ERMCO 11-16-21 User manual

1
INSTRUCTION
MANUAL #105
THREE PHASE POLE MOUNTED DISTRIBUTION TRANSFORMER
ERMCO | 2225 Industrial Road | Dyersburg, TN 38024 | (800)238‐5587
INTRODUCTION
This instrucon manual provides general informaon for the
installaon, operaon, and maintenance of ERMCO three‐phase, pole
mounted transformers. These transformers are to be applied and used
per the “usual service condions” describes in IEEE C57.12.00 (General
Requirements for Liquid‐Immersed Distribuon, Power and Regulaon
Transformers).
RECEIVING AND INSPECTION
ERMCO pole transformers are shipped filled with insulang
transformer oil. Immediately upon receipt, and before being put in
service, transformers should be inspected for any external damage or
loose parts caused by shipping and handling. Damage presumed to
have occurred during shipment should be noted, and your ERMCO
sales representave contacted.
Extreme care is taken at the factory in the processing and sealing of
the transformer to insure that it is clean and dry, and of adequate
dielectric strength. Normally, therefore, it is not recommended that
the transformer seals be broken for internal inspecon. If it is decided,
nevertheless, that the transformer be opened, adequate precauons
should be taken as outlined elsewhere in these instrucons.
HANDLING AND INSTALLATION
Transformers should be lied by the liing lugs only. The transformer
bushings should not be used for liing or moving the transformer into
posion. The transformer should be kept upright at all mes and not
pped over on its side for any reason. This will prevent air bubbles
from entering the coil which could degrade the dielectric strength.
Support lugs for direct pole mounng are provided in accordance with
IEEE standards. Hangers and kickers for cross arm mounng is to be
provided by the user. When installed, transformers should be
protected from dangerous overloads, over voltages and lightning by
suitable, approved devices.
OIL
Transformers are thoroughly dried at the factory and filled with
ERMCO inhibited mineral oil having a minimum dielectric strength of
30 kV at 60 Hz when tested per ASTM D‐877. ERMCO inhibited mineral
oil contains less than 1 ppm of PCB's at me of manufacture. The
transformer should never be energized unless it is filled with oil.
If it should be found necessary to add to or replace the oil in the
transformer, only clean dry oil having the minimum dielectric strength
of 30 kV and less than 1 ppm PCB's should be used. Before opening
the transformer, sufficient me should be allowed for the transformer
to come to temperature equilibrium with the air in the room to
eliminate the possibility of moisture condensaon from the air.
A recommended procedure for opening the transformer is to first
bring the interior of the transformer to atmospheric pressure by
venng the automac pressure relief valve furnished on all ERMCO
transformers. The cover may then be removed. Natural rubber hose
should not be used in the transfer of oil. The correct oil level at 25°C is
marked on the inside of the tank.
Care should be taken to re‐seal the transformer so that moisture is
permanently excluded from the interior. A pressure test using dry air
or nitrogen, may conveniently be made through the pressure‐vacuum
fing, aer removing the pressure relief valve, to be sure all seals are
ght. Pressurize the transformer to 5 psig and hold for 30 minutes. A
drop in pressure during this me would indicate the transformer is not
properly sealed and the tank and fings should be checked and the
leak repaired. Finally, the pressure relief valve should be installed and
carefully ghtened.
CONNECTIONS
Refer to the transformer nameplate for the kVA rang and the
permissible connecons. No connecons other than those shown on
the nameplate should be made; and none of the connecons should
be changed while voltage is applied to the transformer. Provision is
made for grounding the tank by means of a tapped pad or ground
connector.
OVERLOAD AND OVERVOLTAGE PROTECTION
Transformer protecon against overloads and over voltages may be
obtained by suitable devices applied in the field to convenonal
transformers, or by use of protected transformers (ERMCO CSP or CP
types) as supplied from the factory.
1. Fuses: High voltage fused cutouts are recommended for
protecon of convenonal transformers against overloads and to
protect the line against outages. On ERMCO CSP and CP
transformers, a fusible protecve link, mounted inside the tank,
is provided in series with each HV terminal. In case of internal
failure of the transformer, the protecve link disconnects the
transformer from the line without affecng line fuses or breakers.
When the available fault current exceeds the maximum
interrupng rang of the protecve link, a current liming fuse
should be used in series with the protecve link.

