EWC Controls BMPlus 3000 Service manual

The BMPlus Zone Control System allows you to easily
upgrade an inefficient single zone HVAC system, into a
Multi-zone, Energy savings, Comfort producing, HVAC
system. The Superior Design, Intuitive Firmware, Simple
Setup Options, Easy to Understand wiring and Backwards
Compatibility, makes the BMPlus Zoning system the
Contractors dream. Combined with EWC Motorized
Dampers and any off-the-shelf Thermostats, EWC Controls
sets another high standard in the residential & light
commercial Forced Air Zoning Industry.
The main module controls three zones
using motorized dampers and may be
expanded to 5 or 7 zones, using 1 or 2
Model XM2 Expansion Modules.
Controls 2 & 3 stage conventional or dual
fuel heat pumps, without the need for dual
fuel kits. Also single or two-stage gas, oil,
& hydronic heating systems, with single or
two stage air conditioning. Constant or
variable speed fan systems.
Compatible with any off the shelf
Heat Pump Thermostat
(2heat/1cool). You may also use any
regular Heat/Cool thermostat
(1heat/1cool). You may still use
regular Heat/Cool thermostats to
control a Heat Pump system.
The BMPlus Zone system features
automatic changeover from any
thermostat allowing for individual zone
comfort from the HVAC system.
A green STATUS LED pulses as a steady
heart beat to indicate Micro- processor
activity and 24v power is present.
Function specific colored LED’s illuminate
to indicate the HVAC system mode of
operation and active zone identification.
See page 10 for details.
Green LEDs labeled Zone 1 thru Zone 7
indicate which dampers are energized to
the open position.
INPUT VOLTAGE: 19-30VAC 60 Hz
Transformer 40-100VA MAX. NEC Class 2.
CURRENT DRAW: Max 15VA @ 24VAC.
OVER-CURRENT PROTECTION: 4.0 amp
The BMPlus module has a Thermal
circuit breaker that protects the
module(s) from shorts in the damper
and thermostat field wiring. It will
not protect against shorts in the
HVAC system wiring.
CAUTION: When the circuit breaker
is tripped it will get quite hot. To
reset the breaker: Shut off power to
the panel. Find and repair the short.
Restore the 24VAC power.
Any zone can activate the indoor fan
and only the dampers in zones calling
for continuous fan operation will open.
Continuous fan operation will only
occur when there are no active or
pending, heat or cool demands. A dip
switch is provided to enable automatic
fan operation in heat mode. Useful for
straight electric heat or hydronic heat
applications.
Zone
Capacity
Compatible
HVAC
Systems
Compatible
Thermostats
Automatic
Heat/Cool
Changeover
Status LED
System LEDs
Damper LEDs
Operating
Power
Thermal
Circuit
Breaker
Indoor Fan
Control
Models BMPlus 3000/5000/7000 Rev. B
(DISPONIBLE EN ESPAÑOL EN EWCCONTROLS.COM)
ewccontrols.com/acrobat/090375a0244.pdf
TB-228
P/N 090375A0228 REV. L 06.01.18
Box Contents * BMPlus 3000 Control Panel
* Supply Air Sensor
* Technical Bulletin TB228
* Mounting Hardware
Leave this bulletin on the job site for future reference!
Operating
Conditions
J1
ZONE3
MOTOR
ZONE2
MOTOR
MOTOR
ZONE1
24
T’FORMER
VAC
SYSTEM
M6
M4
M2
M1
M6
M4
M2
M1
M6
M4
M2
M1
R
C
G
Y2
Y1
O
RH
RC
W1
B
W2
E
LINK
RH
RC
D
43
D
C
1
C
2
+
+
SAS
SAS
OAS
OAS
C
W/E
O/B
Y
R
G
ONE
ZONE
EM
NORM
SW
4
ZONE1
STAT
T
D
11
D
12
D
13
D
10
2
ND STAGE HEAT
DIFFERENTIAL
LIMIT
HIGH
TEMPLOW TEMP
LIMIT
TIMER OAS
STAGING
47
5
40
33
26
19
12
110
120
130 140 150
160
170
52
49
46
43
40
37
34
42
35
28
21
14
7
OFF
BMPlus3000 rev B
W
2
EM
B
1
W
1
2
Y
Y
ZONE
ZONE
ZONE
FAN
1
2
3
STATUS
OAS
SAS
38
39
R
R
R
37
R
36
R
76
77
R
72
R
73
R
R
70
69
R
67
R
68
R
65
R
R
64
71
R
R
63
62
R
R
61
60
R
59
R
58
R
R
57
56
R
55
R
54
R
R
78
79
R
53
R
52
R
R
51
50
R
49
R
48
R
R
47
46
R
45
R
81
R
R
40
43
R
R
42
41
R
10
LED
9
LED
8
LED
7
LED
6
LED
5
LED
4
LED
3
LED
2
LED
1
LED
11
LED
6
U
U
7
U
8
5
U
4
U
U
2
3
U
U
1
1
K
2
K
3
K
4
K
5
K
6
K
7
K
8
K
R
12
R
3
R
4
R
RESET
1
D
2
D
C
11
8
C
7
C
15
C
5
C
R
35
C
10
13
CY
1
21
D
1
Z
14
C
SW
3
33
R
32
R
31
R
30
R
8
D
29
R
R
28
27
R
26
R
7
D
25
R
R
24
23
R
22
R
6
D
21
R
R
20
R
19
5
D
D
934
R
GAS
OFF
OFF
OAS
HC
HP
OTHER
HP
TIMER
ON
HYDRONIC
ON
O B
DF
<
<
<
<
<
< >
>>
>
>>
>
<>
<
SYSTEM
HP CONV
50
TSTATS
RV
STAGING
RULE
SAS
FAN
E
W
C
SYSTEM
CONTROL
%
C
C
W/E
O/B
Y
R
G
ZONE3
STAT
T
F1
C
W/E
O/B
Y
R
G
9
C
66
R
82
R
R
44
R
14
R
R
15
16
U
9
12
C
R
13
EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- [email protected] 1
Copyright ©2007 EWC Controls All Rights Reserved
Figure 1
TEMPERATURE: -20° to 160°F (-29° to 71°C)
HUMIDITY: 0% - 95% RH Non-Condensing.
ZONE2
STAT
T

