Content
Product information 7
Scope of supply 7
Technical specications 8
Construction and components 9
Installation 11
Fitting 11
Electrical wiring 12
Operation and conguration 13
Troubleshooting 13
UK Conformity Assessed 14
Declaration of Conformity 15

Disposal
Electrical and electronic equipment (EEE) often contain materials, components and substances
that may harm the environment or be hazardous to your health. Products (WEEE) marked with
the ‘crossed-out wheeled bin’ symbol should be disposed of separately from other waste at
the end of its life. Though legislation may differ from country to country we strongly advise
that electrical and electronic waste is separated from other waste and disposed of according to
national legislation to protect the environment and personnel that may come into contact with
waste.
How to use this manual
This manual has been prepared based on the specific product and
contains relevant technical information and installations guides.
Accessories and spare parts are not covered by this manual.
Please refer to the individual manuals of these components.
This installation manual does not contain any system design documentation.
Failure to observe instructions marked with a danger symbol
may result in personal injury and/or damage to the product.
Errors and omissions excepted.

Disposal
Electrical and electronic equipment (EEE) often contain materials, components and substances
that may harm the environment or be hazardous to your health. Products (WEEE) marked with
the ‘crossed-out wheeled bin’ symbol should be disposed of separately from other waste at
the end of its life. Though legislation may differ from country to country we strongly advise
that electrical and electronic waste is separated from other waste and disposed of according to
national legislation to protect the environment and personnel that may come into contact with
waste.
How to use this manual
This manual has been prepared based on the specific product and
contains relevant technical information and installations guides.
Accessories and spare parts are not covered by this manual.
Please refer to the individual manuals of these components.
This installation manual does not contain any system design documentation.
Failure to observe instructions marked with a danger symbol
may result in personal injury and/or damage to the product.
Errors and omissions excepted.
Symbols
The following symbols may be used in the manual
to draw attention to danger or risk of personal
injury or damage to the product.
General prohibition
Failure to observe instructions marked with the prohibited
symbol may result in extreme danger or serious personal injury.
General warning
Failure to observe instructions marked with a danger symbol
may result in personal injury and/or damage to the product.
General attention
Marks a dangerous situation that, in the worst-case scenario,
can cause serious personal injury or significant damage to the product.
Electricity hazard/High Voltage
Marks a situation in which caution is advised due to the risk of high voltage electric
shock which can cause serious personal injury or significant damage to the product.
Connect an earth terminal to the ground
Failure to observe instructions marked with a danger symbol
may result in personal injury and/or damage to the product.
Permitted and approved
Permitted and approved method of installation.
Prohibited and not approved
Prohibited and not approved method of installation.

Warning
To minimise the risk of fire, electric shock, personal injury
and/or damage to the product please observe the following:
• Please always read the manual and only use the product in accordance with the
manufacturer’s instructions. If in doubt, contact one of the Exodraft specialized dealers.
• All installations must be carried out by properly qualifi ed personnel in accordance with
national legislation and regulations.
• This product must be earthed. Get assistance from an qualifi ed electrician when in doubt.
• This product must always be disconnected under the installation.
• Prior to servicing the product, disconnect the power and ensure that it cannot accidentally
be reconnected.
• Exodraft always recommends the use of a smoke alarm when a solid fuel open fire is
installed.
• If the Exodraft fan system has been designed for solid fuel/multi fuel installations, please
ensure that the design meets the requirements of BS EN15287-1. If this cannot be achie-
ved, a smoke alarm must be installed in the same room as the heat appliance.
UK
Your energy. Optimized.

