User Guide
1-Wire Multisensor Pro for
Temperature and Air Humidity
professional temperature and humidity sensor
for private, schools,
public buildings and companies
precise temperature and humidity sensor with
12Bit resolution
universal on-wall mounting
stylish and high quality sensor housing
easy voltage supply (5VDC)
Application:
Heating control (control of individual rooms)
Control sensor for ventilation system
Monitoring of living areas for risks of mould
.
Note
Before you start assembling the device and put the product into operation, read this operating
manual carefully to the end, especially the section on safety instructions. .

All rights reserved. Reproduction as well as electronic duplication of this user guide, complete or in part, requires the written consent of
ESERA GmbH. Errors and technical modification subject to change. ESERA GmbH 2021
www.esera.de 11150 V3.0 R1.0 Manual Page 2 of 7
1 Product description
With the ESERA 1-Wire Multisensor Pro you have acquired a professional and highly accurate Multisensor.
Due to the new technology of the ESERA 1-Wire Pro sensors, the accuracy of humidity measurements is on
average 200 –300 % higher compared to most standard sensors on the market.
Due to the use of highly integrated sensors with 12-bit resolution, the 1-Wire Multisensor delivers very
accurate values for temperature and relative humidity. In addition, the evaluation of the delivered measured
values is enormously simplified.
The 1-Wire Multisensor Pro enables easy climate monitoring of all rooms and buildings.
The 1-Wire Multisensor Pro is installed in a stylish wall-mounted housing and fits perfectly in modern living
and business areas.
Due to the wide ventilation openings, the 1-Wire Multisensor Pro detects climatic conditions in rooms and
buildings very exactly and quickly. For all types of radiator and heating control, an accurate temperature
sensor, as installed in this Multisensor, is an important component.
In combination with 1-Wire ESERA switching modules / binary outputs, a very effective and energy-saving
heating control (individual room control) is possible.
The 1-Wire Multisensor Pro is intended for use in normal living spaces. For outdoor use and in damp rooms, such
as saunas or steam baths, a matching sensor is available on the ESERA website.
Calibration of the sensors is not necessary. The 1-Wire Multisensor Pro can be put into operation immediately
without any waiting time.
The electrical connection to the 1-Wire bus system of the 1-Wire Multisensor Pro is carried out with screwless
push-in terminals and can be operated in standard mode, 3 cables for ground, data and 5V.
Each 1-Wire Multisensor Pro has an individual serial number.
2 Auto-E-Connect® Support
With the launch of the ECO Controller, the ESERA Auto-E-Connect® 1-Wire Plug
and Play system for the 1-Wire Bus is now introduced and supported.
This now enables fully automatic configurations of 1-Wire devices (sensors and
actuators) on the 1-Wire Bus. It is optimized for commercial and industrial applications and enables
significant added value beyond sensor and chip data.
The Auto-E-Connect function is built up in three levels. Currently there are
Level I, Level II and Level III available.
Please refer to the technical data to find out which Auto-E-Connect functionality is supported by this sensor.
With Auto-E-Connect Level III, fully automatic configurations of the 1-Wire devices on the
1-Wire bus are possible. It is optimized for industrial and IoT applications and enables significant added value
beyond sensor and chip data.
With the Auto-E-Connect function, ESERA devices are detected fully automatically, suitable libraries are started
and ready-formatted data is output.
The Auto-E-Connect functionality will be available for the ECO Controller and ESERA-Station 200 Pro from 2021.
Auto-E-Connect Level I
OWD Detect: Detection of new sensors and actuators and automatic start of adapted libraries.
Auto-E-Connect Level II
Visualize product data: Readout and visualization of Auto-E-Connect and manufacturer data of sensors
and actuators, such as article number, date of manufacture, firmware and hardware version.
Auto-E-Connect Level III
Extended Plug and Play system for 1-Wire Bus
oPre Configuration: The OWD number for the next installation can be written to the 1-Wire device.
Note
Basics and tips for the 1-Wire Bus system can be found in the ESERA Online Shop at
https://www.esera.de/1-wire-grundlagen/
or please refer to our eBook in the store under Training/Documentation

