BST Flamonitec IFC 400 User manual

Operating Manual
Compact Flame Detector
IFC 400

Content
1.1 General aspects
1.1 Introduction
1.2 Warning notes
1.3 Copyright protection
1.4 Disposal information
1.5 Warranty
1.6 Obligation of the operating company
1.7 Liability disclaimer
1.8 Declaration of conformity
1.9 Address of the manufacturer
2 Safety
2.1 Intended use
2.2 Requirements on persons
2.3 Safety instructions
2.4 Safety devices
2.4.1 Fundamental aspects
2.4.2 Safety devices on the compact
industrial flame controller IFC 400
2.5 Safety instructions in case of maintenance
and troubleshooting
2.5.1 Fundamental aspects
2.5.2 Electrical / electronic devices
2.5.3 Testing per German Workplace Safety
Ordinance (BetrSichV)
2.5.4 Safety test
3 Technical data
3.1 General characteristic features
3.2 Electrical system, optical system, mechanical system
3.3 Weight
3.4 Dimensions
3.5 Block diagram IFC 400
4 Transport, installation and connection
4.1 Scope of delivery
4.2 Packaging
4.3 Shipping instructions
4.4 Dimensions IFC 400
4.5 Installation
4.5.1 Alignment of IFC 400
4.5.2 Usage of glasses and lenses
4.5.3 Purge air connection
4.6 Connection
4.6.1 Electrical connection
4.6.2 Connection diagram IFC 400
4.7 Storage
4
4
4
5
5
5
5
6
7
7
8
8
8
9
9
9
10
10
10
11
11
12
12
12
13
13
13
14
14
14
14
15
15
16
16
16
17
17
17
17

Content
5 Description
5.1 Functional description IFC 400
6 Operation of the compact flame detector IFC 400
6.1 Test of the compact flame detector
6.2 Operating indicator LED
7 Maintenance and servicing
7.1 Cleaning
8 Troubleshooting
9 Order data
10 Accessories
18
18
18
18
18
19
19
19
20
21

BST Solutions GmbH | COMPACT FLAME DETECTOR IFC 400 Page 4
GENERAL ASPECTS
1 | General aspects
1.1 Introduction
This operating manual is a helpful guide for ensuring the successful and safe operation of
the compact flame detector IFC 400. It contains important information on how to operate
the system safely, correctly and efficiently. Observing the operating manual will help to pre-
vent hazards, reduce cost of repairs and downtime and increase the reliability and life of the
device.
All illustrations and drawings in this operating manual are shown for illustration purposes
and do not contain details for design.
The operating manual always has to be accessible at the device. It must be read and applied
by each person who is required to work with/on the device.
This work may involve, for example:
• operation
• troubleshooting during operation
• servicing
• maintenance (upkeep, inspection, repair) and/or
• transport
This should be confirmed by the operating company in writing.
1.2 Warning notes
The following warning notes are used in these operating instructions:
This warning level indicates an imminent hazardous situation. If the hazardous situation is
not prevented, this will result in death or severe injury. Follow the instructions that accom-
pany this warning to prevent the risk of death and severe personal injury.
This warning level indicates a potentially hazardous situation. If the hazardous situation is
not prevented, this may result in death or severe injury. Follow the instructions that accom-
pany this warning to prevent the potential risk of death and severe personal injury.
This warning level indicates a potentially hazardous situation.
If the hazardous situation is not prevented, this may result in slight or moderate injuries.
Follow the instructions that accompany this warning to prevent the injury of persons.
This warning level indicates potential damage to property.
If this situation is not prevented, it may result in damage to property.
Follow the instructions that accompany this warning to prevent damage to property.
A notice indicates additional information that will make the handling of the device easier.
DANGER
!
WARNING
!
CAUTION
!
NOTICE

