safgard 1100 User manual

126 Bailey Road, North Haven, CT 06473 • Phone (203) 776 0473 • FAX (203) 764 1711 • www.hydrolevel.com
• ADVANCED SOLID STATE DESIGN
• TEST BUTTON FOR EASY DIAGNOSTICS
• POWER, LOW WATER AND SERVICE NEEDED INDICATORS
• MOLEX CONNECTOR FOR EASY WIRING
• COMPACT SIZE ALLOWS FOR MOUNTING IN TIGHT SPACES
Step Step 
Step 
Step 
Low Water Cut-Off
For Residentia
Hot Water Boi ers
24 VAC Operating Voltage
Model 1100
Determine Mounting Location
The Safgard 1100 must be installed at or above the
minimum safe water level established by the boiler
manufacturer. The 1100 can be installed directly into
the boiler if a suitable tapping is available 훽. The
1100 can also be installed in the boiler piping using a
standard 3/4" tee 훾.
Note: When installing in piping, select a location
close to the boiler to ensure the 4' wiring harness will
reach the 24-Volt transformer. The cut-off should be
installed on the boiler side of the circulator or shut-off
valves.
IMPOR AN : Check for adequate clearance
(minimum 1/4") from metal probe sensor to any
surface inside the boiler or pipe.
Do not install in a location that could hold or trap
water in the event of a low water condition.
Apply Teflon®tape to
the threads of the
odel 1100. Do not
use pipe dope or
other pipe sealants.
Hand tighten the
control into boiler
tapping or pipe tee.
Be careful not to
cross thread.
Note: Do not use a
wrench. Hand tighten
only.
Plug wire harness
into connector on
face of control.
WARNING Electrical shock hazard. To prevent electrical s ock, deat or
equipment damage, disconnect power supply before
installing or servicing control. Only qualified personnel may install or service t is control in
accordance wit local codes and ordinances. Read instructions completely before proceeding.
CAUTION To prevent serious
burns, boiler
s ould be t oroug ly cooled before installing or
servicing control.
WARNING Frozen pipes/water damage. Central eating systems are prone to s ut down as a result of power or fuel outages,
safety related fault conditions or equipment failure. Installation of freeze protection monitoring or ot er precautions
is recommended for unattended dwellings in climates subject to sustained below-freezing temperatures.
WIRING TO CONTROL CENTER
For boilers equipped with a Honeywell R8285 Control Center or equivalent
WIRING TO AN AQUASTAT
For boilers equipped with a Honeywell Model L8148E or L8124E Aquastat. Safgard Model 1100 is not to be used with
Model L8148C or L8124C. Safgard Model 1150 should be used for oil-fired boilers.
Y G W
C R
Connect the WHITE wire to Cand the RED wire to R
using the screw terminals on the control center.
Connect the GREEN wire to any suitable, unpainted
ground screw. Note: for operation of the control, the
green wire must be connected to a ground source
electrically common with boiler ground. 햲Unplug the factory-wired quick connect from ter-
minal Rand 햳plug into YELLOW wire with male
connector. 햴Plug YELLOW wire with female con-
nector into terminal R.
Connect the WHITE wire to V and the RED wire to Z. Connect the
GREEN wire to the ground screw on the bottom of the aquastat or any
other suitable, unpainted ground screw. Note: for operation of the con-
trol, the green wire must be connected to a ground source electrically
common with boiler ground.
햲Unplug the factory-wired quick
connect from terminal B1 and 햳plug
into YELLOW wire with male connec-
tor. 햴Plug YELLOW wire with female
connector into terminal B1.
UPON COMPLETION OF WIRING,
REPLACE COVER.
Step Step 
Step Step 
WIRING TO 24 VAC TRANSFORMER
For boilers using a standard 24 VAC transformer
BOILER SPECIFIC MODELS AND WIRE HARNESSES
Connect RED wire to hot side of 24 Volt boiler trans-
former (R). Connect WHITE wire to common side of
24 Volt boiler transformer (C). Connect the GREEN
wire to any suitable, unpainted ground screw.
Note: for operation of the control, the green wire
must be connected to a ground source electrically
common with boiler ground.
Cut-off the connectors and strip the ends of the two
yellow wires of the odel 1100 harness. Break into
the burner circuit between the hot side of the trans-
former (R) and other limit controls. Connect either
YELLOW wire to the hot side. Connect the other
YELLOW wire in series with other limit controls.
Important: The switch contacts of the low water cut-
off (yellow wires) must be wired in series with all
other limit and operating controls (as shown above).
Step Step 
1100H2
Including 45-348 Harness
Part No. Model Description
45-1100 1100 1100 with standard wire harness (cable 45-531-54)
45-1102 1100H2 1100 with wire harness for UTC intergrated control module
(cable 45-348)
45-1103 1100H3 1100 without wire harness
45-1105 1100H5 1100 with wire harness for Weil cLain Ultra, Lochinvar
Knight & Solution (cable 45-349)
45-1107 1100H7 1100 with wire harness for connection to vent damper plug on
boiler control (cable 45-353)
Note: Wire Harnesses are also sold separately (use cable part numbers above)
LIMI ED MANUFAC URER’S WARRAN Y
We warrant products manufactured by Hydrolevel Company to
be free from defects in material and workmans ip for a period
of two years from t e date of manufacture or one year from
t e date of installation, w ic ever occurs first. In t e event of
any claim under t is warranty or ot erwise wit respect to our
products w ic is made wit in suc period, we will, at our
option, repair or replace suc products or refund t e purc ase
price paid to us by you for suc products. In no event s all
Hydrolevel Company be liable for any ot er loss or damage,
w et er direct, indirect, incidental or consequential. T is war-
ranty is your EXCLUSIVE remedy and s all be IN PLACE OF
any ot er warranty or guarantee, express or implied, includ-
ing, wit out limitation, any warranty of MERCHANTABILITY or
fitness for a particular purpose. T is warranty may not be
assigned or transferred and any unaut orized transfer or
assignment t ereof s all be void and of no force or effect.
126 Bailey Road, North Haven, CT 06473 • Phone (203) 776 0473 • FAX (203) 764 1711 • www.hydrolevel.com
OPERATIONAL TEST PROCEDURE
IMPOR AN : Do not run boiler unattended until the following procedure is completed
1. Before raising t e water level above t e Model 1100, turn on power to t e boiler and set t e t ermostat to call for eat. Bot t e green
“POWER” LED and amber “LOW WATER” LED s ould illuminate. T e burner s ould not fire. IMPORTANT: If t e burner fires wit no water
at t e probe, immediately s ut down power to t e boiler and refer to t e Trouble S ooting instructions below.
2. Proceed to fill t e boiler wit water. W en water reac es t e LWCO position, t e burner s ould fire. If t e burner does not fire, refer to t e
Trouble S ooting instructions below.
3. Turn off t e power to t e boiler and finis filling t e system.
4. Before leaving t e job, power up t e system and pus t e TEST button on t e Model 1100 to simulate a low water condition. T e amber
“LOW WATER” LED s ould illuminate and t e burner s ould s ut down.
SERVICE & MAINTENANCE
EVERY YEAR C eck control operation annually by pressing t e TEST button. T e amber “LOW WATER” LED s ould illuminate and t e
burner s ould s ut down.
5 YEARS Remove t e low water cut-off every five years and clean all surfaces in contact wit water.
IF AMBER LED If t e amber “LOW WATER” LED is blinking, t e control s ould be removed and all surfaces in contact wit water s ould be
IS BLINKING cleaned. T e blinking LED indicates t at t e sensor may be getting coated wit oil or ot er residues in t e system. If left
unc ecked, t is could result in a nuisance low water s utdown.
TROUBLE SHOOTING
IF HE BURNER DOES NO SHU DOWN
(w en water is below t e probe or
w en t e TEST button is pressed)
1. Turn off boiler power immediately and re-c eck wiring.
2. Turn off boiler power and drain system. Remove low water cut-
off and c eck for adequate clearance – no metal s ould be in
contact wit t e control’s metal probe tip.
IF HE BURNER DOES NO FIRE
1. Make sure water as reac ed t e level of t e control.
2. C eck green wire for proper ground. Make sure t e wire is
attac ed to an unpainted surface t at is electrically common to
t e boiler.
3. C eck to ensure t e control’s metal probe tip is not surrounded
by an air pocket. S ut down power to t e boiler and slowly
loosen, but do not remove, t e control. Allow any air to escape.
W en water begins to seep past t reads, retig ten t e control.
4. Re-c eck wiring and c eck for correct incoming voltage.
DIMENSIONS
SPECIFICATIONS
VOL AGE 24 VAC
POWER CONSUMP ION 1 VA
SWI CHING CAPACI Y 50 VA
MAX LOAD 5 Amps
MAX PRESSURE 160 PSI (11.25 kg/cm2)
MAX WA ER EMPERA URE 250°F (121°C)
MAX AMBIEN EMPERA URE 170°F (77°C)
1100-051118