Art. No. 11150
All rights reserved. Reproduction as well as electronic duplication of this user guide, complete or in part, requires the written consent of
ESERA GmbH. Errors and technical modification subject to change. ESERA GmbH 2021
www.esera.de 11150 V3.0 R1.0 Manual Page 3 of 7
oAutomatic Positioning: The device logs on to any ECO Controller with Auto-E-Connect III with the new
request OWD number. This automatic login works up to the maximum possible OWD number of the
ECO controller
oSensorfinder Function: The ECO Controller can activate a status LED within the ESERA 1-Wire Pro
sensors. The status LED flashes or lights up permanently for a certain time. This makes the detection of
a device in a 1-Wire network much easier. A faster detection saves a lot of time and therefore money
when searching for a 1-Wire device.
oClasses Assignment: ESERA 1-Wire devices are assigned to OWD classes with the same properties.
This assignment enables fully automatic visualization and data evaluation in control systems. A class list
is available from ESERA.
For further information about the ESERA Auto-E-Connect System please refer to the ESERA website and
the ESERA Config Tool 3.
Auto-E-Connect is registered as a German and European Patent by ESERA GmbH.
3 Technical data
Function
Multisensor or temperature and rel.humidity
Monitoring of the operating voltage
Temperature sensor
high-precision digital temperature sensor with 12-bit measured value
resolution
Measuring range
temperature
-40°C to +85°C (Sensor element: -40°C to +85°C)
Accuracy temperature
0,2° in the range 5 to 60°C (better than DS18B20 Sensor)
Resolution
12 bit, 0.06°C/bit depending on selected resolution
Humidity sensor
capacitive digital humidity sensor with high accuracy
Measuring range humidity
0-100% rel. humidity
Accuracy humidity
2% in the range of 20-80% at 25°C
Data output
0-10V corresponds to 0-100% relative humidity, 0.1V = 1% rH
Interface
3 - wire connection (data, ground and 5V, parasitic operation not
supported)
Connection
screw terminal for cable solid 0.2 to 2.5qmm or
fine stranded 0,2 to 1,5qmm
for connection we recommend slotted screwdriver size 2,5x75
1-Wire interface
based on DS2438
Operating voltage
5 V= (+10%/-20%)
Current consumption
approx. 2mA
Auto-E-Connect
level I,II, from 2022 level I-III
4 Ambient conditions
Protection system
IP20
Protection class
III
Temperature, operation
-25°C to 80°C, (limitation by carrier system, sensor -40°C to +125°C)
Humidity
10 - 90% (non condensing)
Dimensions (outside)
71 x 71 x 32mm (LxWxH)