BST Solutions GmbH | COMPACT FLAME DETECTOR IFC 400 Page 5
GENERAL ASPECTS
1.3 Copyright protection
This operating manual has to be treated as confidential. It may only be used by authorised
staff. Access by third parties may only be granted upon written agreement of BST Solutions.
All documents are protected in keeping with the German copyright law.
The disclosure and reproduction of documentation, in whole or in part, as well as the ex-
ploitation and communication of its content shall not be permitted unless expressly stated
otherwise. Offenders are liable for prosecution and the payment of damages. We reserve all
rights to exercise industrial property rights.
1.4 Disposal information
The following warning notes are used in these operating instructions: The flame
detector is equipped with electrical and electronic components and must be
disposed separate from household waste. Follow the local and actual regulati-
ons for waste disposal.
1.5 Warranty
Read these operating instructions carefully and in full before operating the compact flame
detector IFC 400!
The manufacturer is not liable for damage or operating malfunctions that result from the
operating manual not being observed.
The operating company has to supplement the operating manual with operating instructions
on the basis of national regulations on accident prevention and environmental protection,
including information on supervision and notification requirements with respect to special
operating circumstances, e.g. regarding organisation of work, working processes and staff
deployed.
The recognised technical rules for safe and professional working also have to be observed in
addition to the operating manual and the regulations on accident prevention applicable to
the country and place of use.
The warranty shall become void, for example, in the event of:
• inappropriate use
• use of impermissible equipment
• incorrect connection
• prior works that are not part of the supplied product or service
• use of non-original spares and accessories
• conversion, if this has not been approved by BST Solutions
• non-performance of specified maintenance work
1.6 Obligation of the operating company
The compact flame detector IFC 400 may cause hazards if it is operated inappropriately or
in an improper condition.

BST Solutions GmbH | COMPACT FLAME DETECTOR IFC 400 Page 6
GENERAL ASPECTS
The operating company is under the obligation to operate the machine in its intended state
only. The operating company must secure hazardous areas that exist between BST devices
and the customer‘s own equipment.
The operating company must appoint and instruct responsible staff:
• Only deploy trained or instructed staff.
• Clearly set out the responsibilities of the staff with regard to operation, set-up, maintenan-
ce and repair.
• Regularly check that staff are safety conscious and aware of hazards and are observing the
operating manual.
• Before starting work, staff who are assigned to work with/on the device have to have read
and understood the operating manual, in particular the chapter on „Safety“, as well as the
relevant regulations.
• The operating manual and relevant regulations have to be stored in such a way that they are
accessible to operating and maintenance staff.
• Set out who will have responsibility for device operation and ensure that this person has
the authority to overrule any unsafe instructions of third parties.
1.7 Liability disclaimer
All technical information, data and guidance on device operation that are contained within
this operating manual are, to the best of our knowledge, correct at the time of printing, taking
into account our present understanding and experience.
We reserve the right to make technical changes with respect to the further development of
the compact flame detector outlined in this operating manual. No claims can be made based
on the specifications, illustrations and descriptions of this operating manual.
We shall not be liable for damage or operating malfunctions that result from operating errors,
inappropriate repairs or the non-observance of the operating manual. We expressly state that
only original spare parts and accessories approved by us may be used. This also applies to
the components of other manufacturers that have been used.
The installation or use of non-approved spare and accessory parts and any unauthorized
retrofits and modifications are not permitted for safety reasons and exclude any liability by
BST Solutions for consequential damages.
BST Solutions is liable for possible errors or omissions with the exclusion of additional claims
entered into in the framework of the warranty obligations conceded to in the contract. Claims
for damages, on whatever legal basis they may be, shall be excluded.
Generally valid legal and other binding regulations on accident prevention and envi-
ronmental protection have to be observed and instructed, in addition to the operating
manual.
NOTICE

BST Solutions GmbH | COMPACT FLAME DETECTOR IFC 400 Page 7
GENERAL ASPECTS
Translations into foreign languages are carried out in good faith. We cannot accept any liability
for translation errors; this also applies where the translation has been carried out or has been
commissioned by us. The original text alone shall be binding.
Descriptions and illustrations do not necessarily depict the delivered product or a possible
spare parts order. Drawings and graphics are not to scale.
1.8 Declaration of conformity
1.9 Address of the manufacturer
BST Solutions GmbH
Ruegenstr. 7 . 42579 Heiligenhaus . Germany
T +49 2056 989 47-0 . E-Mail: info@flamonitec-bst.com
www.flamonitec-bst.com
BST Solutions GmbH
Rügenstr. 7
42579 Heiligenhaus
Germany
Tel.: +49 2056 98947-0
Web: www.bst-solutions.de
EU Konformitätserklärung
EC Declaration of Conformity
Produkt Flammenwächter IFCx, IFRx
Product Flame detector IFCx, IFRx
Typ IFC201, IFC400, IFR201, IFR400
Type IFC201, IFC400, IFR201, IFR400
Hiermit erklären wir, dass der nachstehend bezeichnete Flammenwächter in seiner Konzipierung und
Bauart sowie in der von uns in Verkehr gebrachten Ausführung den grundlegenden Sicherheitsanfor-
derungen folgender EU-Richtlinien entspricht
This is to confirm that the below described system in its design and type of construction complies with the
provisions of the Directive of the Council of the European Communities on the approximation of the laws of the
member states relating to
Verordnungen
EU/2016/426
Gasgeräteverordnung
Regulations
Gas appliances regulation
2014/35/EU
Niederspannungsrichtlinie
Low voltage directive
2014/30/EU
EMV Richtlinie
EMC directive
Benannte
Stelle
Notified body
DVGW Cert GmbH
0085
CE-Zertifikat vom
CE certificate from
Gültig bis
Valid until
03.04.2019
03.04.2029
CE-0085CU0083
Baumusterprüfbescheinigung
Type examination certificate
Prüfgrundlagen
EU/2016/426 A III B (09.03.2016)
Standards
EN 298:2012, EN13611:2015+AC:2016
Ausgestellt durch BST Solutions GmbH
Issued by
Rechtsverbindliche
Unterschrift
Legally binding signature
Name Funktion Ort, Datum
Function Place, Date
Eberhard Röllecke Geschäftsführer Heiligenhaus, den 31.05.2021
General Manager

