EVAX EVX-ZM User manual

Installation Manual: EVAX EVX-ZM Zone Splitter
NOTICE TO THE INSTALLER
This manual provides an overview and the installation instructions for the EVAX EVX-ZM Zone Splitter. All terminals are power limited
and should be wired in accordance with the requirements of NFPA 70 (NEC), NFPA 101 (Life Safety Code) and NFPA 72 (National Fire
Alarm Code). Failure to follow the wiring diagrams in the following pages will cause the system to not operate as intended. For further
information, refer to the control panel installation instructions.
The module shall only be installed with listed control panels. Refer to the control panel installation manual for proper system operation.
Description
The EVX-ZM Zone Splitter Module is intended for use with the EVAX 25/50/100. Its purpose is to enable the output of the EVAX
25/50/100 to be split into multiple circuits for audio power distribution. The modules accept input from the EVAX 25/50/100 speaker
output and utilize output relays to distribute the power to separate circuits. The modules may be cascaded to increase the number of
circuits. The modules provide supervision of the individual circuits for either open or short conditions. Indicator LEDs display active or
fault condition for the individual circuits. Fault condition is reported to the EVAX 25/50/100 via the I2C communication port. The EVX-ZM
may also be used with legacy EVAX 25/50/100 models, but supervision must now employ TB2 Terminals 10-11 as a supervisory input.
Consult factory for connection details.
If Manual control of the circuits is required an EVX-SL8 must be employed. Zones may then be selected manually by switches or
through pull-down inputs. In the event of an alarm condition, module defaults to an All-Call. All-Call feature may only be overridden if
accompanying panel has zone control features
Installation and Operation
Install equipment in a clean, dry environment, avoid installation where equipment could be subjected to vibration. Remove electronic
assemblies from the enclosure prior to any drilling or punching of the enclosure. Where possible, make all cable entries from the rear or
sides. Before making any modications to the enclosure, be certain that they will not interfere with assemblies or batteries.
In normal standby the EVX-ZM will supervise each speaker zone wire loop. The EVX-ZM will provide 4 Class B (Style Y) or 2 Class A
(Style Z) speaker circuits. This is eld selectable via SW1. Upon an open or short condition the Amber LED for that zone will light. This
Fault will report through the EVAX 25/50/100 to the supervising FACP.
If manual Zone selection is employed, select the corresponding EVX-SL8 switch. It’s Red LED will light, and the EVX-ZM output relay
activation will be enabled. On activation of the PTT signal from the EVAX 25/50/100, the output relay will connect the zone to the EVAX
25/50/100 speaker output.
In an Alarm condition the EVX-ZM defaults to an All-Call. On activation of the EVAX 25/50/100 V+ Alarm output, all zones are
automatically selected, enabling evac tone and message to play. Modules will have eld selectable option for alarm zone activation only
if the FACP has the ability to provide separate pull-down inputs.
Speaker output may be 25 or 70 Vrms. This is eld selectable by SW1-2. Output circuits are limited to 50W per zone at 70 Vrms and
40W at 25 Vrms. Total speaker load combined is not to exceed output rating of the EVAX 25/50/100 driving the Zone Module. Upon a
short condition, the shorted zone will open excluding that zone from output and enable the other zones to continue operating. Speaker
circuits must be terminated with a 10K EOLR device. The end of line value is not adjustable or programmable. Speaker circuits will
indicate a Fault if the circuit impedance falls to 5K or increases to 15K Ohms.
5403675 Rev A 1/18
Evax by Potter • Branford, CT • Phone: (800) 325-3936 • www.evax.com
PAGE 1 OF 3

INSTALLATION MANUAL: EVAX EVX-ZM ZONE SPLITTER
5403675 Rev A 1/18
Evax by Potter • Branford, CT • Phone: (800) 325-3936 • www.evax.com
PAGE 2 OF 3
TB1:
Ter. 1 - 8 Speaker Output 25/70 Vrms
70V - 50W Max speaker load per zone.
25V - 40W Max speaker load per zone.
TB2:
Te
r. 1 & 2 - Speaker Input (25 or 70VRMS)
Te
r. 3 - PTT (Push To Talk signal)
+24VDC when main system microphone active
Te
r. 4 - V+ (24V DC 0.10A)
Te
r. 5 - Alarm Active
+24VDC when programmed event active at main
amplifier (Bell, secondary message, etc.)
Te
r. 6 - Circuit Negative
Te
r. 7 / 8 / 9 - Aux. Trouble Common Relay
7 - N.O. / 8 - C / 9 - N.C.
Contact Ratings: 1A
@30VDC
Connect to Resistive Load, Class II Power or Power
Limited Sources Only
. Interconnected Equipment
Must be in Same Room and Mounted Within 20'.
Te
r. 10 & 11 - Supv. Circuit Input
TB3:
Ter. 1& 2 - Do Not Use
Ter. 3 - 7 - Aux. Zone Activate (Pull Down)
Connect point to ckt neg for external zone selection
3 - ALL CALL / 4- Zone 4
5 - Zone 3 / 6- Zone 2 7-Zone 1
SW1:Power Selection
SW1-1 Select class “A” or “B” Speaker circuit
On for Class “A” Off Class “B”
SW1-2 Select 25v or 70v speaker voltage
SW1-3
SW1-4
LED1 Power On
LED 2 Status
LED 3 Fault
LED 4 (red) - Zone 1 Selected
LED 5 (yel) - Zone 1 Fault
LED 6 (red) - Zone 2 Selected
LED 7 (yel) - Zone 2 Fault
LED 8 (red) - Zone 3 Selected
LED 9 (yel) - Zone 3 Fault
LED 10 (red) - Zone 4 Selected
LED 11 (yel) - Zone 4 Fault
JUMPER J2:
1-2 Jumped when used with Legacy DMR,
enables 5 volts to P4 to power additional
I2C devices.
2-3 Jumped when used with new
Generation DMR enables 5 volts from
P3 to P4 to power additional I2C devices.
SPECIFICATIONS:
Power: 24 VDC
0.051A Standby
EVX-ZM
Field wiring connections:
#6-32 wire clamp screw 14-18AWG
#8-32 wire clamp screw 12-18AWG
Horizontal wire entry terminal 18-26 AWG
Wire gauge determined by circuit load
TB2
TB3
1
1
2 3 4 5 6 7
2
3
4
5
6
7
8
9
10
11
12345678
132465 78
P1
P3 P4
1 32 4
LED 5
LED 4
LED 6
LED 7
LED 8
LED 9
LED 10
LED 11
3DEL
2DEL
1DEL
10K
EOLR
10K
EOLR
10K
EOLR
10K
EOLR
+----
++++
TB1
Speaker Output
1324
SW1
ON
A / B
25V / 70V
J2
P2
P1: Programming Port
P3: I2C Port In
P4: I2C Port Out
10 Pin Ribbon Connector
The I2C Port from the EVX-25/50/100
will support a maximum of 16 devices total
P2: Diagnostic Port
EVX-ZM Connections

