Faraday 8742 User manual

Air Duct Monitoring Housings
Installation Instructions
Models 8741,8742 and 8743
P/N 315-049708FA-4
INTRODUCTION Models 8741, 8742 and 8743 are air duct monitoring hous-
ings containing sampling tubes. When used with a compat-
ible smoke detector, smoke and combustion products are
detected for shutdown of the duct system and/or operation
of supplementary equipment as provided by the system
control panel. See the following chart for usage.
ledoMsrotceteDelbitapmoCyaleR
14784588
,
0178
,
3178oN
24784588seY
34780178
,
3178seY
FF
FF
Foror
oror
or compatcompat
compatcompat
compatible control equipment,ible control equipment,
ible control equipment,ible control equipment,
ible control equipment, see csee c
see csee c
see charhar
harhar
harts on the pagets on the page
ts on the pagets on the page
ts on the page
11
11
12 of this manual.2 of this manual.
2 of this manual.2 of this manual.
2 of this manual.
TECHNICAL DATA AIR DUCT CONDITIONS
Temperature Range:
32OF (0OC) - 100OF (38OC) per UL 268/268A
Altitude Range:
8741, 8742 and 8743 — No altitude limitations
Relative Humidity Range:
10-85% (non-condensing/non-freezing)
Air Duct Velocity Range:
100-4000 ft/min – 8741, 8742 and 8743
Sampling Tube Pressure Range of Differences:
Greater than 0.01 and less than 1.2 inches of water column
These air duct detectors are designed for detection and
control of products of combustion in a duct system. TheyThey
TheyThey
They
are not to be used forare not to be used for
are not to be used forare not to be used for
are not to be used for open area protopen area prot
open area protopen area prot
open area protectect
ectect
ection.ion.
ion.ion.
ion.
DO NOT USE air duct detectors with Alarm Verification.

P/N 315-049708FA-42
APPLICATION The 8741, 8742 and 8743 duct smoke detectors provide early
detection of smoke and products of combustion present in
air moving through an HVAC duct supply, return, or both.
These devices are designed to prevent the recirculation of
smoke in areas by the air handling system’s fans and blow-
ers. Complete systems may be shut down in the event of
smoke detection.
For the correct installation of a duct smoke unit please refer
to NFPA 72 (National Fire Alarm Code), NFPA 90A (Standard
for Installation of Air Conditioning and Ventilation Systems),
NFPA 70 (National Electrical Code) and NFPA 92A (Recom-
mended Practice for Smoke Control Systems).
OPERATION When the Models 8741, 8742 and 8743 are operating, a
sample of air is drawn from the duct and passed through the
sampling chamber by means of the input sampling tube. The
air sample passes through the smoke detector mounted in
the duct housing and is exhausted back into the duct
through the outlet tube.
This detector is equipped with cover removal switch (SW1) that
instantly provides a trouble condition upon removal of the clear
cover. For all testing and inspection with the cover removed, the
cover removal switch (designated as SW1 on PCB) must be
manually depressed to simulate normal operation.
LED Indicator The 8741, 8742 and 8743 contain an LED indicator (located on
the smoke detector) capable of flashing either one of three
distinct colors: green, yellow, or red. During each flash interval,
the microprocessor based detector checks the following:
• for smoke in its sensing chamber
• that its critical smoke sensing electronics are operating.
Based on the results of these checks, the LED indicator
flashes as follows:
)sdnoceS(lavretnIhsalF
hsalF roloCnoitidnoC45880178/3178
neerG.noitarepoyrosivrepuslamroN74
wolleY siro)riaperro
gninaelc(ecivresseriuqerrotceteD .snoitacificepslatnemnorivnestidnoyebgnitarepo 03-74
deRmralA½24
sehsalFoN.ri
aperseriuqerro,derewoptonsirotceteD--