BST Solutions GmbH | COMPACT FLAME DETECTOR IFC 400 Page 8
2 | Safety
2.1 Intended use
The IFC 400 is a compact flame detector that has been specially designed for industrial com-
bustion furnaces for continuous operation. It provides a galvanically isolated change-over
contact as safety-related output.
As a safety-relevant criterion for flame detection, the flickering of the flame is used. Swit-
ching thresholds, switching times and filter characteristics can only be set by the manufac-
turer.
The flame detection is signaled via a LED and data is transmitted for evaluation.
2.2 Requirements on persons
Do not allow any persons who are being apprenticed, educated, instructed or on a general
training programme to work on the device without the constant supervision of an experien-
ced person.
Persons who are under the influence of drugs, alcohol or medication that affects reactivity
shall not be permitted to carry out work on the device.
Connection, set-up, maintenance and repair work may only be carried out by qualified spe-
cialist staff.
This device may cause hazards if it is operated inappropriately by untrained staff or if it is not
used for its intended purpose.
The Compact Flame Detector IFC 400 may only be operated with a burner control or a
DCS. It is not approved for direct control of the fuel valve!
Danger due to improper use!
The device may be dangerous if used improperly and / or otherwise.
Only use the device as intended.
Follow the procedures described in this operating manual.
The manufacturer / supplier is not liable for damage resulting from improper use. The
risk is borne solely by the user / operator.
Work on/with the device may only be performed by persons authorized to do so based
on their training and qualification. Furthermore, such persons have to have been com-
missioned by the operating company.
DANGER
!
WARNING
!
NOTICE
SAFETY

BST Solutions GmbH | COMPACT FLAME DETECTOR IFC 400 Page 9
Generally valid legal and other binding regulations on accident prevention and environmen-
tal protection in addition to basic health and safety requirements have to be observed. The
operating company has to instruct its staff accordingly.
2.3 Safety instructions
The following instructions on accident prevention have to be observed when operating the
compact flame detector IFC 400.
2.4 Safety devices
2.4.1 Fundamental aspects
Check the safety equipment and locking devices on the device for safe operational condition.
Only operate the device if all safety devices are present and enabled. The operating company
or operator of the compact flame detector IFC 400 is responsible for the proper operation
of the device.
Only operate the device if it is in a proper state!
• Do not remove or disable safety devices.
• Check for externally noticeable damage and defects prior to using the device! Imme-
diately notify the appropriate authority/person of any changes that occur (including
changes in operating performance). If necessary, stop and secure the device imme-
diately.
• Allow only authorised specialist staff to carry out set-up and/or maintenance work.
• Replace worn or defective parts.
• Use suitable maintenance tools only.
• After repair work, refit all safety devices and carry out electrical and mechanical
checks.
• Check the operating manual for details of displays as well as switch-on and switch-off
procedures.
• Prior to switching on the device, make sure that no-one can be endangered by the
device!
• The operating instructions always have to be kept close to the device and be readily
accessible.
• Any non-compliance with the safety instructions outlined in this operating manual
may lead to damage to property, personal injury or even death.
NOTICE
SAFETY
To protect the operating personnel, warning / danger signs are attached to the device.
Note these signs.
Replace damaged or illegible warning / danger signs immediately.
NOTICE

