manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Fenwal
  6. •
  7. Security Sensor
  8. •
  9. Fenwal 27020-0 User manual

Fenwal 27020-0 User manual

Series 27000
Horizontal DETECT-A-FIRE®Units
Installation Instructions
12.02.D
®
INSTALLATION
Figure1: Surface Mount Units
Series 27020-1 and 27021-1
Model
Number
Contact
Operation on
Temperature Rise
Electrical Rating
(Resistive Only)
27020-0
Opens 5.0 Amps 125 VAC
27020-1
27021-0
Closes
5.0 Amps 126 VAC
0.5 Amps 125 VDC
2.0 Amps 24 VDC
1.0 Amps 48 VDC
27021-1
LOCATION
DETECT-A-FIRE detectors are precision temperature sensors.
They must be mounted in an area (normally a ceiling) so that:
1. The detector spacing complies with both system
requirements and requirements of the agency having
local jurisdiction.
2. The thermal air path to the shell is not obstructed.
Spacing per UL, FM, and UL of Canada is shown in Table 1.
Distances given are for between units on smooth ceilings.
Distances from partitions or walls are half that shown.
To assure that all spacing requirements are met, consult
the authority having local jurisdiction.
MOUNTING
DETECT-A-FIRE units are not position sensitive. Horizontal
and vertical detectors refer to the most common mounting
configurations for that unit. However, each type can be
mounted either horizontally or vertically depending on the
application and installation requirements.
*Although incandescent lamps are considered resistive, their inrush
current is 10 -15 times their steady current. Do not exceed ratings.
°F
Setting °F
Tolerance
Spacings (in feet) RTI Color
Coding
UL ULc FM
140 +7/-8 50 50 20 Quick Black
160 +7/-8 25 25 20 Quick Black
190 +7/-8 50 50 25 Fast White
210 +7/-8 25 50 25 Fast White
225 +7/-8 25 50 25 Fast White
275 +10 25 50 25 Fast Blue
325 +10 50 50 25 Fast Red
Table 1: Model Number 27020*, 27021
These detectors are provided with a surface mount adaptor
which may be mounted on a ceiling or to an outlet box.
However, if the adaptor is direct ceiling mounted, CIRCUIT
VOLTAGE MUST BE LIMITED TO 30 VOLTS.
The Canadian Electrical Code, Part 1, requires that these
devices be installed, mounted to an approved outlet box
and connected to Class 1 wiring. Surface mount units shall
be used only in this manner for Canadian approval.
For direct ceiling mount, proceed as follows:
1. The knockouts are located on the side of the surface
mount adaptor. Remove appropriate knockouts and
install rubber grommets.
2. Mount adaptor to solid ceiling surface through slotted holde in
adaptor mounting brackets. Supplied insulator gasket should
be placed between ceiling and adaptor. Adaptor may be
rotated to position detector.
3. Run system wiring through rubber grommets and connect
to terminals on detector per Figure 3 observing applicable
electrical codes.
4. Mount detector to adaptor with two #8-32 screws supplied.
For optional outlet box mount, proceed as follows:
1. Bend the mounting brackets on the supplied adaptor to fit
standard 4-including outlet box.
2. Mount adaptor to solid ceiling surface through slotted holes in
adaptor mounting brackets. Supplied insulator gasket should
be placed between ceiling adaptor. Adaptor may be rotated to
position detector.
Page 1 Horizontal DETECT-A-FIRE®Units 1-800-FENWAL-1 www.fenwalcontrols.com
* 27020 is a normally closed device and does not meet the
requirements of NFPA-72 for use as an initiating device.
Anderson-Bolds -- 216-360-9800
Figure 3: System Wiring
Figure 2: Flush Mount Units
Series 27020-0 and 27021-0
1. In order to function properly, the sensing shell of the unit must
remain free from paint, grease, oil, etc. Should such a build up
occur, DO NOT, under any circumstances, attempt to remove it.
Replace the unit.
2. Detectors mounted in an area subject to physical abuse or damage,
other than above, must be suitable protected without obstruction the
thermal airpath to the unit.
3. Do not install the unit where the shell would be physically
damaged by sand, grain, rocks, etc.
4. Any detector that has been involved in a fire, abused
or damaged must be replaced.
5. Consult the factory for special precautions necessary
for outdoor use or moist environments.
ANY OF THE ABOVE COULD CHANGE THE FACTORY
TEMPERATURE SETTING, WHICH MAY RESULT IN PROPERTY
DAMAGE AND/OR PERSONAL INJURY OR DEATH.
IT IS POSSIBLE FOR A UNIT TO HAVE BEEN ABUSED OR
DAMAGED AND NOT DISPLAY ANY OUTWARD INDICATION OF
THE DAMAGE. ALL UNITS SHOULD BE TESTED PERIODICALLY
IN ACCORDANCE WITH NATIONAL FIRE PROTECTION
ASSOCIATION REQUIREMENTS (72e) OR THE AGENCY HAVING
LOCAL JURISDICTION.
WARNINGS
INSTALLATION (continued)
3. Run system wiring through rubber grommets and connect
to terminals on detector per Figure 3 observing applicable
electrical codes.
4. Mount detector to adaptor with two #8-32 screws supplied.
For optional outlet box mount, proceed as follows:
1. Bend the mounting brackets on the supplied adaptor to fit
standard 4-inch outlet box.
2. Mount adaptor to outlet box through two slotted holes in
adaptor mounting brackets. Adaptor may be rotated to
position detector.
3. Connect system wiring to terminals on detector per Figure 3
observing applicable electrical codes.
4. Mount detector to adaptor with two #8-32 screws supplied.
1. It is recommended that a standard 4-inch outlet box be
used to mount the detector. Care should be taken that a
neat 4-inch diameter hole be cut in ceiling to allow mounting
clearance for detector. An oversized or ragged hole may
show around the mounted unit.
2. Attach supplied flush mount adaptor to outlet box. Adaptor
may be rotated in screw slots to position detectors as desired.
3. Connect system wiring to terminals on detector per Figure 3
observing applicable electrical codes.
4. Mount detector to adaptor with two #8-32 screws supplied.
400 MAIN STREET, ASHLAND, MA 01721
TEL: (508) 881-2000 FAX: (508) 881-6729
www.fenwalcontrols.com
These instructions do not purport to cover all the details or variations in the equipment described,
nor do they provide for every possible contingency to be met in connection with installation,
operation and maintenance. All specifications are subject to change without notice. Should further
information be desired or should particular problems arise which are not covered sufficiently for
the purchaser’s purposes, the matter should be referred to KIDDE-FENWAL, Inc., Ashland,
Massachusetts.
Page 2 Horizontal DETECT-A-FIRE®Units 1-800-FENWAL-1 www.fenwalcontrols.com
© 2009 Kidde-Fenwal. All rights reserved. Printed in U.S.A. 06-L04104-001 3/26/2009
Fenwal is a registered trademark of Kidde-Fenwal, Inc.
®
Anderson-Bolds -- 216-360-9800