3 P/N 315-049708FA-4
Figure 2
Recommended Locations in Duct Systems
RETURN
AIR
SUPPLY
AIR
AIR DUCT
HOUSING
AIR DUCT
HOUSING
DAMPER
BLOWER
FILTER
PLENUM
FRESH AIR INTAKE
DAMPER
TYPE A: CLOSED SYSTEM - NO EXHAUST
D D
TYPE B: PROVISION FOR EXHAUSTING
SOME PERCENTAGE OF RETURN AIR
RETURN
AIR
SUPPLY
AIR
AIR DUCT
HOUSING
AIR DUCT
HOUSING
DAMPER
DAMPER
BLOWER
FILTER
PLENUM
FRESH AIR INTAKE
DAMPER
D D
EXHAUST AIR
OUTPUT
DAMPER
TYPE C: RETURN AIR UNDER POSITIVE PRESSURE
FROM SEPARATE BLOWER
EXHAUST AIR
OUTPUT
DAMPER
RETURN
AIR
SUPPLY
AIR
AIR DUCT
HOUSING
RETURN AIR
BLOWER
AIR DUCT
HOUSING
DAMPER
DAMPER
BLOWER
FILTER
PLENUM
FRESH AIR INTAKE
DAMPER
D D
Figure 1
Typical Mounting of Duct Housing
OUTLET
TUBE
INPUT
SAMPLING
TUBE
CENTER
LINE
OF DUCT
C
L
MOUNTING THE AIR DUCT HOUSING
Location on Duct System
This guideline contains general information on duct smoke
detector installation, but does not preclude the NFPA
documents listed. Siemens Industry, Inc. assumes no
responsibility for improperly installed duct detectors.To
determine the correct installation position for an 8741, 8742
or 8743 duct smoke detector, the following factors must be
considered.
1) A uniform non-turbulent (laminar) airflow between 100 ft/
min. to 4,000 ft/min. must be present in the HVAC duct.
To determine duct velocities, examine the engineering
specifications that define the expected velocities or use
an Alnor model 6000AP velocity meter (or equivalent).

P/N 315-049708FA-44
2) To minimize the impact of air turbulence and stratification
on performance, a duct smoke detector should be
located as far as possible downstream from any obstruc-
tion (i.e. deflector plates, elbows, dampers, etc.). In all
situations, confirmation of velocity and pressure differen-
tial within specifications is required.
The pressure differential between the input sampling
(high pressure) tube and outlet (low pressure) tube for
the 8741, 8742 or 8743 duct smoke detector should be
greater than 0.01 inches of water and less than 1.2
inches of water.
3) Identify a code compliant location (supply or return side,
or both) for the installation of the duct unit that will
permit easy access for viewing and serviceability.
4) When installing on the return side, install duct units prior
to the air being exhausted from the building or diluted
with outside “fresh” air.
5) When installing duct smoke units downstream of filters,
fires occurring in the filters will be detected, but if the
filters become blocked, insufficient air flow through the
duct unit will prevent the correct operation of the duct
detector. Duct units installed in the supply air side may
monitor upstream equipment and/or filters.
6) Where possible, install duct detectors upstream of air
humidifiers and downstream of dehumidifiers.
7) To prevent false alarms, the duct detector should not be
mounted in areas of extreme high or low temperatures,
in areas where high humidity exists, or in areas where
the duct may contain gases or excessive dust.
Duct Preparation The 8741, 8742 and 8743 Housings come with an installation
kit that contains the following items:
• Short return (outlet) sampling tube
• Stopper
• Two #12 x 3/4” sheet metal screws
• Mounting template (packaged separately)
Remove mounting template from the installation kit. Remove
paper backing from the mounting template and affix it to the
duct at the desired location. Using the template as a guide,
drill (2) mounting holes, 3/32" (2.5mm) for the #12 X 3/4”
sheet metal screws packaged in the installation kit. Drill or

5 P/N 315-049708FA-4
punch (2) 1¼” (32mm) holes for input sampling and outlet
tubes, using the template as a guide. Clean all holes.
Sampling Tube Installation
The 8741, 8742 and 8743 duct smoke detectors use a
specially notched sampling tube, which may be ordered
separately in one of four standard lengths.
ST-10 For duct widths of 6" to 1.0’
ST-25 For duct widths of 1.0’ to 3.0’
ST-50 For duct widths of 3.0’ to 5.0’ (requires support)
ST-100* For duct widths of 5.0’ to 10.0’ (requires support)
*This model is supplied as two 5 ft. sections with a coupling.
Assembly is required for installation.
Each model is manufactured with a different number and
size of sampling holes. Only the specific tube must be used
for the specified duct width.
Standard sampling tubes are steel tubes with air intake holes
drilled the entire length of the tube. These tubes can be cut
to length and must span at least 80% the width of the duct.
Sampling tubes over 3.0’ must be supported on the opposite
side of the duct. To ensure the correct operation, the red
stopper (stopper in installation kit) must be inserted in the
end of the air input sampling tube. If the input tube protrudes
through the opposite side of the duct, the opening around
the tube must be sealed. For custom duct widths, always
use the next longest standard size and cut down to the exact
requirement.
Once the airflow direction has been determined (refer to Figure
3), insert the input and outlet tubes into the duct housing.
INPUT TUBE HOLES
FACE AIR FLOW
INSERT RED STOPPER
THIS END OF INPUT TUBE
OUTLET TUBE INSTALLED
DOWNSTREAM OF AIRFLOW
DO NOT INSERT RED STOPPER
AIR FLOW DIRECTION
DUCT WIDTH
TUBE SUPPORT ONLY FOR DUCTS GREATER THAN 3 FEET WIDE
NOTE: Mountings shown
are typical. Detectors can
be installed side, bottom
or top of duct as long as
proper tube operation and
flow/pressure performance
is maintained.
Figure 3
Sampling Tube Orientation