OFF
7
14 21 28
35
42
STAGING
Timer / OAS
110
120
130 140 150
160
170
HIGH TEMP
LIMIT
34
37
40 43 46
49
52
LOW TEMP
LIMIT
The panel has seven built-in Delay Timers
that insure safe & reliable operation.
When all zone demands are
satisfied, the panel will not resume
the same mode of operation for a
minimum of 3 minutes.
A built-in timer prevents the system
from rapidly switching between
heating and cooling modes. At the
end of a call, a 4 minute timer is
started and the panel will not switch to
the opposing mode until the timer has
expired.
The STAGING TIMER sets the
amount of continuous call time in 1st
stage, before second stage heat or
cool is energized. NOTE: The
potentiometer also serves as the
Outside Air Changeover Setting.
The BMPlus 3000 can inhibit heat
staging based on a Timer or
Outside Air Temperature.
NOTE: An Optional OAS Sensor is
required to use the OAS feature.
NOTE: 2nd stage cool delay defaults
to 30 minutes, if OAS is chosen to
inhibit 2nd stage Heat.
The Adjustable Heating Limit
potentiometer sets the 1st stage heat
supply air temperature, at which the
heating is cycled off and the fan
continues to run, allowing the heat
exchanger or coil to cool down.
The Adjustable Cooling Limit
potentiometer sets the supply air
temperature at which the cooling is
cycled off and the fan continues to run,
allowing the coil to warm up.
*Built-In
Timer
Settings
*Short Cycle
Timer
*Changeover
Timer
Staging
Timer / OAS
Cooling and Heating Limit Controls
Reset
BUTTON
Emergency
Heat
Switch
*Opposing
Call
Delay Timer
A 20 minute delay must expire, or the
active zone(s) must satisfy, before
the panel will honor a thermostat
demand to changeover to the
opposite mode of system operation.
OFF, 7 to 42
minutes or 7
to 42
degrees F.
*Supply Air
Limit
Delay Timer
The time delay of 3 minutes must
expire before the BMPlus 3000 will
re-energize heat or cool mode. This
delay occurs when the processor
detects the supply air temperature is
higher or lower than the High or Low
temperature limit settings.
The Adjustable 2nd stage heat
differential potentiometer sets the 2nd
stage heat supply air temperature, at
which the heating is cycled off and the
fan continues to run, allowing the heat
exchanger or coil to cool down.
NOTE: Allows the supply air sensor to
be installed in the supply air plenum,
regardless of the coil/heat exchanger
configuration. Allows the installer to fine
tune virtually any multi stage heating
system!
RESET
EM
NORM
An On-Board Switch is provided that
allows the Customer to set the system
to the Emergency heat mode.
This switch is shown in the NORMAL
position.
This switch would be used for Heat
Pump applications where the
Customer chooses to use Regular
Heat/Cool thermostats instead of
Heat Pump thermostats.
2nd STAGE HEAT
DIFFERENTIAL
5
12
19 26 33
40
47
Example:
Hi Temp. Limit =130°F
plus 2nd stg. DT= 40°F
New Limit = 170°F.
BMPlus 3000 FIRMWARE/HARDWARE FEATURESBMPlus 3000 FIRMWARE/HARDWARE FEATURES
EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- [email protected]
2
The separate reset buttons on the
old BMP3000 have been replaced by
a single button with dual functions.
Momentarily pressing the RESET
button clears the built-in timers
controlling the Startup delay timer,
Short cycle timer, W2 timer, Supply air
sensor timer and the Changeover
timer. This enables you to test the
installation faster. Caution should be
observed when using this button.
Always reset the CPU
anytime you make
dip-switch changes to
the BMP3000 panel!
DO NOT use a sharp
object to press the
button! Your finger tip
will work fine. Pressing the RESET button for 7
seconds will reset the CPU for
the entire zone system.
*Startup
Delay
Timer
The panel will not activate any
cooling or heating operation until
the startup delay has expired. This
occurs after any initial power up or
power failure. Press the Reset
button for 1 second to override.
* Start-up Delay Timer = 3 minutes-fixed
* Short Cycle Timer = 3 minutes-fixed
* Change Over Timer = 4 minutes-fixed
* Opposing Call Timer = 20minutes-fixed
* Staging Timer = OFF or 7-42 min. -Adj.
* Supply Air Limit Timer = 3minutes-fixed
* Purge Delay Timer = 90 seconds-fixed
*Purge Delay
Timer
The last Damper(s) will be held Open
for 90 seconds at the end of every call
allowing a system purge into the last
zone that was calling.
Any setting
below 7 is off!
DO NOT set to off
if using OAS

1
2
3
4
5
6
7
8
HP < SYSTEM > OTHER
DF < HP > CONV
HC < TSTATS > HP
O < RV > B
OAS < STAGING > TIMER
OFF < 50%RULE > ON
OFF < SAS > ON
GAS < FAN > HYDRONIC
Choose the type of HVAC system you want to control. Select HP, if your system is any type of Heat Pump. Select OTHER,
if your system is a standard Gas or Oil furnace. Other setting also applies to straight electric furnaces or hydronic
(hot water coil) heating systems.
Choose the type of Heat Pump you want to control. Select DF (Restricted Mode) if you wish to lock out the
compressor during auxiliary heat operation, typically set for Dual Fuel operation. Select CONV (Unrestricted Mode) if
you wish to have the compressor run during auxiliary heat operations, typically set for Electric Back-up.
Select HC, if you want to use regular Heat/Cool thermostats on your job. Select HP, if you want to use Heat Pump
thermostats on your job. Remember that you can use standard Heat/Cool Thermostats on a Heat Pump application.
Select the correct Reversing Valve signal for your particular Heat Pump. Choose “O” for any Heat Pump that energizes
the RV in the cooling mode. Choose “B” for any Heat Pump that energizes the RV in heating mode.
Select OAS, if you want to delay auxiliary heat based on the outside air temperature sensor. Select TIMER, if you
want to delay W2 and Y2 based on the adjustable on-board timer. NOTE: ‘Y2’ defaults to a 30
minute delay, when OAS is chosen.NOTE: An optional OutsideAir Sensor (OAS) is required to use the OAS feature.
Select OFF, if you do not want to inhibit Y2 and/or auxiliary heat based on the total number of zones calling.
Select ON, if you do want to inhibit Y2 and/or auxiliary heat based on the total number of zones calling. More than
half the total zones must be calling for the same mode of operation (heat or cool), or the BMPlus3000 will not
stage up. This feature is a great way to save energy. Emergency heat mode will override the 50% rule.
Select OFF, if you do not want to use the supply air sensor included with the BMPlus Zone Control system. Select ON, if
you intend to use the included supply air sensor. Refer to the data sheet included with the supply air sensor for details.
Select GAS, if your HVAC system is a gas or oil forced air furnace. Select HYDRONIC, if your HVAC system has a hot
water coil, or straight electric heat with no indoor blower support. Useful when you need the indoor blower to run
automatically in heat mode, just like it does in cool mode. NOTE: When you select HP on dip switch #1, the indoor fan
mode is automatically set for you. There is no need to move this switch when setting up for Heat Pump operations.
Programming and setting up the BMPlus
3000 to control your HVAC system is very easy!
Look below for an explanation of each dip
switch function and choose your settings.
Some functions may not apply to your application.
Then use a pencil to mark/record your settings. If the
settings get changed later on, you will
have a record of the original settings.
1
2
3
4
5
6
7
8
Selecting the Options Using the DIP Switches
RECORD YOUR OWN DIP SWITCH
SETTINGS HERE
ONON
HP < SYSTEM > OTHER FS
DF < HP > CONV FS
FS HC < TSTATS > HP
FS O < RV > B
OAS < STAGING > TIMER FS
FS OFF < 50%RULE > ON
FS OFF < SAS > ON
FS GAS < FAN > HYDRONIC
IMPORTANT NOTE: The BMPlus 3000 Zone Control System allows Heat Pump thermostats to be connected to all zones.
Using heat pump thermostats means that the zone panel will obey thermostatic demands. This comfort over-ride feature
provides a level of versatility to your zoning system and gives the homeowner comfort control over the system, instead of
waiting for the adjustable timer to energize 2nd stage heat. True thermostatic staging is not available when using 2 Stage
compressor heatpumps, it is advisable to use Heat/Cool thermostats and allow the BMPlus to stage via the on-board timer. If
true thermostatic staging is required, then it is recommended to upgrade to the Model UZC series of Control Panels.
***FS = Factory Settings
EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- [email protected] 3