UK |7
3112038_XTP150G_UK
Warning
To minimise the risk of fire, electric shock, personal injury
and/or damage to the product please observe the following:
• Please always read the manual and only use the product in accordance with the
manufacturer’s instructions. If in doubt, contact one of the Exodraft specialized dealers.
• All installations must be carried out by properly qualifi ed personnel in accordance with
national legislation and regulations.
• This product must be earthed. Get assistance from an qualifi ed electrician when in doubt.
• This product must always be disconnected under the installation.
• Prior to servicing the product, disconnect the power and ensure that it cannot accidentally
be reconnected.
• Exodraft always recommends the use of a smoke alarm when a solid fuel open fire is
installed.
• If the Exodraft fan system has been designed for solid fuel/multi fuel installations, please
ensure that the design meets the requirements of BS EN15287-1. If this cannot be achie-
ved, a smoke alarm must be installed in the same room as the heat appliance.
UK
Your energy. Optimized.
Product information
XTP150G is a high-precision pressure transducer specially developed for gas systems. It can also be used
with oil-red or solid-fuel systems.
In order to comply with the provisions of the Gas Appliances Directive 90/396/EEC:
• XTP150G must be connected to an EBC22 or
• XTP150G must be connected to a third party automatic gas control system with built-in “fail safe”
inputs (GAD)
Incorrect use may result in problems with soot, chimney res, etc. which might damage the product.
Please check out this site for advice about the product:
www.exodraft.com
Scope of supply
• XTP150G
• Silicone hose Ø 5 mm
• Installation manual and user instructions
Warranty
All Exodraft products are covered by a 2-year guarantee as per European consumer rights legislation. For
some countries an extended period of guarantee may apply depending on either national legislation or
other clearly stipulated conditions. Customer complaints must be handled by a specialised dealer or who-
lesaler (preferably where the Exodraft product has been bought originally). An updated list of Exodraft
specialised dealers can be found on our website for the country in question.
Exodraft products must always be installed by properly qualied personnel. Exodraft reserves the right to
change these guidelines without prior notice.
The warranty and liability does not cover instances regarding personal injury or damage to property or the
product that can be ascribed to one or more of the following causes:
• Failure to follow this installation and operation manual
• Incorrect installation, start-up, maintenance or servicing
• Improper repairs
• Unauthorised structural modications made to the product
• Installation of additional components that have not been tested/approved with the product
• Any damage resulting from continued use of the product despite an evident defect
• Failure to use original spareparts and accessories
• Failure to use the product as intended
• Exceeding or failure to meet the limit values in the technical data
• Force majeure

8|UK
Your energy. Optimized.
Technical specications
Technical data
Description XTP150G
H x W x D [mm] 90 x 115 x 55
Weight 237 g
Material: Box: Light grey polycarbonat
(PC)
Ingress Protection IP65
Pressure range 15 Pa – 150 Pa +/- 0.1%
Full scale
Ambient temperature -25 °C – +50 °C
Storage temperature: -25 °C – +50 °C
Connection terminals: Screw: max. 1.5 wire
Cable length Max. 100 m, min. 0.75 wire
Project:
Material:
Date:
Rev.:
Title:
Rev. No.: Ref.:
Format: A3
Weight:
Approved:
Draw. No.:
Sheet:
XTP150
19-11-2012
XTP150
PMN
DS/EN 22768 m
Unless otherwise specified tolerances are after
0,000 kg
1 of 4
108
55,1
55,1
80
80
28
14,2
Description Inputs
Supply 15 V DC – 35 V DC
Power Consumption,
absolut max: < 75 mA
Power Consumption,
nominel 60 mA
Description Outputs
Output 0-10 V DC, max. 10 mA
Alarm relay output (max) 48 V/2 A
Alarm relay contact
materiel AgCdO
Description Miscellaneous
Tolerable overload 20.000 Pa
Medium Air and exhaust gases
Responce time < 0.2s
Resolution from digital
sensor 0.01Pa
Repeatability +/- 0.1 % Full scale
Combined non-linearity
and hysteresis +/- 0.05 % Full scale
Offset longtime drift 1 year +/- 0.7 Pa max.
Temperature drift +/- 1.0 % Full scale
Transfer ratio 0.6 (250 Pa signal/150 Pa
output)
55
118
104
115
Fig. 1

UK |9
3112038_XTP150G_UK
ADIP switch
B Operating LED
CZero-point calibration button
DCable connector
E Mounting holes
F(-) Valve (P2)
G (+) Valve (P1)
HStatus LED
IConnecting terminals
JPressure transducer
Construction and components
The XTP150G is certied by GASTEC and have the certication number
PIN: 0063 BU1711
90
115
60 15
103640
Ø4,5
4x
NO NC
G
A
J
B
C
D
E
F
H
I
Fig. 2

10 |UK
Your energy. Optimized.
Key to g. 2-A
DIP switch Setting Function Factory setting OFF ON
ON RSN
1234
1 Calibration enabled OFF Calibration not possible Calibration possible
2 Not used OFF
3 Not used OFF
4 Not used OFF
Key to g. 2-B
Operating LED Indication Function
PIC # 1
PIC # 2
Flashing YELLOW Processor OK
Constant YELLOW Unit is not working
Not lit Unit is not working
Key to g. 2-C
Zero-point
calibration button
To activate Function
Press and hold for 5 s Calibration of zero point
Key to g. 2-D
Operating LED Indication Function
Constant GREEN Normal operation
Flashing RED Alarm (or DIP switch 1 is ON)