P/N 315-049708FA-46
1. Remove the cover from the housing.
2. Loosen the screw and rotate the tube retainer until the
input tube is inserted and oriented properly. Ensure that
the notched end of the tube is inside the housing and
that the air input sampling tube is positioned so that the
input holes are directly facing the airflow.
3. Once the tube is installed, rotate the retainer back into
place and tighten screw.
4. Install the outlet tube in the remaining position. Once
the tube is installed, rotate the retainer back into place
and tighten screw.
Mounting After securing the input and outlet tubes to the duct smoke
unit, (or initially placing the tubes through the 1¼” holes
drilled or punched in the HVAC duct to accept the input and
outlet tubes and then attaching them to the duct unit), hold
the duct unit assembly in position and use (2) # 12 X 3/4”
sheet metal screws (packaged in the installation kit) to secure
the duct smoke detector to the HVAC duct sheet metal.
Air Duct Sampling Tube Pressure Measurement
The Model 8883 Pressure Differential Measuring device
should be used to ensure that the sampling tube pressure
differential is within the specified limits. The differential
pressure between the two tubes should be greater than 0.01
inches of water and less than 1.2 inches of water. Qualified
personnel should take measurements in accordance with
the 8883 instructions, P/N 315-085535FA.
WIRING
Conduit Knockouts To remove plastic knockout, first cut the plastic tab on the
specific knockout. Refer to Figure 4 to locate the tab. Then,
using a screw driver placed at the tab location, tap with a
hammer until the knockout breaks out. Clean the hole before
installing conduit.
PLASTIC TAB
KNOCKOUT
SIDE REAR OF AIR DUCT HOUSING
KNOCKOUT FACTORY
REMOVED
Figure 4
Removing the Knockouts

7 P/N 315-049708FA-4
Wiring The 8741, 8742 and 8743 should be connected as shown in
Figures 5 and 6. Note any limitations on the number of
detectors and restrictions on the use of remote devices
permitted for each circuit.
The 8741 is used with the 8713 detector in the MPC-6000/
MPC-7000 System.The 8743 must be used for the relay
version. Also, all optional accessories in the same loop must
be compatible with the detector series being used. These
devices should be interconnected as shown in Figure 6 and
wired to the FDLC. (Refer to the FDLC Installation Instruc-
tions, P/N 315-447360FA, or the MPC-6000/MPC-7000
Manual, P/N 315-447309, as applicable.) 8710 and 8713 are
polarity insensitive detectors. Line 1 and Line 2 can be either
line of the loop. Note any limitations on the number of
detectors and restrictions on the use of remote devices
permitted for each circuit.
When replacing a detector with a different model, be aware
that existing detector accessories connected to the base or
air duct housing that were compatible with the old detector
may not be compatible with the new detector. Always read
the Installation Instructions accompanying the detector to
determine detector and accessory compatibility.
Installation Of Smoke Detectors
To Install:
• Remove cover by loosening the four screws.Take off the
cover and set it aside.
• Align detector with base and insert detector.
• Rotate detector clockwise while gently pressing on it
until the detector drops fully into base.
• Then rotate the detector clockwise until it stops and
snaps in place.
• Replace cover and tighten the four screws.
To Remove:
• Rotate the detector counterclockwise until stop is
reached.
• Pull detector out of base.