Figure 2d.
ZONE
T'STAT
C
W/E
Y
R
G
O/B
*
CW/E
BW2 Y1
ORC RH
MODEL EWT-955WH
HDY2
Model EWT-955WH Wireless Thermostat:
Configured for 2 heat 1 cool heat pump.
See thermostat instructions for further
*
Field installed jumper.
TYPICAL 24v WIRELESS THERMOSTAT
MODEL EWT-725
CO
BW2
W/E Y1 RG
*
Model EWT-725: configured for 2 heat 1 cool
heat pump. See thermostat
instructions for further details.
Figure 2c.
ZONE
T'STAT
*
C
W/E
Y
R
G
ONE
ZONE
O/B
Field installed jumper.
**
Common wire not required if batteries are used.
**
INSTALLATION & WIRING INSTRUCTIONS
EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- [email protected]
4
WARNING: THESE PANELS ARE DESIGNED FOR USE WITH 24VAC. DO NOT USE OTHER VOLTAGES! USE CAUTION TO AVOID ELECTRIC
SHOCK OR EQUIPMENT DAMAGE. ALL WORK SHOULD BE PERFORMED TO LOCAL AND NATIONAL CODES AND ORDINANCES. USE 18
HEAT PUMP THERMOSTATS
HEAT/COOL THERMOSTATS
Mount the panel housing in a suitable/convenient location. Mounting hardware is provided. Avoid locations that may become wet or
produce condensation. Hot attics are OK. Use the knockouts on the panel housing as wire entryways. Strain relief fittings can be used
if desired. Use care and do not damage the circuit board when removing the knockouts and making wire connections. NOTE: The
24vac power supply should be supplied by a separate transformer. DO NOT use the 24vac power supply from the HVAC system
unless there is no other alternative. 2 zones and 2 dampers is the limit when stealing voltage from the HVAC system.
NOTE: The BMPlus 3000 allows the user to install Heat Pump
thermostats on all zones. You may still use regular
Heat/Cool type thermostats with a Heat Pump system and
use the Staging Timer to energize the auxiliary heat. If you
don’t have enough wires available. It is advisable to use
Heat/Cool thermostats with 2 stage compressor Heat Pumps.
A single 24vac, 40va
UL Listed transformer
can power the
BMPlus3000 Main
module with up to 12
genuine ND or URD
dampers. See page 9
for more load and
transformer data.
Line
Voltage
TRANSFORMER
24vac, 40 - 75va Max
UL LISTED
BMPlus 3000
Main Module
R - Hot
C - Common
Figure 2 BMPlus 3000 Power
POWER WIRING
Thermostat
Wiring
24 VAC
T’FORMER
R
C
PROVIDE
MEANS OF
DISCONNECT
Model EWT-725: Configured for 1 heat 1
cool. See thermostat instructions for further
details.
ZONE
T'STAT
C
W/E
Y
R
G
ONE
ZONE
O/B
Figure 2a.
MODEL EWT-725
CO
BW2
W/E Y1 RG
*
*
Common wire not required if batteries are used.
Typical “Wi-Fi” Thermostat Configured for
1 heat & 1 cool. See thermostat
Figure 2b
W/E
CG
W2 Y1 Y2 RC
EWT-855i “Wi-Fi” Thermostat
C
W/E
Y
R
G
ONE
ZONE
O/B
1
ZONE
DRY R
R
LED
RH O B
G

THERMOSTAT WIRING CONTINUED
EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- [email protected] 5
Figure 5 Wiring a split circuit thermostat to operate a
Radiant floor heating or Baseboard heating
Hydronic system. The BMPlus 3000 controls the
cooling only in this type of configuration.
WIRING FOR RADIANT FLOOR HEAT
To Radiant floor / Baseboard heat
zone valve or pump relay
W
RH
GRC
Y
ZONE2
T’STAT
Y
R
G
O/B
W/E
C
Figure 6 Wiring for a Radiant floor loop as the first
stage of heat via the isolation relay and 2nd
stage Forced Air heat is controlled through the
zone panel.
ZONE2
T’STAT
Y
R
G
O/B
W/E
C
GW1
RH
RCY
W2
C
To Radiant floor / Baseboard heat
zone valve or pump relay
SPST 24vac
Isolation Relay
HEAT/COOL
THERMOSTAT
MULTISTAGE HEAT/COOL
THERMOSTAT
*
Thermostat should be battery powered.
*
Figure 3.
ZONE
T'STAT
C
W/E
Y
R
G
O/B
CW/E
BW2 Y1
ORC RH
MODEL EWT-955WH
HDY2
Model EWT-955WH Wireless Thermostat:
Configured for 1 heat 1 cool.
See thermostat instructions for further
TYPICAL 24v WIRELESS THERMOSTAT
Typical “Wi-Fi” Thermostat Configured for
2 heat & 1 cool Heat Pump. See
thermostat instructions for further details.
Figure 4
W/E
CG
W2 OY1 RC
EWT-855i “Wi-Fi” Thermostat
C
W/E
Y
R
G
ONE
ZONE
O/B
1
ZONE
DRY R
R
LED
RH Y2 B
TYPICAL 24v WiFi THERMOSTAT
*
*
Field installed jumper.
G

SYSTEM WIRING
Typical gas or Electric Furnace with
A/C. Note the common “C” wire is
connected to the SYSTEM terminal
block of the BMPlus 3000.
Typical heat pump system wiring with electric resistance or
Gas backup heat (No Dual Fuel kit required). This diagram
applies to air cooled or geothermal / ground source
systems.
Wiring diagram for a typical oil burner,
hydronic zone / Air handler with A/C.
Cut the Rc / Rh link on the BMPlus
Panel for systems requiring isolation.
Single
Transformer
Gas or Electric
Furnace & A/C
1 or 2 Stage Heat
Conventional or Dual Fuel 2 Heat / 1 Cool Heatpump
with O (Cool) Type Reversing Valve
Two
Transformer
Systems
Figure 7 Single transformer Conventional system.
Figure 9 -- 2 Heat / 1 Cool Heat Pump System
Figure 8 Two transformer Oil or Hydronic / A/C system.
Conventional or
Dual Fuel 3 Heat /
2 Cool Heat Pump
with O (Cool) Type
Reversing Valve
SYSTEM
O
W1/B
G
Y2
Y1
RH
RC
C
W2/E
RC/RH
LINK
Y
R
C
T
T
Y
W
G
C
Figure 10 – 3 Heat / 2 Cool Heatpump System
HEAT PUMP
2 STAGE
BMPlus 3000
**Note that a Conventional & Dual fuel heat pump wire up more or less the
same. The difference is how auxiliary heat operates. In a Conventional
system, the indoor fan & the compressor continues to run when auxiliary
energizes. In a Dual Fuel system, the indoor fan & the compressor shuts
down when auxiliary energizes. The BMPlus 3000 will perform these
functions automatically. All you have to do is set the dip switches to the
correct settings. Select CONV or DF at dip switch #2. Install regular
Heat/Cool thermostats and choose to activate auxiliary heat by TIMER or by
OUTSIDE AIR TEMPERATURE. (Optional Sensor required). Or you may
choose to install Heat Pump Thermostats on all zones. When the thermostat
auxiliary heat demand is satisfied, the BMPlus 3000 will stage down, unless
DF or OAS has been selected and the outdoor temperature is lower than the
OAS changeover setting. In that case the system will continue in FUEL
mode, until all current heating demands are satisfied.
* Note: Your Air Handler may include a W terminal. That means
it may have it’s own isolation circuit. If you can confirm this,
simply connect the W1/B terminal to the W terminal on the air
handler. Do not cut the Rc/ Rh jumper. Wire up your Oil Burner,
Circulator relay, or Hydronic Zone valve to the isolation
contacts or wires provided in the air handler. The fan is
controlled via the time delay relay inside the air handler.
Don’t worry if you accidentally cut the Rc/Rh link. Just install your
own jumper across the Rc/Rh terminals!
AIR HANDLER
OR 1 0R 2 STAGE
GAS FURNACE
HEAT PUMP
1 STAGE
BMPlus 3000
Conventional or Dual Fuel Heat Pump wiring
with 3 Heat / 2 Cool. With electric or Gas
Furnace Backup (No dual fuel kit is required).
This diagram applies to air cooled or
geothermal / ground source systems.
EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- [email protected]
6
You may need
to Cut the
RC/RH Link
Boiler Control
OR
Zone Valve Control
OR
Circulator Control
OIL
BURNER
PRIMARY
CONTROL
OR
TYPICAL FAN
CENTER
TERMINAL
BLOCK
OUTDOOR
CONDENSING
UNIT
T
T
ISOLATION
TERMINALS
OR WIRES
BMPlus 3000
Y
C
SYSTEM
O
W1/B
G
Y2
Y1
RH
RC
C
W2/E
RC/RH
LINK
Y
W1
W2
R
C
G
BMPlus 3000
GAS or Electric
Furnace
1or2 STAGE
OUTDOOR
CONDENSING
UNIT
To make troubleshooting
easier, connect the “C”
Common from the Furnace
to the BMPlus. If you don’t
connect it, it’s OK.
SYSTEM
O
W1/B
G
Y2
Y1
RH
RC
C
W2/E
RC/RH
LINK
O
X/W
R
C
Y
O
W1
W2
R
C
G
Y
SYSTEM
O
W1/B
G
Y2
Y1
RH
RC
C
W2/E
RC/RH
LINK
O
X/W
R
C
O
W1
W2
R
C
G
Y1
*
Y2
Y1
Y2
AIR HANDLER
OR 1 0R 2 STAGE
GAS FURNACE