UK |11
3112038_XTP150G_UK
Installation
Fitting
The XTP150G must be tted with the hose connectors facing down.
For negative-pressure measurement, t the pressure hose to the (-) valve (g. 2-F)
For positive-pressure measurement, t the pressure hose to the (+) valve (g. 2-G)
Outdoor
If there is a risk of adverse effect from strong winds, the hose located inside the XTP150 can be removed
from the (+) valve. Interlter should be tted to the external (+) valve. The lter is not supplied by Exodraft.
Do not blow into the valves on the XTP150
Fig. 3
Fig. 4
NO NC
B
A

12 |UK
Your energy. Optimized.
Electrical wiring
ATTENTION! Electrical wiring of the controller must be carried out in accordance
with national legislation and regulations. Earth must always be connected.
Terminals
XTP150G is connected to the screw terminals as shown below.
Terminal Description
1BUS connection
2BUS connection
3+24 V DC Supply in
4– 0 V DC Supply in
5 – 0 V DC Signal out
6 0–10 V DC Signal out
7C – Common
8 NO – Relay is open
9NC – Relay is closed
NB! Max. 100 metre cable, min. 0.75 wire.

UK |13
3112038_XTP150G_UK
Operation and conguration
Calibration should only be carried out if a positive value is registered on the 0–10 V output, when the
connection hose is disconnected.
How to calibrate the XTP150G sensor
• Disconnect the connection hose
• Set DIP switch 1 to ON (g. 2-A)
• Press and hold button for 5 seconds (g. 2-C)
• Release button
• Set DIP switch 1 to OFF (g. 2-A)
Troubleshooting
Observation Operating LED (Fig. 2-B) Status LED (Fig. 2-H) Solution
Unit cannot be calibrated Constant GREEN Set DIP switch 1 to ON. Status LED
changes to ashing RED
Operating LED not ashing
(g. 2-B)
No change • Check 24 V connection at terminals
3+4
• Check polarity (– / – and + / +)
• Disconnect power for 5 seconds
• Reconnect power.
Status LED ashing
(g. 2-H)
Flashing RED • Check DIP switch 1 is OFF
• Check hose connection on the
transducer (g. 2-K)
• Unit is faulty

UK Conformity Assessed
Exodraft a/s
Industrivej 10
DK-5550 Langeskov
Hereby declares that the following products:
Were manufactured in conformity with the provisions of the following regulations:
The Supply of Machinery (Safety) Regulations 2008
Electrical Equipment (Safety) Regulations 2016
Electromagnetic Compatibility Regulations 2016
Langeskov, 01-11-2022
Managing Director
Anders Haugaard
UK Conformity Assessed
XTP150G