All rights reserved. Reproduction as well as electronic duplication of this user guide, complete or in part, requires the written consent of
ESERA GmbH. Errors and technical modification subject to change. ESERA GmbH 2021
www.esera.de 11150 V3.0 R1.0 Manual Page 4 of 7
5 Conformity
EN 50090-2-2
EN 61000-4-2, ESD
EN 61000-4-3, HF
EN 61000-4-4, Burst
EN 61000-4-5, Surge
EN 61000-6-1, interference immunity
EN 61000-6-3, interference radiation
RoHS
6 Software / Control
The 1-Wire Multisensor Pro is read out via 1-Wire command for DS2438 modules. The sensor is supported by
many controllers like ESERA-Station, Loxone, IP-Symcon, OWFS, FHEM, (Linux) or Micro Controller
applications.
For ESERA 1-Wire Multisensors of the Pro series no complex formulas are necessary anymore.
A sensor controller within the Multisensor takes over the preprocessing of all measured values and thus simplifies
the integration into 1-Wire systems enormously. Also, the measured values are no longer dependent on the
operating voltage of the 1-Wire Multisensor.
The sensor measured values are assigned to the standard DS2438 device values as follows:
VDD = operating voltage (5V), VAD = humidity, Xsense = no data output, fixed at 0
Calculations
Temperature
Standard output according to DS2438 module
Operating voltage
Standard output according to DS2438 module
Humidity
To obtain the rel. humidity in percent, multiply the output value (Vas) by a factor of 10. 0.1V corresponds to
1% relative humidity.
7 Data output 1-Wire Controller / 1-Wire Gateway
For the 1-Wire Multisensor Pro, the following measured values are calculated and output by the 1-Wire
Controller / 1-Wire Gateway. The dew-point calculation is a function of the 1-Wire Controller /
1-Wire Gateway.
Data output:
1_EVT|12:27:40
1_OWD1_1|2008 => controller no._module no._data set|temperature (°C) example: 20,08 °C
1_OWD1_2|511 => controller no._module no._data set |voltage VCC (V)
1_OWD1_3|470 => controller no._module no._data set|humidity (rF) example 47,0%
1_OWD1_4|1200 => controller no._module no._data set|dew point (°C) example: 12,00 °C
Further information for options and commands can be found in the latest available documentation for
1–Wire Controller / 1–Wire Gateway.
8 Integration in IP-Symcon / ESERA-Station
Through our website we provide ESERA IP-Symcon software-modules to import the 1-Wire Multisensor in
IP-Symcon via 1-Wire Controller / 1-Wire Gateway. Therefore, no scripts are necessary.
Details can be found on the ESERA website at : https://www.esera.de/kompatible-steuerungen-zentralen/ip-
symcon-integration/.
For conventional connection via 1-Wire Bus couplers, the sensor values must be calculated according to the
specified formulas.
9 Integration in Loxone
At our webshop we provide a sample project on how to import the 1-Wire Multisensor by 1-Wire Controller
1/1-Wire Gateway. Further details can be found here:

Art. No. 11150
All rights reserved. Reproduction as well as electronic duplication of this user guide, complete or in part, requires the written consent of
ESERA GmbH. Errors and technical modification subject to change. ESERA GmbH 2021
www.esera.de 11150 V3.0 R1.0 Manual Page 5 of 7
https://www.esera.de/kompatible-steuerungen-zentralen/loxone-integration/demo-1-wire-controller-1-loxone-
integration/
10 Integration in FHEM
For the integration into the open source automation software FHEM we provide a software module for
reading in the 1-Wire Multisensor via 1-Wire Controller / 1-Wire Gateway. This means that evaluation scripts
are no longer necessary.
Details can be found on the ESERA website under "Compatible controllers - control units / FHEM integration”
https://www.esera.de/kompatible-steuerungen-zentralen/fhem-integration/
11 Measurement accuracy
The sensor elements inside the 1-Wire Multisensor Pro are calibrated. Please note that the measuring
accuracy may possibly decrease towards the measuring range limits as well as at very high/low operating
temperatures.
12 Connection
The 1-Wire Multisensor Pro is connected by screw terminals.
The connection terminal is intended for solid cables with 0.2 to
2.5qmm or fine wire cables with 0.2 to 1.5qmm cross-section.
For the connection we recommend slotted screwdriver size
2,5x75.
The pin assignment is printed on the circuit board.
The correct polarity must be observed during connection.
The Multi-sensor must be connected with three cables (ground,
1-Wire Data and 5V). Parasitic mode is not supported.
13 Assembly
The mounting location must be protected from direct sunlight, moisture (e.g. dripping water) and drafts. The
device may only be used in dry indoor rooms and in protected outdoor areas. During installation, make sure
that the ventilation openings are located at the top and bottom. Also note the imprint of the direction of the air
flow on the connection side of the unit
A draught-free location must be selected for installation. The unit is intended for installation inside a living
room as a stationary unit. The 1-Wire Multisensor can be ideally mounted on a flush-mounted box through
clever housing cut-outs.
14 1-Wire Network Cabling
The special feature of the 1-Wire system is the "BUS technology". All devices (sensors and actuators) are
operated in parallel on a three-wire line, which is used for both power supply and data communication. The 1-
Wire bus system joins the list of other successful bus systems such as CAN or Modbus RTU. All of the installation
principles recommended for these are also applicable and appropriate to 1-Wire.
The maximum size of a 1-Wire Network is determined by various factors. These are mainly:
Note
The module may only be operated at the voltages and under the ambient conditions intended for it. The
operating position of the device is arbitrary.
The modules may only be commissioned by a qualified electrician.
For further information on the operating conditions, see the following instructions under
"Operating conditions".

