
The UPS is not providing battery
power
Shutdown your computer and turn the UPS off. Wait 10 seconds and turn the
UPS back on. This should reset the unit
DEFINITIONS FOR ILLUMINATED LED INDICATORS
TECHNICAL SPECIFICATIONS
MANAGEMENT SOFTWARE DOWNLOAD
MAINTENANCE
TROUBLE SHOOTING
If the UPS has been damaged during delivery, please report it to the transporter.
If the UPS requires repairs check the trouble shooting table.
If the problem persists contact our technical support at www.justepyc.com
Opening, repairing, or replacing parts inside the UPS must always be carried out by specialized technical personnel
only, otherwise warranty has to be considered forfeited.
The standard warranty for Epyc UPS’s is 24 months from the date of purchase.
Epyc’s standard procedure is to repair the UPS, or to replace the original unit with a factory reconditioned unit.
The warranty period is 12 months from the date of purchase for all parts subject to wear and tear (such as batteries
and fuses).
Please visit www.justepyc.com for further details about warranty conditions.
Epyc's packagings are made by recyclable materials, in compliance with company environmental policy.
For proper disposal please separate the different packaging materials as listed on the table below.
Then dispose all materials according to your Country specific regulations.
Disposal
The UPS contains circuit boards and batteries, that are considered toxic waste and dangerous.
At the end of its life the UPS must be disposed in compliance to WEEE current regolations (Waste of Electric and
Electronic Equipment). Check www.justepyc.com for more details.
Proper disposal helps to protect the environment.
K01-C000505-00 NE04
.
Component Material
Box Cardboard
Angular packaging Expandend polystyrene
Protective bags Polyethylene
All rights reserved. Reproduction without permission is prohibited.
ENVIRONMENTAL PROTECTION
WARRANTY
SUPPORT

Other EPYC UPS manuals

EPYC Quantum 1500 User manual

EPYC

EPYC Quantum 1500 User manual

EPYC ION 600 User manual

EPYC

EPYC ION 600 User manual

EPYC NYTRO 1500 VA User manual

EPYC

EPYC NYTRO 1500 VA User manual

Popular UPS manuals by other brands

Vertiv Liebert NX 225 kVA installation manual

Vertiv

Vertiv Liebert NX 225 kVA installation manual

Legacy Legend SB825 user manual

Legacy

Legacy Legend SB825 user manual

SynQor UPS-1250-S-1U Operator's guide

SynQor

SynQor UPS-1250-S-1U Operator's guide

sinercom LION100K user manual

sinercom

sinercom LION100K user manual

AEC IST6 user manual

AEC

AEC IST6 user manual

DSPM Power Lynx 1 Technical specifications

DSPM

DSPM Power Lynx 1 Technical specifications

INFOSEC UPS SYSTEM ModT user manual

INFOSEC UPS SYSTEM

INFOSEC UPS SYSTEM ModT user manual

Powerware 9355 Technical specifications

Powerware

Powerware 9355 Technical specifications

Avaya 4500 VA Installation and operator's manual

Avaya

Avaya 4500 VA Installation and operator's manual

ICA CS Series user manual

ICA

ICA CS Series user manual

Atlantis A03-PDU1000-RC manual

Atlantis

Atlantis A03-PDU1000-RC manual

Elektro-Automatik PSI Rack 24U installation guide

Elektro-Automatik

Elektro-Automatik PSI Rack 24U installation guide

CyberPower BR650ELCD-UK user manual

CyberPower

CyberPower BR650ELCD-UK user manual

Eaton 5P 1500 RT user manual

Eaton

Eaton 5P 1500 RT user manual

INFOSEC XP PRO 1600 VA user guide

INFOSEC

INFOSEC XP PRO 1600 VA user guide

NEC 500 UPS user manual

NEC

NEC 500 UPS user manual

Uninterruptible Power Supplies PowerWAVE 9000 DPA Installation and operating guide

Uninterruptible Power Supplies

Uninterruptible Power Supplies PowerWAVE 9000 DPA Installation and operating guide

WÄRTSILÄ JOVYSTAR-DELTA operating manual

WÄRTSILÄ

WÄRTSILÄ JOVYSTAR-DELTA operating manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.