SYSTEM WIRING CONTINUED
Typical 2 stage gas furnace with 2
stage A/C. Constant or variable
speed systems can be connected
and controlled. Choose Timer or
Outside air to delay 2nd stage.
Single
Transformer
Gas & A/C
2 stage heat
2 stage cool
Figure 11 Single transformer 2 Stage Heat & Cool system
2 STAGE GAS
FURNACE
BMPlus 3000
Figure 12 -- 3 Heat / 2 Cool Heat Pump with
B (Heat) Type Reversing Valve
Warning: All of the wiring diagrams provided are
general in nature and may not perfectly match your
particular application, due to differences in HVAC Mfr’s
design and terminal designations and functions!
Variations on these diagrams and other System or
Thermostat applications are available by contacting the
EWC Technical Support Hotline.
ENHANCED FEATURES AND FUNCTIONS
The BMPlus 3000 Zone Control System
includes the Shorted Zone Feature. This
feature allows the BMPlus to ignore demands
from a zone thermostat that is putting out
simultaneous demands for heat & cool. A
condition most likely due to a short in the field
wiring, incorrect wiring, or a defective
thermostat. The BMPlus will honor any
legitimate demands from any other zone(s),
except the shorted zone. When the problem is
identified and repaired, the BMPlus 3000 will
automatically recognize that zone.
DUAL FUEL COMPATIBLE
MODULE TO MODULE FACTORY POWER WIRING
SHORTED ZONE FEATURE FIRMWARE
* OFF, 7 TO 42 MINUTE STAGING TIME DELAY SETTINGS
* 7 TO 42°F. OUTSIDE AIR CHANGEOVER
* OPERATES WITH MULTI STAGE HEATPUMPS
* STATUS LED’s ARE INCLUDED ON ALL MODULES
*1 ZONE MODE COMPLIES WITH CALIFORNIA TITLE 24
* SIMPLIFIED WIRING AND EASY SYSTEM SETUP
The BMPlus 3000 is compatible with Dual Fuel
Heat Pumps. Dual Fuel kits are not required.
Select staging based on Adjustable Time
Delay or an Optional Outside Air temperature
Sensor. The intelligent firmware does the rest.
The BMPlus 3000 includes Factory Power
Wiring on all expanded systems. The 24 vac
power to the expansion modules is fed
through the bus cable. This simplifies your
wiring and minimizes the chances of reversing
polarity.
EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- [email protected] 7
* ADJUSTABLE DIFFERENTIAL LIMIT CONTROL
*SECOND STAGE 50% ZONE RULE SAVES ENERGY
NOTE: If desired, you can connect a “C” Common
wire back to the “System” terminal block. Use it as
a TEST point while troubleshooting.
NOTE: The “R” wire connection to the condensing
unit may not be required on your system.
SYSTEM
O
W1/B
G
Y2
Y1
RH
RC
C
W2/E
RC/RH
LINK
2 STAGE
OUTDOOR
CONDENSING
UNIT
Y2
G
Y2
C
R
Y1
W1
W2
R
C
Y1
HEAT PUMP
2 STAGE
BMPlus 3000
SYSTEM
O
W1/B
G
Y2
Y1
RH
RC
C
W2/E
RC/RH
LINK
B
X/W
R
C
B
W1
W2
R
C
G
Y1
Y2
Y1
Y2
Conventional or
Dual Fuel 3 Heat /
2 Cool Heat Pump
with B (Heat) Type
Reversing Valve
Conventional or Dual Fuel Heat Pump wiring
with 3 Heat / 2 Cool with B (Heat) Type
Reversing Valve. Electric or Gas Furnace
Backup (No dual fuel kit is required). This
diagram applies to air cooled or geothermal /
ground source systems.
AIR HANDLER
OR 1 0R 2 STAGE
GAS FURNACE

DAMPER WIRING AND CONFIGURATIONDAMPER WIRING AND CONFIGURATION
Note: All zone dampers default to the "OPEN"
position after a purge delay has occurred.
Dampers also default “OPEN” during
changeover & short cycle delays, and when
all zone demands are satisfied, and no
signals are detected from the thermostats.
6
4
1
PC
PO
COM
ZONE
MOTOR
M1
M6
M4
M2
ZONE
MOTOR
M1
M6
M4
M2
6
4
1
PC
PO
COM
Common 24vac
Constant 24vac HOT
24vac to Open a damper(s)
24vac to Close a damper(s)
Terminal M1
Terminal M2
Terminal M4
Terminal M6
ZONE MODULE DAMPER
MOTOR TERMINAL BLOCK
DESIGNATION & FUNCTION
.
.
A Spring Open Damper is wired to M1 & M6
A Spring Close Damper is wired to M1 & M4
{
MA-ESR
NC NO C M M
Auxilary
SPDT
End Switch
Dry Contacts
Rated for
24vac only
REFERENCE THESE DIAGRAMS PRIOR TO
INSTALLATION AND POWER WIRING. DOING SO WILL
SAVE TIME AND LABOR LATER ON.
Figure 13
Figure 15
Figure 16
All Models RSD Damper Wiring
All Models ND, URD and SID Damper Wiring
Figure 14
On all these dampers and most older style
dampers, including competitor’s dampers,
always wire up number to number or designation
to designation.
Do not overload your transformer!
Contact EWC Controls Technical Support when you
are on the job site for assistance with damper wiring.
Have a Multi-Meter, pocket screw driver and wire
snips on hand.
Multiple ND and/or URD
Damper Wiring on a Single Zone
(2-4 Dampers)
Figure 17
EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- [email protected]
8
Either one
Not both
MA-RSD
A Spring Open Damper is wired to M1 & M6
A Spring Close Damper is wired to M1 & M4
All Models ESR Damper Wiring
ZONE
MOTOR
M1
M6
M4
M2
ZONE
MOTOR
M1
M6
M4
M2
ZONE
MOTOR
M1
M6
M4
M2
6
4
1
PC
PO
COM
6
4
1
PC
PO
COM
NOTE: Do not connect more
than 4 motor actuators in a
series configuration. That will
decrease the chances of poor
electrical connections and
voltage drop issues. If wiring
more than 4 dampers see figure
18.
6
4
1
PC
PO
COM