2
THREE PHASE POLE MOUNTED DISTRIBUTION TRANSFORMER INSTRUCTION
MANUAL #105
2. Lightning Arresters: Convenonal transformers should be
protected by properly rated lightning arresters. Ground
connecons on the arresters should be made before connecon
to the high voltage line is made.
CSP transformers are lightning protected by gapped or direct
connected lightning arresters bolted to mounng pads welded to
the tank wall. Gapped arresters have an adjustable electrode on
the top terminal of the arrester to obtain the proper gap seng
to the bushing electrode.
Before the transformer is put into service, the gap type arrester
electrode should be checked for proper gap alignment and
spacing. Adjustments should be made as necessary.
3. Secondary Breakers: ERMCO CSP and CP transformers are
protected against secondary overloads and short circuits by an
internally mounted circuit breaker. The funcon of the breaker is
to open the low voltage circuit and protect the transformer from
faults or severe overloads.
The breaker operang mechanism is designed to be operated by
a lineman's hot sck. Transformers are shipped with the circuit
breakers closed.
To open the low voltage manually, move the handle fully
counterclockwise so that the pointer moves from the "C" (closed)
to "O" (open), at which point the circuit is open. Verify that the
circuit breaker is latched in the "open" posion. To ensure the
discharge of the stac charge which is somemes present in the
low voltage winding due to capacitance, it is recommended that
the low voltage be grounded aer opening the circuit breaker
unl aer the high voltage is disconnected.
To close the breaker, rotate the handle fully counterclockwise to
"R" (reset), which engages the latch mechanism, and then
clockwise to "C" (closed). If a fault exists or an excessive load
exists at the me the breaker is closed, the breaker will reopen
even though the handle is held in the "C" (closed) posion.
Some breakers are provided with a red signal light which gives
warning that the load has reached a value near the tripping point
of the breaker. The signal light remains lighted unl reset (turned
off) by means of the breaker operang handle. Transformers
should not be operated under load condions that will cause the
red light to appear frequently, since it indicates an overload on
the transformer. When such a condion exists, it is
recommended that a larger transformer be substuted to avoid
impairing the life of the smaller unit.
To reset the signal light without disconnecng the load, rotate
the handle to "L" (light), and then return to "C" (closed). If the
light fails to go out, the transformer is sll overheated. To check
the signal light bulb when the transformer is in service, rotate the
handle to "L" (light). The light should turn on. If it does not, the
bulb should be replaced.
Some circuit breakers are equipped with an emergency overload
device which can be used to restore service following a circuit
breaker operaon due to overload. The emergency overload
lever is located immediately above the breaker operang handle.
With the emergency lever in the normal posion, the breaker will
trip at its normal seng as calibrated at the factory. Moving the
lever in a clockwise direcon increases the seng so a higher
temperature is required to trip the breaker. The emergency
seng may be adjusted to an intermediate or extreme value.
This emergency seng provides extra load capacity and sll
permits manual breaker operaon, and also retains short circuit
protecon of the transformer. It is important that the emergency
seng be used only when, and as long as, absolutely necessary
because its use will result in a reducon of transformer life.
A meter seal is provided on the emergency lever to prevent
tampering. It is recommended that a new seal be applied to the
lever when it is returned to the normal posion aer emergency
operaon.
The breaker is a thermal and short circuit protecve device for
the transformer. It is not recommended that the breaker be used
for roune disconnect operaons.
GASKETS
Cover and bushing gaskets are all made of Buna‐N Nitrile rubber.
Gaskets may be reused if not damaged. Round covers must seat
evenly on the gaskets so that pressure is distributed evenly. The cover
must be ghtened firmly to insure an effecve seal.
DUAL VOLTAGE AND TAPS
ERMCO transformers rated for more than one primary voltage are
equipped with a dual voltage switch or tap changer. These switches
are externally operated, but should never be operated while the
transformer is energized. When switching from one voltage to
another, make sure the switch is in the proper posion before re‐
energizing the transformer. Aer turning the switch, ghten the
locking device to minimize the possibility of unintenonal
movement.
STORAGE
Transformers should be stored filled with oil and in a clean dry place,
if possible where there will be no extreme temperature changes.
Before the transformer is put in service, it should be checked in the
same manner as when received.
ERMCO | 2225 Industrial Road | Dyersburg, TN 38024 | (800)238‐5587

3
THREE PHASE POLE MOUNTED DISTRIBUTION TRANSFORMER INSTRUCTION
MANUAL #105
MAINTENANCE
A periodic visual inspecon of the transformer is recommended. At
such mes, the general condion of the following should be noted:
1. High voltage bushings
2. Low voltage bushings
3. Arresters (if provided)
4. Evidence of oil leakage
5. Ground connecons
6. Accessories
7. Safety labels.
Where tanks show evidence of rusng or deterioraon of the finish,
they may be cleaned and then retouched with paint. It is necessary to
remove all loose paint and rust by wire brushing, scraping, or sanding,
and clean with a good solvent. Apply an acrylic lacquer, alkyd enamel,
two part urethane or silicone alkyd primer, allow to dry, and then
apply a color matched compable top coat and allow to dry.
If metal is rusted to the point of being weak such that the tank
integrity can be compromised, repair or replace the part rather than
painng it.
REPLACEMENT PARTS
Replacement parts are available from ERMCO. When ordering parts,
give a complete descripon of the part. Also, give the kVA, voltage,
and serial number of the transformer, all of which may be found on
the nameplate.
ADDITIONAL INFORMATION
Complete informaon on details of construcon, installaon,
operaon and maintenance can be obtained from the ERMCO factory
or your nearest ERMCO Sales office.
ERMCO | 2225 Industrial Road | Dyersburg, TN 38024 | (800)238‐5587