P/N 315-049708FA-48
LOOP WIRES.
SEE COMPATIBLE
CONTROL
EQUIPMENT TABLE.
NO
COM
NC
LOOP WIRES.
SEE COMPATIBLE
CONTROL
EQUIPMENT TABLE.
TO NEXT DETECTOR
OR EOL DEVICE
(1A)
TO REMOTE DEVICE
(6)
CNTL
+
-
(5)
-+
+
-
ALARM CONTACTS
125 VAC, 24 VDC, 2.5A
SEE NOTE 2
DEVICE
REMOTE
DEVICE LOOP
-
DEVICE LOOP
+
LOOP/REM
-
DEVICE
CONTROL
NOT USED
LOOP/REM
+
MODEL 8741
TO NEXT DETECTOR
OR EOL DEVICE
+
-
TO SECOND
REMOTE DEVICE
(SEE MULTIPLE
REMOTE DEVICES)
REM+
-
+
REM-
CONTL
REMOTE
ALARM
RELAY
COMNC NO
+
-
CNTL
-
+ +
DEVICE
LOOP
MODEL 8742
NOTE:
EOL DEVICE MUST BE
COMPATIBLE WITH
SYSTEM INITIATING
CIRCUIT. OBSERVE
PROPER POLARITY
WHERE APPLICABLE.
(6)
(5)
(1A)
TB1 TB1
8854 8854
NOTES:
1. Up to 30 air duct housings can be
installed on one initiating circuit,
except as noted in Note 2.
2. When an 8742 is used to control a fire
safety function, the 8742 must be the
ONLY device on the initiating circuit.
3. Do not use looped wire under base
terminal.
4. Break wire run to provide supervision
of connection.
5. The green grounding screw in the
wiring compartment of the air duct
housing is not used.
Figure 5
Typical Connections for the 8741 / 8742 Using 8854 Detectors
If remote devices are supported by the initiating
circuit, each detector/base may have up to 2
remote devices with the following configurations
and restrictions only:
MULTIPLE REMOTE DEVICES
Remote
Device 1
8741
8741
Remote
Device 2
8845, 8849
8844, 8848
Restrictions
See Note 2
See Note 2
†
SEE REMOTE DEVICE
INSTRUCTIONS FOR
WIRING DETAILS:
DEVICE
8845, 8849
8844, 8848
INSTALLATION
INSTRUCTIONS
P/N 315-094925FA
P/N 315-094926FA
If the relay contacts are
being used to control 120
VAC operated equipment,
ensure that the conduit is
properly attached to the
internal metal ground strap,
using the proper conduit
locking nuts. Failure to
provide proper grounding
may result in fatal
electrical shock and
violation of national and
local codes.

9 P/N 315-049708FA-4
Figure 6
Typical Connections for the 8741 / 8743 Using 8710 and 8713 Detectors
NOTES:
1. The relay contacts are shown after a reset pulse, which represents the non-alarm condition.
2. Refer to the 8727W / 8727C Installation Instructions, P/N 315-033230FA.
3. The green grounding screw in the wiring compartment of the air duct housing is not used.
LINE 2
LINE 1
NOT USED
LINE1OR2
TO REMOTE TB1
OTHER LINE
TO REMOTE TB3
COM
NO
NC
NO
DEVICE
LOOP
OTHER
LINE
LINE
1OR2
RELAY
ALARM
COM NC
COM
NO
NC
TB2
(6 or 5)
TB3
(5 or 6)
TB1
(1A)
TB1 TB1 TB1
MODEL 8741 MODEL 8743 MODEL 8743
8710
8713
OPTIONAL REMOTE ALARM
INDICATOR MODEL 8727C OR 8727W
SEE NOTE 2
LOOP WIRES.
SEE COMPATIBLE CONTROL
EQUIPMENT TABLE.
8710
8713
TO NEXT
ADDRESSABLE
DEVICE
ALARM CONTACTS
125 VAC, 24 VDC, 2.5A
SEE NOTE 1
ALARM CONTACTS
125 VAC, 24 VDC, 2.5A
SEE NOTE 1
NO
DEVICE
LOOP
OTHER
LINE
LINE
1OR2
RELAY
ALARM
COM NC
8710
8713
TO REMOTE TB2
If the relay contacts
are being used to
control 120 VAC
operated equipment,
ensure that the
conduit is properly
attached to the
internal metal
ground strap, using
the proper conduit
locking nuts. Failure
to provide proper
grounding may
result in fatal
electrical shock
and violation of
national and local
codes.