All rights reserved. Reproduction as well as electronic duplication of this user guide, complete or in part, requires the written consent of
ESERA GmbH. Errors and technical modification subject to change. ESERA GmbH 2021
www.esera.de 11150 V3.0 R1.0 Manual Page 6 of 7
- Total cable length and cable type
- Number of 1-Wire devices
- Type of cable installation (topology)
- Number and design of cable connectors (unnecessary connection transitions should be avoided)
All factors in total are summarised and referred to as 1-Wire Bus load. Each increase of a factor increases the
total 1-Wire Bus load for the 1-Wire controller and thus reduces the maximum network size.
According to our many years of experience and a lot of feedback from customers, the following conservative
recommendation can be made:
- Maximum cable length 50 -120m
- Number of 1-Wire devices no more than 20 -22 pieces
- As linear a topology as possible without T-junctions
The topology in particular plays a major role. If possible, linear topology should be used. The linear topology can
be compared like pearls on a pearl necklace. The data line should be laid from one device to the next without
T-joints.
Furthermore, the type of cable used can also be mentioned here. We recommend for the cabling
CAT5 or CAT6 network cable. It is also possible to use J-Y(St)Y telephone cables and KNX cables. Longer cable
runs are possible with CAT5 versus CAT7 cables.
With twisted pair cables, a longer connection length can be achieved in an undisturbed environment, as the
capacitive bus load is lower. A total length of 50 m and more can be easily achieved without additional measures.
In disturbed, commercial and industrial environments, the cable should always be shielded in order to increase
the "robustness" or interference sensitivity of the system
15 Operating conditions
The Multisensor is designed for temperature and humidity measurements of air and gases indoors, such as
living spaces, offices, workshops or public facilities. The measured values given under technical data are
limit data for the entire 1-Wire Multisensor and must not be undershot or exceeded, otherwise the sensor
may be damaged.
16 Disposal note
Do not dispose of the device within the household waste! According to the directive
concerning old electrical and electronic appliances, electronic devices must be disposed of
via the collecting points for old electronic appliances!
17 Safety instructions
When using products that come into contact with electrical voltage, the valid VDE regulations must be
observed, especially VDE 0100, VDE 0550/0551, VDE 0700, VDE 0711 and VDE 0860
All final or wiring work must be carried out with the power turned off.
Before opening the device, always unplug or make sure that the unit is disconnected from the mains.
Components, modules or devices may only be put into service if they are mounted in a contact proof housing. During
installation they must not have power applied.
Tools may only be used on devices, components or assemblies when it is certain that the devices are disconnected
from the power supply and electrical charges stored in the components inside the device have been discharged.
Live cables or wires to which the device or an assembly is connected, must always be tested for insulation faults or
breaks.
If an error is detected in the supply line, the device must be immediately taken out of operation until the faulty cable
has been replaced.
When using components or modules it is absolutely necessary to comply with the requirements set out in the
accompanying description specifications for electrical quantities.
If the available description is not clear to the non-commercial end-user what the applicable electrical characteristics for
a part or assembly are, how to connect an external circuit, which external components or additional devices can be
connected or which values these external components may have, a qualified electrician must be consulted.
It must be examined generally before the commissioning of a device, whether this device or module is basically
suitable for the application in which it is to be used.
In case of doubt, consultation with experts or the manufacturer of the components used is absolutely necessary.
For operational and connection errors outside of our control, we assume no liability of any kind for any resulting
damage.
Note
The above statements about 1-Wire are hints and tips and do not describe any product property or
represent any warranted product property of the product and the 1-Wire Controller.
1-Wire Controller dar.