This manual suits for next models

3

Other Fenwal Security Sensor manuals

Fenwal THD-7052 Installation and operation manual

Fenwal

Fenwal THD-7052 Installation and operation manual

Fenwal F1H-RYW1K Administrator Guide

Fenwal

Fenwal F1H-RYW1K Administrator Guide

Fenwal F1H-RYW1 Administrator Guide

Fenwal

Fenwal F1H-RYW1 Administrator Guide

Fenwal FenwalNET 2000 User manual

Fenwal

Fenwal FenwalNET 2000 User manual

Popular Security Sensor manuals by other brands

DigiSpec DS1-PL Operation manual

DigiSpec

DigiSpec DS1-PL Operation manual

Honeywell BW Ultra user manual

Honeywell

Honeywell BW Ultra user manual

Velleman K7101 quick start guide

Velleman

Velleman K7101 quick start guide

Navim Group Company EsiWelma Sensigas ESN.F.O Series manual

Navim Group Company

Navim Group Company EsiWelma Sensigas ESN.F.O Series manual

AJAX MotionProtect Jeweller user manual

AJAX

AJAX MotionProtect Jeweller user manual

Vallen spotWave 201 instruction manual

Vallen

Vallen spotWave 201 instruction manual

Powerfix Profi 271367 Operation and safety notes

Powerfix Profi

Powerfix Profi 271367 Operation and safety notes

Hoyt H286SVD instruction manual

Hoyt

Hoyt H286SVD instruction manual

RIDGID A-Frame Fault Locator Operator's manual

RIDGID

RIDGID A-Frame Fault Locator Operator's manual

AVE LUCE AMICA 44 068/3F Series manual

AVE

AVE LUCE AMICA 44 068/3F Series manual

Biral BTD-300 user manual

Biral

Biral BTD-300 user manual

Wenglor P1MH Series operating instructions

Wenglor

Wenglor P1MH Series operating instructions

Uniden R9 user manual

Uniden

Uniden R9 user manual

BST Flamonitec IFC 400 operating manual

BST

BST Flamonitec IFC 400 operating manual

ABS ABS-Lock X-H-4 Series installation manual

ABS

ABS ABS-Lock X-H-4 Series installation manual

Lince 1883 ZENITH DT/E Installation, programming, and operating manual

Lince

Lince 1883 ZENITH DT/E Installation, programming, and operating manual

Milesight EM300 Series user guide

Milesight

Milesight EM300 Series user guide

Crow FW2-SMK Installation instruction

Crow

Crow FW2-SMK Installation instruction

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.