Other safgard Controllers manuals

safgard 250 User manual

safgard

safgard 250 User manual

safgard 1100M User manual

safgard

safgard 1100M User manual

Popular Controllers manuals by other brands

EGS Sola Hevi Duty MCR Installation and operation manual

EGS

EGS Sola Hevi Duty MCR Installation and operation manual

Apollo AAN-1 Hardware manual

Apollo

Apollo AAN-1 Hardware manual

AMALGAMATED INSTRUMENT LD4-LN Operation and instruction manual

AMALGAMATED INSTRUMENT

AMALGAMATED INSTRUMENT LD4-LN Operation and instruction manual

Bosch 2600 Series instruction manual

Bosch

Bosch 2600 Series instruction manual

Cooper i-on 40 Setup guide

Cooper

Cooper i-on 40 Setup guide

CentriPro Aquavar SPD series Quick start up guide

CentriPro

CentriPro Aquavar SPD series Quick start up guide

Deif AGC 200 Series Operator's manual

Deif

Deif AGC 200 Series Operator's manual

Evco EVF 300 Series Installer manual

Evco

Evco EVF 300 Series Installer manual

Ledj FF-1 user manual

Ledj

Ledj FF-1 user manual

Siemens RVL471 Basic documentation

Siemens

Siemens RVL471 Basic documentation

Adaptec PowerDomain 29160 installation guide

Adaptec

Adaptec PowerDomain 29160 installation guide

Gira KNX 2139 00 Product documentation

Gira

Gira KNX 2139 00 Product documentation

Alicat Scientific MC Series operating manual

Alicat Scientific

Alicat Scientific MC Series operating manual

warmth R8C.963 instructions

warmth

warmth R8C.963 instructions

Deif Multi-line 2 Designers reference handbook

Deif

Deif Multi-line 2 Designers reference handbook

B&B Electronics RS-485 Digital I/O Module 485SDD16 user manual

B&B Electronics

B&B Electronics RS-485 Digital I/O Module 485SDD16 user manual

YUNEEC ST10+ quick start guide

YUNEEC

YUNEEC ST10+ quick start guide

industrie technik evolution AHU-XXXSX1 series user manual

industrie technik

industrie technik evolution AHU-XXXSX1 series user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.