BST Solutions GmbH | COMPACT FLAME DETECTOR IFC 400 Page 10
2.4.2 Safety devices on the compact industrial flame controller IFC 400
The industrial flame controller IFC 400 has been fitted with the following safety devices:
• Housing (protection against accidental contact)
• IP 65
• Internally protected by fuse (not changeable)
2.5 Safety instructions in case of maintenance and troubleshooting
2.5.1 Fundamental aspects
• Deadlines set or indicated in the operating manual for repetitive checks / inspections must
be observed!
• Appropriate workshop equipment is essential for performing maintenance work.
• In conformance with the electrical regulations, work on the electrical equipment of the
system may only be carried out by an electrical specialist or by trained staff under the di-
rection and supervision of an electrical specialist.
• The adjustment, maintenance and inspection activities and deadlines stipulated by BST
Solutions, including information on the replacement of parts / assemblies, have to be ob-
served! These tasks may only be carried out by authorised specialist staff.
• Operating staff have to be informed before maintenance or other special work is carried
out. A supervisor has to be appointed.
• Screw connections which have been loosened during maintenance and servicing work, have
to be tightened.
• If maintenance and repairs require safety devices to be dismantled, these devices have to
be remounted and checked as soon as the maintenance and repair work has been comple-
ted.
• Operating and auxiliary materials as well as exchanged parts have to be disposed of in a
safe and eco-friendly way.
• Spare parts supplied by BST Solutions or approved of by BST Solutions only may be used.
2.5.2 Electrical / electronic devices
SAFETY
Danger to life caused by electrical current!
Contact with live wires or components presents a danger to life!
Prior to any work on the electrical equipment, disconnect the flame amplifying system
from the power supply network!
In keeping with the electrical regulations, work on electrical / electronic parts / com-
ponents may only be carried out by electrical specialists.
DANGER
!
NOTICE

BST Solutions GmbH | COMPACT FLAME DETECTOR IFC 400 Page 11
Important rules of conduct
• Check the device at regular intervals. Any defects or faults ascertained have to be corrected
immediately. Switch off the device until the defects have been corrected.
• Equipment undergoing inspection, maintenance or repair work must be deenergised, if re-
quired. First check that the disconnected parts are no longer live, then short to earth. Also
isolate neighbouring live parts.
• If work is required on live parts, a second person must be present to disconnect the power
supply in case of an emergency. Only use insulated tools!
• Fuses must not be repaired or bridged. Only use original fuses with the specified current!
• Before opening the housing, the device must be deenergized.
2.5.3 Testing per German Workplace Safety Ordinance (BetrSichV)
In case of the coupling or installation of devices from various manufacturers or suppliers,
the operating company has to carry out a precise test, prior to start-up, in accordance with
the German Workplace Safety Ordinance (BetrSichV) in force and the applicable electrical
regulations.
In case of queries, please get in touch with BST Solutions.
2.5.4 Safety test
In order to ensure correct operation, the compact flame detector IFC 400 of all applica-
tions have to be tested several times by starting and stopping the burner several times.
In all cases the flame relay has to be switched off reliably in case of an absent flame.
The test should be performed in different operating situations. This is an indispensable
pre-requisite for a safe and correct operation of the device!
WARNING
!
SAFETY

BST Solutions GmbH | COMPACT FLAME DETECTOR IFC 400 Page 12
TECHNICAL DATA
Optical features 350 to 1100 nm
Orientation axial
Input 230 V AC / 50-60 Hz
120 V AC (optional)
Prefuse max. 1 A, slow
consumption max. 50 mA
Operating temperature -20 to +70°C
Operating position any position
Kind of protection IP 65
Protection class I
Humidity max. 95% r.H., non-condensing
Electrical connenction Fixed cable connection, 1.5m
Restart time Standard 5s
Other times on request
Reaction time
Switch-on time
Switch-o time
< 1s
< 1s
For the switch-off time applies: For installations in accordance with DIN / EN 267 or
DIN / EN 676 at the moment of self-checking < 2s
Thresholds
Amplitude
Pressure
Frequency
Off / On / Max.
50 / 100 / 1023
150 / 200 / 900
15 / 20 / 400
Relay output Floating, potential-free change-over contact
max. switching current 0.5 A
max. switching power 125 W
max. switching voltage 250 V AC
3 | Technical data
3.1 General characteristic features
• Semiconductor sensor
• Fully electronic construction
• Galvanically isolated change-over contact
• Continuous operation
• CE0085CU0083
3.2 Electrical system, optical system, mechanical system

