Wire the controls in accordance with the National Electrical Code, manufacturer’s recommendations and/
or applicable local codes. UNIT MUST BE GROUNDED. Check ground circuit to make certain that the unit
has been properly grounded. The wiring should be protected by an overcurrent circuit device rated at 15
amperes. CAUTION must be taken to ensure that the wiring does not come into contact with any heat source.
All line voltage circuits MUST be wired in accordance with the National Electrical Code for Class 1 wiring or
equivalent methods.
1. Remove one knockout from the junction box on the fan proving switch side. Install line voltage power
supply wires to the CAS unit as shown in Figure 1.
2. Remove one knockout from the side of the junction box opposite the fan proving switch. Run line voltage
wiring to the appliance controls as shown in Figure 1. Refer to the appropriate gas system conguration
diagram for your specic appliance.
3. Insert the 24 VAC relay into the base on the CAC-24 and secure with the retaining clip.
4. Install the junction cover and secure with the 4 provided sheet metal screws.
WIRING
MOUNTING JUNCTION BOX
The junction box may be mounted anywhere that is convenient for routing the wiring and tubing. Mount the
CAC-24 to a wall or oor joist using the four dimpled locations on the base of the box (See Figure 1).
Note: The unit must be mounted so the draft proving switch is vertical as shown in Figure 1. The CAC-24
should be placed close enough to the CAS unit to route the provided 10 foot long plastic tubing from the
draft proving switch to the exposed tubing on the CAS. If mounting further away, the installer must provide
any necessary ttings and extra tubing.