DAMPER WIRING CONTINUED
If you need to connect numerous dampers to a single zone, or you are using dampers of unknown current draw
such as Spring Types, Isolation relays and separate power supplies may be required. Parallel as many dampers
as you want as long the total current load of the motor actuators does not exceed the VA rating of the
transformer. Other factors should also be considered, such as the full load amp rating of the isolating relay
contacts, voltage drops from long wire runs and feeder conductor sizing to junction points.
NOTE: Some older style dampers and competitor’s dampers cannot be paralleled and must be isolated or wired
in tandem. Contact EWC Controls Technical Support for assistance.
EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- [email protected]
Non-inherently current limiting transformers must have field provided over-current protection on the secondary 24 vac output. The table values
provided pertain to genuine ULTRAZONE Dampers and Competitors typical 24vac Spring loaded dampers. Included in these VA load ratings are the
correct number of thermostats, the BMPlus Zone System, and a 5% field factor. Spring loaded dampers draw higher currents & require more power.
BMPlus 3000, 5000, 7000, Revision “B” Recommended Power Solutions
TESTING DAMPER MOTORS
SR / ESR / RSD Power Open / Spring Close Dampers - Connect 24vac common & hot to the two motor (M) terminals.
Damper should Open. Remove 24vac hot. Damper should Close.
ND / URD / SMD / BMD Dampers - Connect 24vac common to terminal 1 and 24vac hot to terminal 4. Damper should
Open. Remove 24vac hot from terminal 4 and apply to terminal 6. Damper should Close.
RDN / SMDL / BMDL Dampers - Connect 24vac common to terminal 1 and 24vac hot to terminals 2 and 4. Damper
should Open. Remove 24vac hot from terminal 4. Damper should Close.
SR / ESR / RSD Power Close / Spring Open Dampers - Connect 24vac common & hot to the two motor (M) terminals.
Damper should Close. Remove 24 vac hot. Damper should Open.
9
Spring Types
@ 8 VA
per damper
ND / URD’s
@ 2 VA
per damper
Transformer Size
60VA
75VA
30
22
19 26
15 23
40VA
12
9
5
These charts show the maximum
number of dampers that can be
connected to the entire
BMPlus3000/5000/7000 based on the
transformer being used.
Maximum number of dampers
per ZONE is 12.
Use Class 2 UL Listed 1585 Inherently
current limiting transformers only!
Figure 18
Variations on this diagram and other damper solutions are available.
6
4
1
PC
PO
COM
6
4
1
PC
PO
COM
6
4
1
PC
PO
COM
ZONE
MOTOR
M1
M6
M4
M2
6
4
1
PC
PO
COM
6
4
1
PC
PO
COM
6
4
1
PC
PO
COM
6
4
1
PC
PO
COM
6
4
1
PC
PO
COM
6
4
1
PC
PO
COM
6
4
1
PC
PO
COM
6
4
1
PC
PO
COM
6
4
1
PC
PO
COM
12 Dampers wired to a single zone.
BMPlus
3000
Zone Panel
BMPlus
5000
BMPlus
7000
Transformer Size
60VA
75VA
7
5
46
3 5
40VA
3
2
1
BMPlus
3000
Zone Panel
BMPlus
5000
BMPlus
7000

BMPlus 3000
LED’s
The BMPlus is equipped with 11 function specific LED’s that indicate HVAC system operation
and zone damper status. Familiarize yourself with the LED functions and definitions, in order to
accurately determine the Zoned HVAC system status and mode of operation.
STATUS
GREEN
SAS
RED
OAS
RED
FAN
ZONE 3
ZONE 2
ZONE 1
The STATUS LED pulses as a steady heart beat to indicate proper Microprocessor system status.
The OAS LED illuminates solid to indicate that the Outdoor Temperature has fallen below the chosen
set point. The OAS LED will blink rapidly to indicate a shorted or open Outdoor Air Sensor circuit.
The SAS LED illuminates solid to indicate that the Supply Temperature has exceeded the chosen
set point on either the HIGH TEMP LIMIT or the LOW TEMP LIMIT. The SAS LED will blink rapidly
to indicate a shorted or open Supply Air Sensor circuit.
The ZONE 3 LED will illuminate solid to indicate that damper(s) is energized open, and the Zone is active.
The ZONE 2 LED will illuminate solid to indicate that damper(s) is energized open, and the Zone is active.
The ZONE 1 LED will illuminate solid to indicate that damper(s) is energized open, and the Zone is active.
The FAN LED will illuminate solid to indicate a demand for fan operation, during COOLING, HEATING,
PURGE, or CONTINUOUS FAN operations.
Y1
Y2
W1/B
RED
W2/E
RED
The Y2 LED illuminates solid to indicate the 2nd stage of DX COOLING or DX HEATING is energized.
The Y1 LED illuminates solid to indicate the 1ST stage of DX COOLING or DX HEATING is energized.
The W1/B LED illuminates solid to indicate 1st stage of HEATING is energized in Gas/Hydronic mode.
The W1/B LED illuminates solid to indicate ‘B’ reversing valve is energized in HEAT PUMP operation.
NOTE: In Heat Pump Operation, this LED will stay illuminated after the call for heat is completed.
The W2/E LED illuminates solid to indicate 2nd or 3rd stage of HEATING is energized in GAS/HYDRONIC
or HEAT PUMP mode.
The W2/E LED illuminates solid to indicate EMERGENCY HEAT is energized in HEAT PUMP mode.
NOTES:
EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- [email protected]
10
LED’S
GREEN
GREEN
GREEN
GREENGREEN
GREENGREEN
YELLOW
YELLOW
GREENGREEN

BMPlus3000
3 Zone Main
Module
Rugged 10 pin
Expansion Header
Supply Air
Sensor
Connections
Outdoor Air
Sensor
Connections
Rugged Damper
Motor Terminal
Blocks
User Friendly
Adjustable
Potentiometers
On-Board
Emergency Switch
On-Board
CUTTABLE
Rc/Rh Link
Isolated HVAC
System
Terminal
Block
Rugged
Thermostat
Terminal
Blocks
Multi
Functional
Zone 1
Thermostat
Terminal
Block
Easy Setup
8 switch Bank
Dual Function
Reset
Button
Polarized
Power Input
Terminals
The BMPlus 3000 Zone Control System includes Module to Module Factory Wiring. We power up the Expansion Modules
for you. The XM2 Expansion module includes a Status LED and Damper Status LED’s.
See page 11 and 12 for drawing representations of a 5 and 7 zone system and appropriate dip switch settings.
All you have to do is:
1. Set the dip switches to your specific application.
2. Connect your thermostats, dampers and system wiring.
3. Power up the Main Module
4. Check System Operation.
5. Enjoy.
Protective
header cap not
shown for clarity
EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- [email protected] 11
Thermal Circuit
Breaker
Isolated Common
terminal. Useful
when HVAC
troubleshooting
System Status LED’s
Figure 19
J1
ZONE3
MOTOR
ZONE2
MOTOR
MOTOR
ZONE1
24
T’FORMER
VAC
SYSTEM
M6
M4
M2
M1
M6
M4
M2
M1
M6
M4
M2
M1
R
C
G
Y2
Y1
O
RH
RC
W1
B
W2
E
LINK
RH
RC
D
43
D
C
1
C
2
+
+
SAS
SAS
OAS
OAS
C
W/E
O/B
Y
R
G
ONE
ZONE
EM
NORM
SW
4
ZONE1
STAT
T
D
11
D
12
D
13
D
10
2
ND STAGE HEAT
DIFFERENTIAL
LIMIT
HIGH
TEMPLOW TEMP
LIMIT
TIMER OAS
STAGING
47
5
40
33
26
19
12
110
120
130 140 150
160
170
52
49
46
43
40
37
34
42
35
28
21
14
7
OFF
BMPlus3000 rev B
W
2
EM
B
1
W
1
2
Y
Y
ZONE
ZONE
ZONE
FAN
1
2
3
STATUS
OAS
SAS
38
39
R
R
R
37
R
36
R
76
77
R
72
R
73
R
R
70
69
R
67
R
68
R
65
R
R
64
71
R
R
63
62
R
R
61
60
R
59
R
58
R
R
57
56
R
55
R
54
R
R
78
79
R
53
R
52
R
R
51
50
R
49
R
48
R
R
47
46
R
45
R
81
R
R
40
43
R
R
42
41
R
10
LED
9
LED
8
LED
7
LED
6
LED
5
LED
4
LED
3
LED
2
LED
1
LED
11
LED
6
U
U
7
U
8
5
U
4
U
U
2
3
U
U
1
1
K
2
K
3
K
4
K
5
K
6
K
7
K
8
K
R
12
R
3
R
4
R
RESET
1
D
2
D
C
11
8
C
7
C
15
C
5
C
R
35
C
10
13
CY
1
21
D
1
Z
14
C
SW
3
33
R
32
R
31
R
30
R
8
D
29
R
R
28
27
R
26
R
7
D
25
R
R
24
23
R
22
R
6
D
21
R
R
20
R
19
5
D
D
934
R
GAS
OFF
OFF
OAS
HC
HP
OTHER
HP
TIMER
ON
HYDRONIC
ON
O B
DF
<
<
<
<
<
< >
>>
>
>>
>
<>
<
SYSTEM
HP CONV
50
TSTATS
RV
STAGING
RULE
SAS
FAN
E
W
C
SYSTEM
CONTROL
%
C
C
W/E
O/B
Y
R
G
ZONE3
STAT
T
F1
C
W/E
O/B
Y
R
G
9
C
66
R
82
R
R
44
R
14
R
R
15
16
U
9
12
C
R
13
ZONE2
STAT
T