INSTALLATION MANUAL: EVAX EVX-ZM ZONE SPLITTER
5403675 Rev A 1/18
Evax by Potter • Branford, CT • Phone: (800) 325-3936 • www.evax.com
PAGE 3 OF 3
Class "B" (Style Y) Wiring
(supervised)
Amp
EOLR
+24VDC
Ckt. Neg.
SIG
CKT
SPKR
POWER
(SUPERVISED)
(SUPERVISED)
SPEAKER
CONNECTION
(NON-SUPERVISED)
Zone 1
Zone 2
Zone 3
Zone 4
All Call
N.O. Dry Contact Per Zone for
“Alarm By Zone” operation
(relays and wiring customer supplied)
ZONE 1
ZONE 2
ZONE 3
ZONE 4
Break wire run to maintain supervision.
Do not loop wire around speaker terminals.
Ground faults are indicated at 10K impedance or less
10K
EOLR
Field wiring connections:
#6-32 wire clamp screw 14-18AWG
#8-32 wire clamp screw 12-18AWG
Horizontal wire entry terminal 18-26 AWG
Wire gauge determined by circuit load
CAUTION:
TB2
P3
++
TB1
1
2
3
4
5
6
7
8
9
10
11
1 2
1DEL
-
1
2DE
L
+
2
3
13
246578
3D
EL
J2
TB3
3
4
-
4
P1
+
25V / 70V
5
5
1324
SW1
ON
A / B
6
6
-
1324
7
+
7
LED 5
LED 4
LED 6
LED 7
LED 8
LED 9
LED 10
LED 11
8
P4
-
1
2
TB1
12 345678
P7
1
2
3
4
5
6
7
8
MSG
GAIN
MIC
GAIN
FAULT
NORMAL
ALARM
YEL
GRN
RED
P2
S1
Sn1
Sn2
J5
J1
1
2
3
TB6
P5
P8
J8
P4
1
2
3
4
5
6
7
8
9
10
11
123
J2
70V 25V
TB2
LED 1
LED2
LED 3
LED 4
LED 5
J3
TB3
P9
Amp Set Value EOLR
Ribbon Cable
2
3
1
#18 AWG min.
#28 AWG min.
#20 AWG min.
EVX-ZM Zone Splitter
Typical Wiring Diagram
TB2
P3
++
TB1
1
2
3
4
5
6
7
8
9
10
11
1 2
1DEL
-
1
2DEL
+
2
3
13246
578
3DEL
J2
TB3
3
4
-
4
P1
+
25V / 70V
5
5
132 4
SW1
ON
A / B
6
6
-
1324
7
+
7
LED 5
LED 4
LED 6
LED 7
LED 8
LED 9
LED 10
LED 11
8
P4
-
TB2
P3
++
TB1
1
2
3
4
5
6
7
8
9
10
11
1 2
1DE
L
-
1
2DEL
+
2
3
13
246
578
3DEL
10K
EOLR
J2
TB3
3
4
-
4
P1
+
25V / 70V
5
5
1324
SW1
ON
A / B
6
6
-
1 324
7
+
7
LED 5
LED 4
LED 6
LED 7
LED 8
LED 9
LED 10
LED 11
10K
EOLR
8
P4
-SPEAKER
CONNECTION
AMP EOLR
ZONE 1
ZONE 2
Class "A" (Style Z) Wiring
(supervised)
10K
EOLR
10K
EOLR
FROM
EV
AX 25/50/100
Field wiring connections:
#6-32 wire clamp screw 14-18AWG
#8-32 wire clamp screw 12-18AWG
Horizontal wire entry terminal 18-26AWG
Wire gauge determined by circuit load
Ribbon Cable
Ribbon Cable
2
3
1
#18 AWG min.
2
3
1
Class "A" configuration selected by
putting SW1-1 in the On position
Additional units may be daisy
chained in the same fashion.
For all field wiring, use FPL, FPLR,
or FPLP as required per NFPA 70,
Article 760
EVX-ZM Zone Splitter
Typical Wiring Diagram
Multiple Units
Table of contents