Art. No. 11150
All rights reserved. Reproduction as well as electronic duplication of this user guide, complete or in part, requires the written consent of
ESERA GmbH. Errors and technical modification subject to change. ESERA GmbH 2021
www.esera.de 11150 V3.0 R1.0 Manual Page 7 of 7
Kits should be returned without their housing when not functional with an exact error description and the
accompanying instructions. Without an error description it is not possible to repair. For time-consuming assembly or
disassembly of cases charges will be invoiced.
During installation and handling of components which later have mains potential on their parts, the relevant VDE
regulations must be observed.
Devices that are to be operated at a voltage greater than 35 VDC / 12mA, may only be connected by a qualified
electrician and put into operation.
Commissioning may only be realized if the circuit is built into a contact proof housing.
If measurements with an open housing are unavoidable, for safety reasons an isolating transformer must be installed
upstream or a suitable power supply can be used.
After installing the required tests according to DGUV / regulation 3 (German statutory accident insurance,
https://en.wikipedia.org/wiki/German_Statutory_Accident_Insurance) must be carried out.
18 Warranty
ESERA GmbH guarantees that the goods sold at the time of transfer of risk to be free from material and workmanship
defects and have the contractually assured characteristics. The statutory warranty period of two years begins from date of
invoice. The warranty does not extend to the normal operational wear and normal wear and tear. Customer claims for
damages, for example, for non-performance, fault in contracting, breach of secondary contractual obligations,
consequential damages, damages resulting from unauthorized usage and other legal grounds are excluded. Excepting to
this, ESERA GmbH accepts liability for the absence of a guaranteed quality resulting from intent or gross negligence.
Claims made under the Product Liability Act are not affected.
If defects occur for which the ESERA GmbH is responsible, and in the case of replacement goods, the replacement is
faulty, the buyer has the right to have the original purchase price refunded or a reduction of the purchase price.
ESERA GmbH accepts liability neither for the constant and uninterrupted availability of the ESERA GmbH or for technical
or electronic errors in the online offer.
We are constantly developing our products further and reserve the right to make changes and improvements to any of the
products described in this documentation without prior notice. Should you require documents or information on older
19 Trademarks
All mentioned designations, logos, names and trademarks (including those which are not explicitly marked) are
trademarks, registered trademarks or other copyright or trademarks or titles or legally protected designations of their
respective owners and are hereby expressly recognized as such by us. The mention of these designations, logos, names
and trademarks is made for identification purposes only and does not represent a claim of any kind on the part of
ESERA GmbH on these designations, logos, names and trademarks. Moreover, from their appearance on ESERA GmbH
webpages it cannot be concluded that designations, logos, names and trademarks are free of commercial property rights.
ESERA and Auto-E-Connect are registered trademarks of ESERA GmbH.
ESERA GmbH is a supporter of the free internet, free knowledge and the free encyclopedia Wikipedia.
We are a member of Wikimedia Deutschland e.V. (registered association), the provider of the German site
Wikipedia (https://de.wikipedia.org). ESERA membership number: 1477145
Wikimedia Germany's association purpose is the promotion of free knowledge.
Wikipedia® is a registered trademark of the Wikimedia Foundation Inc.
20 Contact
ESERA GmbH
Adelindastrasse 20
87600 Kaufbeuren
GERMANY
Tel.: +49 8341 999 80-0
Fax: +49 8341 99980-10
www.esera.de
WEEE-Number: DE30249510
Table of contents
Other esera automation Accessories manuals

esera automation
esera automation Multisensor 11132 Gen2 User manual

esera automation
esera automation 11112 User manual

esera automation
esera automation Multisensor Pro I User manual

esera automation
esera automation 11134 User manual

esera automation
esera automation Windsensor Pro 200 User manual

esera automation
esera automation 20002 User manual

esera automation
esera automation MS 100 User manual

esera automation
esera automation Multisensor Pro 11150 User manual