BMPlus5000
DIP switch
settings
for 1st
Expansion
panel.
Zones 4 & 5
FACTORY
SUPPLIED
POWER & DATA
POLARIZED
BUS CABLE
Each expansion
module has a 2
position DIP
switch. Factory
set to insure the
main module
recognizes each
expansion
module in the
proper
sequence.
Setting the XM2
Expansion Panel
DIP Switches
Protective
header caps not
shown for clarity
DO NOT CONNECT
OR DISCONNECT
BUS CABLE
WHILE THE PANEL
IS POWERED.
To
Line
Voltage
24 vac transformer
Provide Over-Current
Protection
EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- [email protected]
12
J1
ZONE3
MOTOR
ZONE2
MOTOR
MOTOR
ZONE1
24
T’FORMER
VAC
SYSTEM
M6
M4
M2
M1
M6
M4
M2
M1
M6
M4
M2
M1
R
C
G
Y2
Y1
O
RH
RC
W1
B
W2
E
LINK
RH
RC
D
43
D
C
1
C
2
+
+
SAS
SAS
OAS
OAS
C
W/E
O/B
Y
R
G
ONE
ZONE
EM
NORM
SW
4
ZONE1
STAT
T
D
11
D
12
D
13
D
10
2
ND STAGE HEAT
DIFFERENTIAL
LIMIT
HIGH
TEMPLOW TEMP
LIMIT
TIMER OAS
STAGING
47
5
40
33
26
19
12
110
120
130 140 150
160
170
52
49
46
43
40
37
34
42
35
28
21
14
7
OFF
W
2
EM
B
1
W
1
2
Y
Y
ZONE
ZONE
ZONE
FAN
1
2
3
STATUS
OAS
SAS
38
39
R
R
R
37
R
36
R
76
77
R
72
R
73
R
R
70
69
R
67
R
68
R
65
R
R
64
71
R
R
63
62
R
R
61
60
R
59
R
58
R
R
57
56
R
55
R
54
R
R
78
79
R
53
R
52
R
R
51
50
R
49
R
48
R
R
47
46
R
45
R
81
R
R
40
43
R
R
42
41
R
10
LED
9
LED
8
LED
7
LED
6
LED
5
LED
4
LED
3
LED
2
LED
1
LED
11
LED
6
U
U
7
U
8
5
U
4
U
U
2
3
U
U
1
1
K
2
K
3
K
4
K
5
K
6
K
7
K
8
K
R
12
R
3
R
4
R
RESET
1
D
2
D
C
11
8
C
7
C
15
C
5
C
R
35
C
10
13
CY
1
21
D
1
Z
14
C
SW
3
33
R
32
R
31
R
30
R
8
D
29
R
R
28
27
R
26
R
7
D
25
R
R
24
23
R
22
R
6
D
21
R
R
20
R
19
5
D
D
934
R
E
W
C
SYSTEM
CONTROL
C
C
W/E
O/B
Y
R
G
ZONE3
STAT
T
F1
C
W/E
O/B
Y
R
G
9
C
66
R
82
R
R
44
R
14
R
R
15
16
U
9
12
C
R
13
M6
M4
M2
M1
M6
M4
M2
M1
C
W/E
O/B
Y
R
G
E
W
C
4
R
R
1
2
R
3
R
R
6
5
R
R
17
J1
16
R
R
15
14
R
13
R
12
R
R
11
10
R
23
R
21
R
R
19
37
R
22
RR
20
18
R
27
R
26
R
25
R
R
24
R
28
29
R
30
R
7
D
5
D
6
D
D
4
3
D
2
D
1
D
C
1
3
C
>
<
0
A
A
0
<>
2
1
U
5
U
3
U
1
STATUS
U
4
Y
1
K
1
+
K
2
1
Z
D
M
P
R
D
M
P
R
T
S
T
A
T
T
S
T
A
T
38
R
40
R
39
R
8
D
U
2
36
R
35
R
34
R
Figure 20
BMPlus3000 rev B
C
W/E
O/B
Y
R
G
ZONE2
STAT
T
GAS
OFF
OFF
OAS
HC
HP
OTHER
HP
TIMER
ON
HYDRONIC
ON
O B
DF
<
<
<
<
<
< >
>>
>
>>
>
<>
<
SYSTEM
HP CONV
50
TSTATS
RV
STAGING
RULE
SAS
FAN
%