Declaration of Conformity
DK: EU-Overensstemmelseserklæring
GB: Declaration of Conformity
DE: EU-Konformitätserklärung
FR: Déclaration de conformité de l’Union Européenne
NO: EU-Samsvarserklæring
PL: EU Deklaracja zgodności
NL: EU-Conformiteits verklaring
SE: EU-Överensstämmelsedeklaration
FI: EU-Vaatimustenmukaisuusvakuutus
IS: ESS-Samræmisstaðfesting
IT: Dichiarazione di Conformità Unione Europea
Exodraft a/s
Industrivej 10
DK-5550 Langeskov
Erklærer på eget ansvar, at følgende produkter:
Hereby declares that the following products:
Erklärt hierdurch auf eigene Verantwortung, daß folgende Produkte:
Déclare, sous sa propre responsabilité, que les produits suivants:
Erklærer på eget ansvar at følgende produkter:
Niniejszym oświadcza, że następujące produkty:
Veklaart dat onderstaande producten:
Deklarerar på eget ansvar, att följande produkter:
Vastaa siltä, että seuraava tuote:
Staðfesti à eigin àbyrgð, að eftirfarandi vörur:
Dichiara con la presente che i seguenti prodotti:
Som er omfattet af denne erklæring, er i overensstemmelse med følgende
standarder:
Were manufactured in conformity with the provisions of the following stand-
ards:
Die von dieser Erklärung umfaßt sind, den folgenden Normen:
Auxquels s’applique cette déclaration sont en conformité avec les normes
ci-contre:
Som er omfattet av denne erklæring, er i samsvar med følgende standarder:
Zostały wyprodukowane zgodnie z warunkami określonymi w następujących
normach:
Zijn vervaardigd in overeenstemming met de voorschriften uit de hieronder
genoemde normen en standaards:
Som omfattas av denna deklaration, överensstämmer med följande standard-
er:
Jota tämä selvitys koskee, on seuraavien standardien mukainen:
Sem eru meðtalin i staðfestingu Pessari, eru i fullu samræmi við eftirtalda
staðla:
Sono stati fabbricati in conformità con le norme degli standard seguenti:
EN 60335-1, EN 60335-2-80, DS/EN ISO 12100: 2011
I.h.t bestemmelser i direktiv:
In accordance with
Entsprechen gemäß den Bestimmungen der folgenden Richtlinien:
Suivant les dispositions prévues aux directives:
I.h.t bestemmelser i direktiv:
Zgodnie z:
En voldoen aan de volgende richtlijnen:
Enligt bestämmelserna i följande direktiv:
Seuraavien direktiivien määräysten mukaan:
Med tilvisun til àkvarðana eftirlits:
In conformità con le direttive:
Maskindirektivet:
The Machinery Directive:
Richtlinie Maschinen:
Directive Machines:
Maskindirektivet:
Dyrektywą maszynową:
De machinerichtlijn:
Maskindirektivet
Konedirektiivi:
Vèlaeftirlitið:
Direttiva Macchinari:
2006/42/EF/-EEC/-EWG/-CEE
Lavspændingsdirektiv:
The Low Voltage Directive:
Niederspannungsrichtlinie:
Directive Basse Tension:
Lavspenningsdirektivet:
Dyrektywą Niskonapięciową
De laagspanningsrichtlijn:
Lågspänningsdirektivet:
Pienjännitedirektiivi:
Smáspennueftirlitið:
Direttiva Basso Voltaggio:
2014/35/EC
EMC-direktivet:
And the EMC Directive:
EMV-Richtlinie:
Directive Compatibilité Electromagnétique:
EMC-direktivet:
Dyrektywą EMC – kompatybilności elektromagnetycznej
En de EMC richtlijn:
EMC-direktivet:
EMC-direktiivi:
EMC-eftirlitið:
Direttiva Compatibilità Elettromagnetica:
2014/30/EC
Langeskov, 01-11-2022
Adm. direktør
Managing Director
Anders Haugaard
Algemeen directeur
Geschäftsführender Direktor
Président Directeur Général
Verkställande direktör
Toimitusjohtaja
Framkvemdastjori
Direttore Generale
Declaration of Conformity
XTP150G

DK: Exodraft a/s
Industrivej 10
DK-5550 Langeskov
Tel: +45 7010 2234
Fax: +45 7010 2235
info@exodraft.dk
www.exodraft.dk
SE: Exodraft a/s
Kalendevägen 2
SE-302 39 Halmstad
Tel: +46 (0)8-5000 1520
info@exodraft.se
www.exodraft.se
NO: Exodraft a/s
Storgaten 88
NO-3060 Svelvik
Tel: +47 3329 7062
info@exodraft.no
www.exodraft.no
UK: Exodraft Ltd.
24 Janes Meadow, Tarleton
GB-Preston PR4 6ND
Tel: +44 (0)1494 465 166
Fax: +44 (0)1494 465 163
info@exodraft.co.uk
www.exodraft.co.uk
DE: Exodraft a/s
Niederlassung Deutschland
Soonwaldstr. 6
DE-55569 Monzingen
Tel: +49 (0)6751 855 599-0
Fax: +49 (0)6751 855 599-9
info@exodraft.de
www.exodraft.de
FR: Exodraft sas
78, rue Paul Jozon
FR-77300 Fontainebleau
Tel: +33 (0)6 3852 3860
info@exodraft.fr
www.exodraft.fr
Your energy. Optimized.
3112038_XTP150G_UK |201222
This manual suits for next models
1
Table of contents
Other Exodraft Transducer manuals
Popular Transducer manuals by other brands

Omega
Omega RH62C-MV manual

CONTINENTAL CONTROL SYSTEMS
CONTINENTAL CONTROL SYSTEMS WattNode Pulse Quick install guide

Fairchild
Fairchild T5220 Installation, operation and maintenance instructions

B-band
B-band UST installation manual

Airmar
Airmar R599LM Owner's guide and installation instructions

Garmin
Garmin GT8HW-TM installation instructions