Faget EM2020 Instructions and recipes

FAGET BV Tel.: ++31 (0) 521533333
Postbus 12, 8330AA Steenwijk Fax: ++31 (0) 521533398
Nederland E-mail: sales@faget.nl
FAGET
Installation and start up instructions
EM2020
Selectable AC transducer
4189300016A (UK)
•Watt or var transducer
•Supply and measuring voltage up to 690V
•Configuration via PC-interface possible
•35 mm DIN rail or base mounting

Description
EM2020 is a micro controller based power transducer with 1 analog output for
measurement of Watt or var. The transducer holds no mechanical moving parts like
potentiometers and therefore the calibration stability is excellent.
Label
The configured transducer is provided with a label with the following data:
The un-configured transducer is provided with a label with the following data:
Faget´s order ack. no. can be
found on a paper label on the
transducerbox.
About configuration see special
manual.
FAGET
Type designation Faget´s order ack. no. To be stated
when contacting Faget
Coupling
Measuring range
Primary values
Output range
Output limited
to ±22mA
Auxiliary voltage
Condition of external
voltage transformer
Condition of external
current transformer
Max. output load
current output
Min. output load
voltage output
Distributor´s ID
Other information
If. special product
Measuring range
Secondary values
FAGET

Installation and start up instructions, EM2020
4189300016A (UK)
Mounting instructions
EM2020 is designed for panel
mounting, being mounted on a
35 mm DIN rail, or by means
of two 4-mm screws.
Weight: Approx. 0.650 kg
The design of the transducer makes mounting of it close to similar equipment
possible, however make sure there is min. 50 mm between the top and bottom of the
transducer and other equipment.
The DIN rail must always be placed horizontally when several transducers are
mounted on the same rail.

Connection diagram
It is not necessary to protect the measuring voltage inputs. But it is recommended to
use a 2A fuse for the supply input (terminals 1 and 3).
The transducer is protected against ESD (electrostatic electricity), and further special
protection against this during the mounting of the transducer is not necessary.

Installation and start up instructions, EM2020
4189300016A (UK)
The voltage inputs are connected as follows, if the current transformers are placed in
other phases than indicated in the above diagram:
2W3/2var3
External current transformer Connect
Connected to
L1 (23 + 24) and L2 (29 + 30)
L1
to term. no. 17
L3
to term. no. 19
L2
to term. no. 21
Connected to
L2 (23 + 24) and L3 (29 + 30)
L2
to term. no. 17
L1
to term. no. 19
L3
to term. no. 21
Couplings 1W/1var and 1W4/1var4: Connect terminal no. 17 to the phase to
which the external current transformer is connected.
1W3/1var3
External current transformer Connect
Connected to L2 L2
to term. no. 17
L3
to term. no. 19
L1
to term. no. 21
Connected to L3 L3
to term. no. 17
L1
to term. no. 19
L2
to term. no. 21
Connection / set up
The transducer is equipped with a red LED for indication of wrong phase connection
or errors in the calibration / configuration. This LED is placed under the front plate.
The function of the LED is as follows:
Constant light. The wiring may be wrong. There is not equal power direction on all
phases. There must be signal on all inputs to ensure correct testing and current flow
in all phases. Note this function is only activated in coupling 2W3, 2var3 and 3W3(4),
3var3(4).
Fast pulse 5Hz. The calibration data are corrupted. Contact Faget BV.
Slow pulse 1Hz. The configuration data are wrong or corrupted. Make a re-
configuration or contact Faget BV. About configuration see special manual.

Opening of the unit
Mounting of the front panel
The front panel is
removed by means of a
screwdriver.
The front
panel may be loosened
in the right side first and
is then totally demounted
by moving the screw-
driver towards left.
Press with a screwdriver as
indicated by the arrow and press
the front panel down with your
thumb, simultaneously. It is
recommended that one side of
the front panel snaps into place
before the other.