M6
M4
M2
M1
M6
M4
M2
M1
C
W/E
O/B
Y
R
G
E
W
C
4
R
R
1
2
R
3
R
R
6
5
R
R
17
J1
16
R
R
15
14
R
13
R
12
R
R
11
10
R
23
R
21
R
R
19
37
R
22
RR
20
18
R
27
R
26
R
25
R
R
24
R
28
29
R
30
R
7
D
5
D
6
D
D
4
3
D
2
D
1
D
C
1
3
C
>
<
0
A
A
0
<>
2
1
U
5
U
3
U
1
STATUS
U
4
Y
1
K
1
+
K
2
1
Z
D
M
P
R
D
M
P
R
T
S
T
A
T
T
S
T
A
T
38
R
40
R
39
R
8
D
U
2
36
R
35
R
34
R
C
W/E
O/B
Y
R
G
BMPlus7000
DIP switch settings for
1st Expansion panel.
Zones 4 & 5
DIP switch settings for
2nd Expansion panel.
Zones 6 & 7
Setting the XM2
Expansion Panel
DIP Switches
Each expansion
panel has a 2
position DIP switch.
Factory set to insure
the main module
recognizes each
expansion module in
the proper sequence.
FACTORY
SUPPLIED
POWER & DATA
POLARIZED
BUS CABLE
To
Line
Voltage
24 vac transformer
Provide Over-Current
Protection
Figure 21
EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- [email protected] 13
J1
ZONE3
MOTOR
ZONE2
MOTOR
MOTOR
ZONE1
24
T’FORMER
VAC
SYSTEM
M6
M4
M2
M1
M6
M4
M2
M1
M6
M4
M2
M1
R
C
G
Y2
Y1
O
RH
RC
W1
B
W2
E
LINK
RH
RC
D
43
D
C
1
C
2
+
+
SAS
SAS
OAS
OAS
C
W/E
O/B
Y
R
G
ONE
ZONE
EM
NORM
SW
4
ZONE1
STAT
T
D
11
D
12
D
13
D
10
2
ND STAGE HEAT
DIFFERENTIAL
LIMIT
HIGH
TEMPLOW TEMP
LIMIT
TIMER OAS
STAGING
47
5
40
33
26
19
12
110
120
130 140 150
160
170
52
49
46
43
40
37
34
42
35
28
21
14
7
OFF
W
2
EM
B
1
W
1
2
Y
Y
ZONE
ZONE
ZONE
FAN
1
2
3
STATUS
OAS
SAS
38
39
R
R
R
37
R
36
R
76
77
R
72
R
73
R
R
70
69
R
67
R
68
R
65
R
R
64
71
R
R
63
62
R
R
61
60
R
59
R
58
R
R
57
56
R
55
R
54
R
R
78
79
R
53
R
52
R
R
51
50
R
49
R
48
R
R
47
46
R
45
R
81
R
R
40
43
R
R
42
41
R
10
LED
9
LED
8
LED
7
LED
6
LED
5
LED
4
LED
3
LED
2
LED
1
LED
11
LED
6
U
U
7
U
8
5
U
4
U
U
2
3
U
U
1
1
K
2
K
3
K
4
K
5
K
6
K
7
K
8
K
R
12
R
3
R
4
R
RESET
1
D
2
D
C
11
8
C
7
C
15
C
5
C
R
35
C
10
13
CY
1
21
D
1
Z
14
C
SW
3
33
R
32
R
31
R
30
R
8
D
29
R
R
28
27
R
26
R
7
D
25
R
R
24
23
R
22
R
6
D
21
R
R
20
R
19
5
D
D
934
R
GAS
OFF
OFF
OAS
HC
HP
OTHER
HP
TIMER
ON
HYDRONIC
ON
O B
DF
<
<
<
<
<
< >
>>
>
>>
>
<>
<
SYSTEM
HP CONV
50
TSTATS
RV
STAGING
RULE
SAS
FAN
E
W
C
SYSTEM
CONTROL
%
C
C
W/E
O/B
Y
R
G
ZONE3
STAT
T
F1
C
W/E
O/B
Y
R
G
9
C
66
R
82
R
R
44
R
14
R
R
15
16
U
9
12
C
R
13
M6
M4
M2
M1
M6
M4
M2
M1
C
W/E
O/B
Y
R
G
E
W
C
4
R
R
1
2
R
3
R
R
6
5
R
R
17
J1
16
R
R
15
14
R
13
R
12
R
R
11
10
R
23
R
21
R
R
19
37
R
22
RR
20
18
R
27
R
26
R
25
R
R
24
R
28
29
R
30
R
7
D
5
D
6
D
D
4
3
D
2
D
1
D
C
1
3
C
>
<
0
A
A
0
<>
2
1
U
5
U
3
U
1
STATUS
U
4
Y
1
K
1
+
K
2
1
Z
D
M
P
R
D
M
P
R
T
S
T
A
T
T
S
T
A
T
38
R
40
R
39
R
8
D
U
2
36
R
35
R
34
R
C
W/E
O/B
Y
R
G
ZONE2
STAT
T
BMPlus3000 rev B
Protective
header caps not
shown for clarity
DO NOT CONNECT
OR DISCONNECT
BUS CABLE
WHILE THE PANEL
IS POWERED.

G
R
W
C
ZONE 3 THERMOSTAT
HEAT
Y
68
To Line Voltage.
Provide Over-Current
Protection.
24vac transformer
40va
OUTDOOR
HEAT PUMP
2STAGE GAS
FURNACE
ND / URD DAMPERS
SUPPLY AIR SENSOR OUTDOOR AIR SENSOR
BMPlus 3000Wiring Diagram
Dual Fuel Heat Pump
Auxiliary Heat Activates via
OutdoorairTemperature or
HeatPump Thermostat EmergencyInput
Allwiring shouldbedone to local and
national codesand ordinances. Use
color-coded, multi-conductor wire. Wire
number to number or lettertoletter on
eachcontrol.
WARNING: THESE PANELSARE DESIGNED
FOR USE WITH 24VAC. DO NOTUSE OTHER
VOLTAGES! USE CAUTIONTOAVOID
ELECTRICSHOCK OREQUIPMENTDAMAGE.
EWCControls Inc. 385 Highway 33 Englishtown, NJ07726 800-446-3110 FAX 732-446-5362 E-Mail- info@ewccontrols.com
J1
ZONE3
MOTOR
ZONE2
MOTOR
MOTOR
ZONE1
24
T’FORMER
VAC
SYSTEM
M6
M4
M2
M1
M6
M4
M2
M1
M6
M4
M2
M1
R
C
G
Y2
Y1
O
RH
RC
W1
B
W2
E
LINK
RH
RC
D
43
D
C
1
C
2
+
+
SAS
SAS
OAS
OAS
C
W/E
O/B
Y
R
G
ONE
ZONE
EM
NORM
SW
4
ZONE1
STAT
T
D
11
D
12
D
13
D
10
2
NDSTAGEHEAT
DIFFERENTIAL
LIMIT
HIGH
TEMP
LOW TEMP
LIMIT
TIMER OAS
STAGING
47
5
40
33
26
19
12
110
120
130140150
160
170
52
49
46
43
40
37
34
42
35
28
21
14
7
OFF
W
2
EM
B
1
W
1
2
Y
Y
ZONE
ZONE
ZONE
FAN
1
2
3
STATUS
OAS
SAS
38
39
R
R
R
37
R
36
R
76
77
R
72
R
73
R
R
70
69
R
67
R
68
R
65
R
R
64
71
R
R
63
62
R
R
61
60
R
59
R
58
R
R
57
56
R
55
R
54
R
R
78
79
R
53
R
52
R
R
51
50
R
49
R
48
R
R
47
46
R
45
R
81
R
R
40
43
R
R
42
41
R
10
LED
9
LED
8
LED
7
LED
6
LED
5
LED
4
LED
3
LED
2
LED
1
LED
11
LED
6
U
U
7
U
8
5
U
4
U
U
2
3
U
U
1
1
K
2
K
3
K
4
K
5
K
6
K
7
K
8
K
R
12
R
3
R
4
R
RESET
1
D
2
D
C
11
8
C
7
C
15
C
5
C
R
35
C
10
13
CY
1
21
D
1
Z
14
C
SW
3
33
R
32
R
31
R
30
R
8
D
29
R
R
28
27
R
26
R
7
D
25
R
R
24
23
R
22
R
6
D
21
R
R
20
R
19
5
D
D
934
R
GAS
OFF
OFF
OAS
HC
HP
OTHER
HP
TIMER
ON
HYDRONIC
ON
O B
DF
<
<
<
<
<
<>
>>
>
>>
>
<>
<
SYSTEM
HPCONV
50
TSTATS
RV
STAGING
RULE
SAS
FAN
E
W
C
SYSTEM
CONTROL
%
C
C
W/E
O/B
Y
R
G
ZONE3
STAT
T
F1
C
W/E
O/B
Y
R
G
9
C
66
R
82
R
R
44
R
14
R
R
15
16
U
9
12
C
R
13
6
4
1
PC
PO
COM
6
4
1
PC
PO
COM
6
4
1
PC
PO
COM
Y2
O/B
X/W
R
C
Y1
O/B
W1
W2
R
C
Y1
G
R
W
C
ZONE 2 THERMOSTAT
HEAT
Y
72
G
R
W
C
ZONE1 THERMOSTAT
HEAT
Y
70
ZONE2
STAT
T
Y2
G
BMPlus3000 rev B

