The PCZ-528.3 control timer is a universal programmable timer
that combines the features of an astronomical, weekly and an-
nual timer.
»256 programs for switching the relay on/off;
»Each of the programs can be executed in one of the seven date
intervals defined in the annual cycle;
»Ability to enter up to 32 holidays and select which programs
will run on holidays;
»For each of the work programs, it can be independently deter-
mined whether the program will be executed in an hourly cyc-
le (fixed hour and minute) or in an astronomical cycle (related
to the position of the sun in relation to the horizon);
»In each of the astronomical programs, it is possible to set an in-
dependent shift of switching on/off in relation to the selected
astronomical point (e.g. turn on one hour before sunset, turn
off two hours after dusk);
Purpose
Features of the timer
F&F Filipowski sp. j.
Konstantynowska 79/81, 95-200 Pabianice, POLAND
phone/fax (+48 42) 215 23 83 / (+48 42) 227 09 71
www.fif.com.pl; e-mail: biuro@fif.com.pl
Do not dispose of this device in the trash along with other waste!
According to the Law on Waste, electro coming from households free of charge and can
give any amount to up to that end point of collec� on, as well as to store the occasion of
the purchase of new equipment (in accordance with the principle of old-for-new, regard-
less of brand). Electro thrown in the trash or abandoned in nature, pose a threat to the
environment and human health.

- 2 -
»For each of the programs, you can freely choose which days of
the week it will be performed;
»Possibility to program the timer with the free PCZ Konfigurator
mobile application using the NFC* short-range radio commu-
nication system;
»Possibility to protect the clock settings with a PIN code;
»Advanced work time counter that allows you to measure the
receiver activation time:
– on the current day and month;
– monthly, from the last 12 months;
– total from the moment the clock was first started.
»Auxiliary, resettable, work time counter;
»Possibility of limiting the total time of the receiver activation
(up to a maximum of 99999 hours);
»Control input that allows connection of momentary external
button;
»Backlit LCD display with with adjustable brightness and con-
trast levels;
»Replaceable 2032 type battery to keep the clock running in
case of power failure**.
* Remote programming requires an Android phone with built-in NFC com-
munication and free PCZ Configurator app (downloadable from Google
Play store). NFC communication range is limited to a few centimeters, so a
direct phone-to-timer connection is required to transfer the configuration
from the app to the timer.
** In the event of a power failure, the internal battery will only support the
internal clock so that the current time and date will not be lost. In the
event of a power failure, all external timer functions, such as the display
and relay, remain disabled.

- 3 -
The PCZ-528.3 clock controller can operate in one of the three
modes of operation:
»Automatic mode
Operation in automatic mode involves the automatic proces-
sing of all programs stored in the memory of the controller.
»Semi-automatic mode
Semi-automatic mode means a temporary interruption of
operation in automatic mode and the possibility of manually
switching the relay contact to the opposite position. The timer
operation in semi-automatic mode is indicated by blinking of
the timer dial on the controller display. Operation in semi-au-
tomatic mode is stopped when the next operating program
is activated, after which the controller returns to automatic
mode.
»Manual mode
In manual mode, the list of programs stored in the memory
of the controller is ignored and switching on/off is performed
manually by the user.
In manual mode, the state of the relay can be changed by brie-
fly pressing the +/– button on the front of the controller or an
external button connected to the timer control input.
Functioning

- 4 -
Display description

- 5 -
Display Mode Relay status
Automatic ON
Automatic ON
Semi-automatic ON
Semi-automatic OFF
Manual ON
Manual OFF
Legend:
ON
Blinks/pulses
OFF
Operation mode indication

- 6 -
Button Description
MENU
Press the button to enter the controller
configuration mode.
In parameter editing mode, pressing Menu
abandons the edited parameter (without
remembering the changes made) and returns
to the parent menu level.
OK
Press the button in edit mode to edit the next
setting item. If you are editing the last item,
pressing the OK button will save the new
parameter value, exit the edit mode and go
to the parent menu level.
Pressing the OK button in the time display
mode will bring up a quick access menu
allowing you to view information about the
current date, details of the currently running
program, and access to operating time
statistics..
continued on next page
Control buttons

- 7 -
Button Description
+
(Up)
In edit mode, pressing the button increases
the value of the edited parameter by 1.
If the button is pressed for a long time, the
parameter value will cyclically increase by 1.
In manual operation mode, pressing the
button will switch the contact permanently
(ON -> OFF or OFF->ON).
In automatic operation mode, pressing
the button toggles between automatic and
semi-automatic mode.
–
(Down)
In edit mode, pressing the button decreases
the value of the edited parameter by 1.
If the button is pressed for a long time, the
parameter value will cyclically decrease by 1.
In manual operation mode, pressing the
button will switch the contact permanently
(ON -> OFF or OFF->ON).
In automatic operation mode, pressing
the button toggles between automatic and
semi-automatic mode.
Control buttons cont.

- 8 -
1. Turn off the power.
2. Install the clock on the rail in the distribution box.
3. Connect the power cables according to the diagram.
4. Connect receivers according to the diagram.
5. Set the correct date and time.
6. Make software configuration of the clock.
Mounting
Controller diagram

- 9 -
1 COM relay power supply
2 L power supply
3 N power supply
4 control input (triggered by L/N/+ level)
5 NC contact (normally closed)
6 NO contact (normally open)
Wiring diagram

- 10 -
The full version of the manual for the PCZ-528 timer can
be downloaded from www.fif.com.pl from the product
subpage or by using the QR code below:
The control application is available free of charge in the Google
Play store:
The NFC connection uses very short-range communica-
tion, which means that you need to directly touch the
phone to the front of the programmed controller.
Mobile app

- 11 -
power supply 24÷264 V AC/DC
maximum load current (AC-1) 16 A
contact separated 1×NO/NC
backup time clock operation 6 years*
battery type 2032 (lithium)
backup time display operation none
accuracy of the clock 1 s
error time ±1 s/ 24 h
power consumption 1.5 W
terminal 2.5 mm² scrrew terminals (cord)
4.0 mm² screw terminals (wire)
tightening torque 0.5 Nm
working temperature -20÷50°C
dimensions 2 modules (35 mm)
mounting on TH-35 rail
ingress protection IP20
* Battery life depends on operating conditions and how long the timer is
powered by battery only. Low ambient temperature greatly reduces the
life of the battery.
Technical data

- 12 -
The F&F products are covered by a warranty of the 24 months
from the date of purchase. Effective only with proof of purchase.
Contact your dealer or directly with us.
F&F Filipowski sp. j. declares that the device is in conformity
with the essential requirements of Directive 2014/53/EU of the
European Parliament and of the Council of 16 April 2014 on the
harmonization of the laws of the Member States relating to the
making available on the market of radio equipment and repe-
aling Directive 1999/5/EC.
The CE Declaration of Conformity, along with the references to
the standards in relation to which conformity is declared, can be
found at www.fif.com.pl on the product page.
Warranty
CE declaration
E220809
Table of contents
Other F&F Timer manuals