BST Solutions GmbH | COMPACT FLAME DETECTOR IFC 400 Page 13
3.3 Weight
Weight approx. 0.700 kg
3.4 Dimensions
Length (without plug or gland) 142 mm
Width 66 mm
Height 92 mm
Dimensions see under item 4.4
3.5 Block diagram IFC 400
Item Designation
1 Sensor
2 Shutter
3 Preamplifier
4 Signal evaluation
5 Optical output
6 Relay
7 Power supply
TECHNICAL DATA

BST Solutions GmbH | COMPACT FLAME DETECTOR IFC 400 Page 14
4 | Transport, installation and
connection
4.1 Scope of delivery
• Compact flame detector IFC 400
• Operating instructions (optional, customer dependend)
• Connection cable in other length (optional)
Refer to the order papers for the exact scope of delivery and compare with the delivery note.
Checking for completeness
Check the entire delivery for completeness against the accompanying delivery note. Please
refer to our terms of sale and delivery otherwise.
Report any damage
After arrival of the device and accessories, notify the shipping agent, the insurance company
and BST Solutions immediately in case of any damage caused by transport or inadequate
packaging.
Take steps to minimise and prevent further damage.
Report the insurance case to the insurance company without delay and transmit the full
claim documents at once in order to expedite the claims settlement (at the latest in suf-
ficient time before the expiry of any periods of preclusion and/or limitation relating to the
compensation claims against third parties).
4.2 Packaging
The compact flame detector IFC 400 is shipped in different packaging materials.The most
frequently used packaging materials are cardboard and plastics (foils, foamed material).
4.3 Shipping instructions
All installation and connection work may be carried out by qualified and approved spe-
cialist staff only!
Observe the legal stipulations and adjustment instructions of the plant operator!
NOTICE
TRANSPORT, INSTALLATION AND CONNECTION
Packaging has to be disposed of in an environmentally friendly way and in accordance
with the relevant provisions on disposal.
NOTICE
Do not subject the appliance to heavy impacts during transport. Do not subject the
appliance to any humidity!
NOTICE

BST Solutions GmbH | COMPACT FLAME DETECTOR IFC 400 Page 15
4.4 Dimensions IFC 400
All dimensions in mm
4.5 Installation
The IFC 400 should be installed as close as possible to the flame with low vibration. The
alignment is to concentrate on the primary zone of the flame (flame root). The compact
flame detector should be mounted with the adapter. In order to prevent interference, the
direct view of a spark is to be avoided.
The connecting cable is to run separately from the high-energy ignition and power lines over
long distances and not parallel to avoid interference.
All installation and connection work may be carried out by qualified and approved spe-
cialist staff only! The legal regulations as well as adjustment instructions of the plant
operator have to be observed!
NOTICE
TRANSPORT, INSTALLATION AND CONNECTION
The cable length when using the ionization circuit depends on the used burner control.
For connection length > 1.5 m, the wires of the relay contacts in the connection cable
must be shielded.
NOTICE

BST Solutions GmbH | COMPACT FLAME DETECTOR IFC 400 Page 16
4.5.1 Alignment of IFC 400
4.5.2 Usage of glasses and lenses
Depending on the distance and viewing angle to the flame, the adapter lens to be used when
needed. If pressure is prevailing in the combustion chamber, an adapter with quartz glass is
recommended.
4.5.3 Purge air connection
If the sensor temperature may rise due to high combustion chamber temperatures above
60°C, a purge air connection in order to limit the temperature sensor to provide a maximum
of 60°C is essential. The dimensioning of the scavenging air is dependent on the parameters
of the furnace back pressure, and the pending purge air pressure and temperatures. Purge air
connections are available as the diameters ¼‘‘ and ½‘‘ optionally. The air connection is com-
bined with the adapter. Depending on the application again lenses and glasses are available.
This eliminates the normal adapter.
TRANSPORT, INSTALLATION AND CONNECTION