ZONE 3 THERMOSTAT
HEAT
68
GR
YW
C
24vac transformer
40va
ND / URDDAMPERS
SUPPLYAIR SENSOR
BMPlus 3000 WiringDiagram
2STAGE GAS HEAT WITH 2 STAGEA/C
2nd Stage Heat & 2nd Stage Cool Activates via
The Adjustable Timer.
2 STAGE GAS
FURNACE
OUTDOOR
CONDENSING
UNIT
All wiringshould be done to local
and nationalcodesandordinances.
Use color-coded, multi-conductor
wire. Wire number to number or
letter to letter on each control.
WARNING: THESEPANELS ARE DESIGNED
FOR USE WITH24VAC. DO NOT USE OTHER
VOLTAGES! USECAUTION TO AVOID ELECTRIC
SHOCKOREQUIPMENTDAMAGE.
EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- [email protected]
To Line Voltage.
Provide Over-Current
Protection.
J1
ZONE3
MOTOR
ZONE2
MOTOR
MOTOR
ZONE1
24
T’FORMER
VAC
SYSTEM
M6
M4
M2
M1
M6
M4
M2
M1
M6
M4
M2
M1
R
C
G
Y2
Y1
O
RH
RC
W1
B
W2
E
LINK
RH
RC
D
43
D
C
1
C
2
+
+
SAS
SAS
OAS
OAS
C
W/E
O/B
Y
R
G
ONE
ZONE
EM
NORM
SW
4
ZONE1
STAT
T
D
11
D
12
D
13
D
10
2
ND STAGE HEAT
DIFFERENTIAL
LIMIT
HIGH
TEMPLOW TEMP
LIMIT
TIMER OAS
STAGING
47
5
40
33
26
19
12
110
120
130 140 150
160
170
52
49
46
43
40
37
34
42
35
28
21
14
7
OFF
W
2
EM
B
1
W
1
2
Y
Y
ZONE
ZONE
ZONE
FAN
1
2
3
STATUS
OAS
SAS
38
39
R
R
R
37
R
36
R
76
77
R
72
R
73
R
R
70
69
R
67
R
68
R
65
R
R
64
71
R
R
63
62
R
R
61
60
R
59
R
58
R
R
57
56
R
55
R
54
R
R
78
79
R
53
R
52
R
R
51
50
R
49
R
48
R
R
47
46
R
45
R
81
R
R
40
43
R
R
42
41
R
10
LED
9
LED
8
LED
7
LED
6
LED
5
LED
4
LED
3
LED
2
LED
1
LED
11
LED
6
U
U
7
U
8
5
U
4
U
U
2
3
U
U
1
1
K
2
K
3
K
4
K
5
K
6
K
7
K
8
K
R
12
R
3
R
4
R
RESET
1
D
2
D
C
11
8
C
7
C
15
C
5
C
R
35
C
10
13
CY
1
21
D
1
Z
14
C
SW
3
33
R
32
R
31
R
30
R
8
D
29
R
R
28
27
R
26
R
7
D
25
R
R
24
23
R
22
R
6
D
21
R
R
20
R
19
5
D
D
934
R
GAS
OFF
OFF
OAS
HC
HP
OTHER
HP
TIMER
ON
HYDRONIC
ON
O B
DF
<
<
<
<
<
< >
>>
>
>>
>
<>
<
SYSTEM
HP CONV
50
TSTATS
RV
STAGING
RULE
SAS
FAN
E
W
C
SYSTEM
CONTROL
%
C
C
W/E
O/B
Y
R
G
ZONE3
STAT
T
F1
C
W/E
O/B
Y
R
G
9
C
66
R
82
R
R
44
R
14
R
R
15
16
U
9
12
C
R
13
6
4
1
PC
PO
COM
6
4
1
PC
PO
COM
6
4
1
PC
PO
COM
Y2
G
Y2
C
R
Y1
W1
W2
R
C
Y1
ZONE 1 THERMOSTAT
HEAT
70
GR
YW
C
ZONE 2 THERMOSTAT
HEAT
72
GR
YW
C
ZONE2
STAT
T
BMPlus3000 rev B

ISOLATING 24vac SHORTS
Dampers not responding and THE
BMPLUS 3000 LED’s are off.
HVAC system not responding and
BMPLUS 3000 LED’s are off.
DETECTING 24vac SHORTS
Check HVAC & BMPlus system transformer supply voltage.
Check HVAC & BMPlus system 24vac transformer voltage, fuse & the BMPlusB
circuit breaker.
Check HVAC & BMPlus system wiring for shorts/miswiring.
Check HVAC system wiring for shorts/miswiring.
Check HVAC system wiring for proper connections.
Check HVAC thermostat for proper connections.
Refer to Technical Bulletin for correct Setup/Wiring/Dip Switch settings.
Check HVAC system wiring for proper connections.
Check HVAC system wiring for shorts/miswiring.
Check HVAC System.
Refer to Technical Bulletin for correct Setup/Wiring/Dip Switch settings.
SOLUTIONS
TROUBLESHOOTING
REFER TO THE DAMPER MOTOR TESTING PAGE 9
LED’s illuminate and HVAC system
functions normally but dampers do
not respond.
Check damper motor wiring for proper connections.
Check damper motor 24vac transformer voltage/fuse/BMPlus circuit breaker.
Check damper motor wiring for shorts/miswiring.
Refer to Technical Bulletin for correct Setup/Wiring.
F1 circuit breaker protects the
BMPlus 3000 and reacts to a short in
the damper motor or thermostat
component and field wiring.
CHECK YOUR WIRING
EWC Controls provides superior toll free Troubleshooting Support for the BMPlus 3000 when you are on the job site!
Call 1-800-446-3110 Monday - Friday 8am to 5pm EST
Otherwise call 1-732-446-3110 for information on the BMPlus 3000 and other ULTRA-ZONE products..
When calling for Technical Support, please have a multi-meter, pocket screwdriver, and wire cutter/stripper handy.
TECHNICAL SUPPORT
LED’s do not illuminate and HVAC
system does not respond.
LED’s are not responding properly
and HVAC system is malfunctioning.
LED’S are responding properly but
HVAC system is malfunctioning.
SYMPTOM
Disconnect the wire(s) from the ‘R’ terminals on the BMPlus 3000 thermostat
terminal blocks , and the “M2/M4/M6’’ terminals on the BMPlus 3000 damper
motor terminal blocks. Restore power. If the short is no longer present, Ohm
out the thermostat and damper field wiring for shorts/misconnections. Replace
or repair wires as necessary. Restore power. Module(s) will resume operation.
SOLUTIONS: Remove 24vac power from BMPlus 3000 and allow circuit breaker to cool!
Find and repair short(s) in damper and/or thermostat field wiring. Restore 24 vac power.
If 24vac short has occurred, 24vac will be present at the BMPlus 3000 Module
Input terminals R & C; but 24vac will not be present at the Thermostat R&C.
SYMPTOMS: Module(s) appear to be dead!
TESTING THERMOSTATS
Check to make sure that the thermostat Rc and Rh terminals are connected together, unless your application requires
separation of these circuits.
Use the (C) Common terminal provided at each thermostat terminal block to wire up full 24 vac hard-wired thermostats.
You should reference the (C) Common terminal when troubleshooting incoming thermostat demand signals, even if no wire is
connected there.
Make sure that you wire and configure your thermostats for the correct application. Most thermostats built today can be field
configured to operate as regular Heat/ Cool type or as Heat Pump type. Remember that you can use regular Heat/Cool
thermostats on the BMPlus 3000 for Heat Pump applications.
EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- [email protected]
16
Other manuals for BMPlus 3000
1
This manual suits for next models
2
Table of contents
Other EWC Controls Controllers manuals
Popular Controllers manuals by other brands

Pentair
Pentair AVID XA+ Installation & operating instructions

Phaeton
Phaeton HT-MPPT-48V 30A user manual

Brink
Brink Air for life Installation regulations

kincrome
kincrome K13350 instruction manual

Burkert
Burkert 8605 Series operating instructions

Siemens
Siemens BACnet PTEC Dual Duct 2 AVS installation instructions