P/N 315-049708FA-410
TESTING Only qualified service personnel should test these units. To
assure proper operation of the detector and control panel,
both the Sensitivity and the Functional tests should be
conducted. The minimum test schedule may be found in the
current edition of NFPA 72 for installations in the U.S.
Sensitivity Test The 8854 detector monitors its smoke sensitivity automati-
cally and requires no test equipment. A green flash of the
detector LED about every seven seconds indicates that the
smoke sensitivity is within its listed limits.
The following detector models are analog types that must
be programmed for the air duct application using the
control unit configuration tool; that is, CIS-4.
To test the 8713/8710 detector refer to its installation instruc-
tions. See Table A on page 11.
These tests ensure that the detector is within its listed and
marked sensitivity range. For additional instructions on
applying the Sensitivities mode, refer to the 8720 Manual,
P/N 315-033260FA.
Functional Test Smoke Testing
Using TG-11 smoke test canister with testing nozzle model
AD-TGN (purchased separately) available from Siemens
Industry, Inc., insert the test gas nozzle into the hole in the
red test plug in the unit cover. Press can against cover for
about 1/2second to release gas into the chamber.
DO NODO NO
DO NODO NO
DO NOT SPRAT SPRA
T SPRAT SPRA
T SPRAY GAY GA
Y GAY GA
Y GAS FOR MORES FOR MORE
S FOR MORES FOR MORE
S FOR MORE
THAN ½ SECONDTHAN ½ SECOND
THAN ½ SECONDTHAN ½ SECOND
THAN ½ SECOND..
..
.OO
OO
OVER-VER-
VER-VER-
VER-
USE OFUSE OF
USE OFUSE OF
USE OF
TESTES
TESTES
TEST GAT GA
T GAT GA
T GAS MAS MA
S MAS MA
S MAY RESULY RESUL
Y RESULY RESUL
Y RESULT IN DETECTT IN DETECT
T IN DETECTT IN DETECT
T IN DETECTOR CONOR CON
OR CONOR CON
OR CONTT
TT
TAMI-AMI-
AMI-AMI-
AMI-
NANA
NANA
NATION.TION.
TION.TION.
TION.
After 15 to 20 seconds the detector will go into alarm,
illuminating the detector LED and causing the duct unit
functions to operate; alarm relays will change state, and the
alarm related remote accessories, if attached, will function.
If no test gas is available to conduct functional testing,
remove cover and, while holding down the cover removal
switch, blow smoke from a smoldering cotton wick or punk
directly at the head to cause an alarm.The alarm indicator on
the detector should illuminate within one minute.

