9 Fault clearance
Malfunction Possible cause Remedy
No display No operating voltage or imper
missible operating voltage
Apply permissible operating
voltage
Electrical connections swapped Connect the device in accordance
with the circuit diagram
Device defective Replace device
Display or switching
output does not re
act in accordance
with the settings
Short circuit or overload at the output Eliminate short circuit or overload
Incorrect switching point taught
(e.g. at 0 bar)
Repeat teaching procedure
Device defective Replace device
Device variants with LCD display
[Er_1] / [FAIL] 1) Device error Replace device
[Er_2] / [ASIC] 1) Device error Replace device
[Er10] / [OVER] 2) Measuring range exceeded Comply with the measuring range
[Er17] / [SUPL] 2) Undervoltage Apply permissible operating voltage
[Er20] / [tEMP] 2) Temperature error Check operating conditions
Replace device
[Er21] / [SHRt] 2) Short circuit at OutA Eliminate short circuit
[Er22] / [SHRt] 2) Short circuit at OutB Eliminate short circuit
[Err] / [BUSY] C/Q busy Check device settings
[Err] / [ID] Device ID error,
replication function failed
When replicating, use sensors
with the same pressure range
(same device ID)
[Err] / [COMM] IO-Link communication error Check the C/Q line
Device variants without LCD display
LED flashes red Device error Replace device
LED illuminated red Temperature error, undervoltage,
measuring range exceeded, short
circuit
Check operating conditions
1) Display flashes red
2) Display illuminated red
Fig. 24
10 Technical data
SPAU-
General
Certification RCM Mark, c UL us – Listed (OL)
CE marking (èDeclaration of conformity) In accordance with EU EMC directive
Note on materials RoHS-compliant
Input signal / measuring element
Operating medium Compressed air in accordance with
ISO 8573-1:2010 [7:4:4]; inert gases, operation
with lubricated medium possible
Temperature of medium [°C] 0 … +50
Ambient temperature [°C] 0 … +50
Max. permissible relative air humidity [%RH] 93
Max. current consumption [mA] 240
Output, general
Accuracy
– P16 [% FS] ±2 at room temperature
– B2, B11, V1, P1, P2, P6, P10,
P025, P05, V025, V05, P12
[% FS] ±1.5 at room temperature
– B2, B11, V1, P1, P2, P6, P10 [% FS] ±3 in the entire temperature range
– P025, P05, V025, V05, P12, P16 [% FS] ±4 in the entire temperature range
Repetition accuracy [% FS] ±0.3 (short-time), with Filt = OFF
Temperature coefficient [% FS/K] Typically 0.05
Switching output
Switch-on time [ms] Max. 4.4
Switch-off time [ms] Max. 5.3
Max. output current [mA] 100
Capacitive load maximum DC [nF] 100
Voltage drop [V] Max. 1.6
Pull-down/pull-up resistor PNP: integrated; NPN: not integrated
Inductive protective circuit On hand
Analogue output
Output characteristic curve initial value … final
value
– SPAU-...-V [V] 0 … 10
– SPAU-...-B [V] 1 … 5
– SPAU-...-A [mA] 4 … 20
Rise time [ms] 3, at [Filt] = [OFF]
Max. load resistance of current
output (SPAU-...-A)
[Ω] 500
Min. load resistance of voltage
output (SPAU-...-V, SPAU-...-B)
[kΩ] 2.5
Output, additional data
Protection against short circuit Yes
Overload protection On hand
SPAU-
Electronics
Operating voltage range DC [V] 20 … 30
Idle current [mA] Typically 35
Ready-state delay [ms] Typically 160
Protection against incorrect polarity All connections against each other
Mechanical system
Mounting position Any, avoid condensation gathering in the sensor
Housing material PA reinforced
Keyboard material TPE-O
Plug housing material Brass (nickel-plated)
Display / operation
Displayable units bar, kPa, MPa, psi, mmHg, inchHg, inchH2O,
kgf/cm2
Threshold value setting range % FS 0 … 100 (recommended range 1 … 99)
Threshold value setting range, auto
difference monitoring
% FS 0.5 … 100
Hysteresis setting range % FS 0 … 90
Immission / emission
Storage temperature [°C] –20 … +80
Degree of protection (in accordance with
EN 60529)
– SPAU-…T/H/W/A-… IP65/IP67
– SPAU-…F-… IP65
Protection class (in accordance with
DIN VDE 0106-1)
III
Resistance to shocks (in accordance with
EN 60068-2)
30 g acceleration with 11 ms duration
(half-sine)
Vibration resistance (in accordance with
EN 60068-2)
10 … 60 Hz: 0.35 mm / 60 … 150 HZ: 5 g
Fig. 25
SPAU- -B2 -B11 -V025 -V05 -V1 -P025 -P05
Pressure measuring range
Initial value
[bar]
[MPa]
-1
-0.1
0
0
Pressure measuring range
Final value
[bar]
[MPa]
1
0.1
10
1
-0.25
-0.025
-0.5
-0.05
-1
-0.1
0.25
0.025
0.5
0.05
Overload range
Initial value
[bar]
[MPa]
-1
-0.1
Overload range
Final value
[bar]
[MPa]
5
0.5
15
1.5
1
0.1
2
0.2
5
0.5
1
0.1
2
0.2
Fig. 26
SPAU- -P1 -P2 -P6 -P10 -P12 -P16
Pressure measuring range
Initial value
[bar]
[MPa]
0
0
Pressure measuring range
Final value
[bar]
[MPa]
1
0.1
2
0.2
6
0.6
10
1
12
1.2
16
1.6
Overload range
Initial value
[bar]
[MPa]
-1
-0.1
Overload range
Final value
[bar]
[MPa]
5
0.5
6
0.6
15
1.5
20
2.0
Fig. 27
IO-Link
Protocol version Device V1.1
Profile Smart sensor profile
Function classes: 0x8000, 0x8001, 0x8002, 0x8003, 0x8004
Communication mode COM2 (38,4 kBaud)
Port class A
Process data length IN 2 byte
Process data content 2 bit BDC (Pressure monitoring)
14 bit PDV (Pressure measured value)
IODD, IO-Link device description èwww.festo.com/sp
Fig. 28
Hole patterns
Fig. 29 Fig. 30