BST Solutions GmbH | COMPACT FLAME DETECTOR IFC 400 Page 17
4.6 Connection
4.6.1 Electrical connection
For connection data, please refer to the chapter titled „Technical data“ as well as to the fol-
lowing terminal diagram.
Ensure that the available supply voltage complies with the voltage indicated on the type
plate. Prior to connection, check the device and the connecting cables for visible damage.
4.6.2 Connection diagram IFC 400
4.7 Storage
Do not unpack any packed compact flame detector IFC 400 and accessories.
The following conditions apply to storage:
• Store in a dry place. Maximum relative humidity 95 %. Non condensing.
In addition, ensure that the floor in the storage area will remain dry throughout the storage
period.
• Protect from direct sunlight. Storage temperature 0 to +25°C.
• Store in a dust-free location.
• Avoid mechanical vibrations and damage.
Danger to life caused by electrical current!
The safety instructions and local safety regulations have to be observed during con-
nection!
DANGER
!
TRANSPORT, INSTALLATION AND CONNECTION
Internal connection diagram AC/DC Cable No. Connection
L 1 L
N 2 N
3NC
4NO
5 Com
PE PE PE

BST Solutions GmbH | COMPACT FLAME DETECTOR IFC 400 Page 18
5 | Description
5.1 Functional description IFC 400
The IFC 400 is a compact flame detector, that has been specially designed for use in industri-
al continuous-combustion furnaces. It provides a galvanically isolated changer as an output.
As a safety-relevant criterion for flame detection, the flickering of the flame is used. Swit-
ching thresholds, switching times and filter characteristics can only be set by the manufac-
turer.
The flame detection is signalled via an LED and data is transmitted for evaluation.
6 | Operation of the
flame detector IFC 400
6.1 Test of the flame detector
To ensure the proper operation, the flame detector must be tested several times by starting
and stopping the burner. As long as there is no flame in all cases the flame relays has to be
switched off solid.The test should be repeated for different operation situations ( see also
datasheet ). This is an essential condition for safe and proper operation of the device.
6.2 Operating indicator LED
Via the built-in LED the flame detector is indicating the following operating conditions:
The compact flame detector IFC 400 may only be operated wih a burner control or DCS.
It is not approved for direct control of the fuel valve!
DANGER
!
LED Meaning
off IFC 400 is without potential or defective
Flashing with short interruptions
flashes with long interruptions
Flame is off
Flame is on
on IFC 400 is defective
DESCRIPTION
OPERATION OF THE FLAME DETECTOR IFC 400

BST Solutions GmbH | COMPACT FLAME DETECTOR IFC 400 Page 19
7 | Maintenance and servicing
7.1 Cleaning
For cleaning, use a moist cloth to wipe the housing from the outside only. For maintenance of
the sight glass, please use a clean and lint free cloth. Do not use any kind of cleaning sprays
or liquids.
8 | Troubleshooting
Do not scratch the glass!
NOTICE
Error description Cause Remedy
No flame signal connecting error
or no active power
Glass dirty
IFC 400 malfunction
Alignment wrong
Please check the plugs an the
connections of the burner control-
ler box
Power off the IFC and take it out
of the flange. Now clean the glass
carefully with a clean and lint-free
cloth
Replace IFC
Correct alignment
Ambient light
interference
View of sparks or artificial
light
Change view or shield against
artificial light
MAINTENANCE AND SERVICING
TROUBLESHOOTING

BST Solutions GmbH | COMPACT FLAME DETECTOR IFC 400 Page 20
9 | Order data
The compact flame detector IFC 400 is available from BST Solutions GmbH under the follo-
wing order data:
Type Description Part-No.
Compact Flame Detectorm IFC 400/230,
sensitive*, fixed connection
cable 1.5 m
230 V AC 611189010452
Compact Flame Detector IFC 400/230,
sensitive* Ionization, fixed connection
cable 1.5 m
230 V AC 611189010462
Compact Flame Detector IFC 400/120,
sensitive*, xed connection
cable 1.5 m
120 V AC 611289010452
Compact Flame Detector IFC 400/120,
sensitive* Ionization, xed connection
cable 1.5 m
120 V AC 611289010462
* For installations according to DIN / EN 267 or DIN / EN 676, the switch-off time at the moment of the self-check
< 2 s.
ORDER DATA
Table of contents
Other BST Security Sensor manuals
Popular Security Sensor manuals by other brands

Virone
Virone DC-3 manual

Thinkcar
Thinkcar PLD-212 user manual

ZILA
ZILA FluidIX LUB-VDT Mounting and operating instructions

Xylem
Xylem FLYGT MiniCAS II Installation, operation and maintenance manual

Cavius
Cavius 6005-001 quick start guide

CALECTRO
CALECTRO Uniguard Superflow UG-3-O-MB installation instructions