11 P/N 315-049708FA-4
Refer to the following Installation Instructions for additional
information on testing each of these detectors:
The 8710 and 8713 can also be tested individually using the
8720. Refer to the 8720 Manual, P/N 315-033260FA.
MAINTENANCE The performance of the air duct detector unit may be
adversely affected by dirt or foreign matter on the sampling
tubes or detector. If the air holes in the input sampling tube
become restricted, the unit cannot receive a proper air
sample, and performance is impaired. It is recommended
that the sampling tubes be checked and cleaned periodically.
The detector maintenance program should consist of
periodic cleaning of dust from the detector head by using a
vacuum cleaner. For cleaning Models 8854, 8713 or 8710,
refer to the detector’s Installation Instructions (See Table A).
The cleaning and test program is recommended for 6 month
intervals, or more frequently, if needed, depending on the
individual detector environment. Consult your local code and
AHJ requirements for required maintenance schedules.
UnderUnder
UnderUnder
Under no circumstno circumst
no circumstno circumst
no circumstances is the detances is the det
ances is the detances is the det
ances is the detectorector
ectorector
ector porpor
porpor
portt
tt
tion of the unition of the unit
ion of the unition of the unit
ion of the unit
to be disassembled by anto be disassembled by an
to be disassembled by anto be disassembled by an
to be disassembled by anyy
yy
yone otherone other
one otherone other
one other than an authorizthan an authoriz
than an authorizthan an authoriz
than an authorizeded
eded
ed
FF
FF
Faradaarada
aradaarada
araday Sy S
y Sy S
y Syy
yy
ystst
stst
stemsems
emsems
ems
TT
TT
Tecec
ecec
echnician.
hnician.
hnician.hnician.
hnician. FF
FF
Foror
oror
or service,service,
service,service,
service, contcont
contcont
contact yact y
act yact y
act yourour
ourour
our
nearest authoriznearest authoriz
nearest authoriznearest authoriz
nearest authorized Fed F
ed Fed F
ed Faradaarada
aradaarada
araday Sy S
y Sy S
y Service Rervice R
ervice Rervice R
ervice Representepresent
epresentepresent
epresentatat
atat
atii
ii
ive.ve.
ve.ve.
ve.
If the fire alarm syIf the fire alarm sy
If the fire alarm syIf the fire alarm sy
If the fire alarm systst
stst
stem is connectem is connect
em is connectem is connect
em is connected to a central sted to a central st
ed to a central sted to a central st
ed to a central statat
atat
ation orion or
ion orion or
ion or firefire
firefire
fire
depardepar
depardepar
department,tment,
tment,tment,
tment, oror
oror
or operatoperat
operatoperat
operates extes ext
es extes ext
es external devices sucernal devices suc
ernal devices sucernal devices suc
ernal devices such as fans,h as fans,
h as fans,h as fans,
h as fans, extext
extext
extin-in-
in-in-
in-
guishers,guishers,
guishers,guishers,
guishers, etc.,etc.,
etc.,etc.,
etc., connectconnect
connectconnect
connected,ed,
ed,ed,
ed, not
not
notnot
notify appropriatify appropriat
ify appropriatify appropriat
ify appropriate personnel ande personnel and
e personnel ande personnel and
e personnel and
disconnect the extdisconnect the ext
disconnect the extdisconnect the ext
disconnect the external devices unternal devices unt
ernal devices unternal devices unt
ernal devices until all til all t
il all til all t
il all tests are completests are complet
ests are completests are complet
ests are completed.ed.
ed.ed.
ed.
AfAf
AfAf
Aftt
tt
terer
erer
er tt
tt
testest
estest
esting,ing,
ing,ing,
ing, reset the syreset the sy
reset the syreset the sy
reset the systst
stst
stem,em,
em,em,
em, reconnect the devices,reconnect the devices,
reconnect the devices,reconnect the devices,
reconnect the devices, and notand not
and notand not
and notifyify
ifyify
ify
the personnel that the sythe personnel that the sy
the personnel that the sythe personnel that the sy
the personnel that the systst
stst
stem is operatem is operat
em is operatem is operat
em is operating aging ag
ing aging ag
ing again.ain.
ain.ain.
ain.
AELBAT
rotceteD noitallatsnI noitcurtsnI
4588AF891490-513
3178AF092330-513
0178AF092330-513

COMPATIBLE CONTROL EQUIPMENT
ELECTRICAL RATINGS FOR 8713 AND 8710
Electrical ratings are not provided here for these detectors.
Guidance for detector loop loading, along with loop wire
electrical specifications are provided in the applicable control
unit instructions given in the above Compatible Control
Equipment tables.
Siemens Industry, Inc.
Building Technologies Division
Florham Park, NJ P/N 315-049708FA-4
ROTCETED4588GNISU2478DNA1478 tnempiuqEeludoM reifitnedIytilibitapmoC /noitallatsnIeludoM snoitcurtsnIgnir
iW
5078)0007-CPM/0006-CPM(5-AF058430-513N/P
104-WL 3-AF799590-513N/P
)104-WL(A4-EZWL 4-AF810690-513N/P
)104-W
L(A8-EZWL 3-AF220690-513N/P
ROTCETED3178RO0178GNISU3478DNA1478 tnempiuqEeludoM reifitnedIytilibitapmoC /noitallatsnIeludoM snoitcurts
nIgniriW
)0007-CPM/0006-CPM(CLDF6-903744-513N/P
The detector model number is the compatibility identifier.
ELECTRICAL RATINGS FOR 8854
egatloVCDV72-61
elppiRkaep-ot-kaepV3
tnerruCyrosivrepuS.xamAu011
emiTpu-tratS.xamsdnoces05
rotceteD4588 +rotce
teD4588 eciveDetomeR
tnerruCmralAAm05-33Am07-05
This manual suits for next models
2
Table of contents
Other Faraday Smoke Alarm manuals
Popular Smoke Alarm manuals by other brands

Kidde
Kidde PI 2000 user guide

Firex
Firex AD instruction manual

System Sensor
System Sensor Innovair DH100ACDCLWP Installation and maintenance instructions

BRK electronic
BRK electronic SC7010BA quick start guide

Bentel
Bentel FireClass FC400PH manual

Ei Electronics
Ei Electronics Ei 176 Optical Technical specifications