Installation and start up instructions, EM2020
4189300016A (UK)
Technical specifications
Accuracy: Class 0.5 (-10…15…30…55°C) according to IEC 60688
Meas. current (In) 0.75/1.5/3.0/6.0A Meas. range: 0…200% In
In can be set between 0.375…6A
Overload, currents: 20A max., continuously
75A max. for 10 s
240A max. for 1 s
Load: Max. 0.5VA per phase
Meas. voltage (Un): 73/140/254/400V phase to neutral
Meas. range (Un): 30…120%Un(57...400V)
Un can be set between 57…400V
127/240/440/690V phase to phase
Meas. range(Un): 30…120%Un(100...690V)
Un can be set between 100…690V
Overload, voltages: 1.2 x Unmax., continuously, 2 x Unmax. for 10 s
Load: Min. 480k
Frequency range: 30…45…65…80Hz
Note: For fundamental frequency (1. harmonic) outside 20Hz
…80Hz the input is fixed to 0
Indication: Red LED function:
(The LED is located behind the front plate)
Incorrect wiring = constant light, only active for coupling 1W3,
2W3, 3W3(4) and 1var3, 2var3, 3var3(4)
Calibration error = flash frequency 5Hz
Configuration error = flash frequency 1Hz
Other ranges possible
Output: 1 analog output
Standard range: Output (0...100%):
0...1mA, 0...5mA, 0...10mA, 0...20mA, 0...1V, 0...5V, 0...10V
Output (10...100%):
0.1...1mA, 0.5...5mA, 1...10mA, 2...20mA, 0.1...1V, 0.5...5V,
1...10V
Output (20...100%):
0.2...1mA, 1...5mA, 2...10mA, 4...20mA, 0.2...1V, 1...5V,
2...10V
Output (-100...0...100%):
-1...0...1mA, -5...0...5mA, -10...0...10mA, -20...0...20mA,
-1...0...1V, -5...0...5V, -10...0...10V

Limit: Max. ±120% of nominal output
Output load: Current: Max. 10V (max. 1k)
Voltage: Max. 20mA
Ambient temperature: -10…55oC (nominal)
-25…70oC (operating)
-40…70oC (storage)
Temperature
coefficient: Max. ±0.2% of full scale per 10°C
Response time: Coupling 2W3/2var3, 3W3/3var3, 3W4/3var4 <225ms,
typically 200ms
Coupling 1W/1var, 1W3/1var3, 1W4/1var4 <150ms,
typically 125ms
Ripple: Twice the class index according to IEC 60688 (1%pp)
Galvanic separation: Between inputs, outputs and aux. supply: 3750V-50Hz-1 min.
Supply voltage: 57.7-63.5-100-110-127-200-220-230-240-380-400-415-440-
450-660-690VAC ±20%
24-48-110-220VDC -25/+30%
Consumption: (Aux. supply) 3.5VA/2W
Climate: HSE, to DIN 40040
EMC: According to EN 50081-1/2, EN 50082-1/2
Protection: Housing: IP40. Terminals: IP20, to IEC 529 and EN 60529
Connections: Max. 2.5mm² multi-stranded
Max. 4.0mm² single-stranded
Materials: All plastic parts are self-extinguishing to UL94 (V1)
Weight: 0.650kg
This manual suits for next models
1
Popular Transducer manuals by other brands

Simrad
Simrad ES38B - REV E Dimensions

SonoSite
SonoSite TEExi user guide

SonoSite
SonoSite TEExp user guide

Electro-Voice
Electro-Voice 3-Inch High Frequency Neodymium Transducer... Technical specifications

Mianyang Weibo Electronic
Mianyang Weibo Electronic WBV415S01 user manual

Theta Digital
Theta Digital 30P operating manual

Geokon
Geokon 4450 instruction manual

Asco
Asco Power Manager Xp 5200 Series Operator's manual

Ashcroft
Ashcroft GC55 Installation and maintenance instructions

Airmar
Airmar TRIDUCER P23 Owner's guide & installation instructions

Balluff
Balluff BTL5-C/E1 Series Condensed guide

Shark
Shark 100T quick start guide