manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Field Controls
  6. •
  7. Controllers
  8. •
  9. Field Controls 46334900 User manual

Field Controls 46334900 User manual

P/N 46334900
INSTALLATION INSTRUCTIONS
Designed for use with the SWG Series Power Venter for controlling Natural Gas or L.P. Gas
appliances. Items included in Kit:
1) Junction box with mounted pressure switch and post purge timer
1) Fan control gas pressure switch
1) 2 ft. length of 1/4 inch aluminum tubing
2) Flexible conduit connector
1) 1/4 inch tubing connector
MOUNTING JUNCTION BOX:
The junction box can be mounted at the venter or remotely mounted away from the venter. (See Fig. 1
& Fig. 2)
1. Remove one of the knockouts from the side of the
junction box where the pressure switch is mounted.
Install the flexible conduit connector onto the CK-
40F junction box and secure with fastening nut. If
remote mounting the CK-40F junction box, mount
the flexible conduit connector onto a 2" x 4"
installer supplied junction box.
2. Fasten the flexible conduit from the SWG Venter
into the conduit connector. Mount the CK-40F
junction box or installer supplied junction box onto
the wall or floor joist without straining the flexible
conduit. Fasten the CK-40F junction box through
the four dimpled locations on the base of the box.
(See Fig. 3)
Page 2
PRESSURE SWITCH SENSING TUBE INSTALLATION:
1. Attach the 1/4 inch tubing connector to the pressure tube on the SWG Venter. (See Fig. 3)
2. Connect the supplied 1/4" aluminum tubing to the tubing connector. Route the tubing to the CK-
40F junction box and connect the tubing to the pressure switch. When routing the tubing, avoid
kinking the tubing by bending the tubing too sharply.
For remote mounted CK-40F Junction Box, use a 1/4" OD copper, aluminum or plastic tubing and
route the tubing to avoid contact with any heat source.
PROVING SWITCH ADJUSTMENTS:
After proper air flow is established, the pressure switch
adjustment is made by turning the pressure switch
adjustment screw clockwise (See Fig. 4) until burner
operation stops. Turn the adjustment screw
counterclockwise until burner ignites. Turn the adjustment
screw an additional 1/4 to 3/4 turn counterclockwise to
ensure adequate switch adjustment.
Warning: Failure to properly adjust the pressure switch
as specified above could lead to improper operation of
the pressure switch which will result in a hazardous
condition and bodily harm!
THERMOSTAT HEAT ANTICIPATOR ADJUSTMENT:
After venting kit installation and checkout, check the amperage current draw through the thermostat
circuit and adjust the thermostat anticipator accordingly.
Page 3
Figure 1
Figure 2
Figure 3
Figure 4
WIRING INSTRUCTIONS
CAUTION: DISCONNECT ELECTRICAL POWER WHEN WIRING POWER VENTER
Wire the venter motor and controls in accordance with the National Electrical Code, manufacturer's
recommendations and/or applicable local codes. UNITS MUST BE GROUNDED. Check ground
circuit to make certain that the unit has been properly grounded. The wiring should be protected by an
overcurrent circuit device rated at 15 amperes. CAUTION must be taken to ensure that the wiring
does not come into contact with any heat source. All line voltage and safety control circuits, between
the venter and the appliance, MUST be wired in accordance with the National Electrical Code for class
one wiring or equivalent methods. Route the venter motor and control wiring with an appropriate wiring
method. Refer to Wiring Diagrams A and B.
LOW VOLTAGE WIRING INSTRUCTIONS FOR BOILERS AND WARM AIR FURNACES:
1. With boilers, locate terminal on spark ignition module or gas valve (if standing pilot) which would
normally be 24 volts hot on a call for heat. With spark ignition systems, this terminal could be TH-
W, 24 V, THS or T1 depending on the spark ignition control.
With warm air furnaces, locate terminal W in furnace junction box.
2. Remove wire from this terminal and reroute to T1 on CK-40F.
3. With boilers, connect T3 on CK-40F to hot side of gas valve (if standing pilot) or to terminal TH-W,
24 V, THS or T1 if spark ignition.
NOTE: Remember, the correct terminal is the one that would normally be hot on a call for heat.
With warm air furnaces, connect T3 on CK-40F to terminal W in furnace junction box.
4. Connect T2 on CK-40F to a 24 volt neutral where convenient.
LINE VOLTAGE WIRING INSTRUCTIONS:
1. Connect 120 volts hot power source wire to terminal L1 on CK-40F.
2. Connect 120 volts neutral power source wire and white wire from venter motor to terminal N on
the CK-40F.
3. Connect black wire from venter motor to terminal M on the CK-40F.
REFER TO THE SWG VENTER INSTALLATION INSTRUCTIONS FOR SETTING SYSTEM AIR FLOW.
Page 4
SYSTEM CONTROL CHECK OUT PROCEDURES:
1. For furnaces or boilers, adjust the thermostat to call for heat and observe the power venting
system for proper operation sequence. (Repeat if necessary)
a. Thermostat calls for heat.
b. Relay is energized and venter motor starts.
c. Pressure switch closes and burner starts.
d. Thermostat is satisfied, the burner stops.
e. This starts the post purge cycle. Purge time 1 to 2 min.
2. While system is operating, disconnect power to the venter motor. This should open the pressure
switch contacts and stop burner operation.
TROUBLE SHOOTING HINTS
1. Venter does not activate when thermostat calls for heat.
a. Check wiring.
b. Check gas pressure switch for continuity across terminals when gas valve is pressurized.
c. Check gas pressure.
2. Flue gas odor:
a. Check system draft.
b. Check for negative pressure in building.
Page 5
Diagram A
INTERNAL WIRING FOR CK-CONTROL KIT: DIAGRAM A & B
L1 TO 1 ON POST PURGE TIMER T2 TO TIMER RELAY BASE
M TO 3 ON POST PURGE TIMER T3 TO N/O ON PRESSURE SWITCH
T1 TO COMMON ON PRESSURE SWITCH TIMER BASE TO COMMON ON PRESSURE
SWITCH
REPAIR AND REPLACEMENT PARTS LIST FOR CK-CONTROL KIT
Pressure Switch P/N 46273100
Post Purge Timer P/N 46282800
Page 6
DO NOT DESTROY
THESE INSTRUCTIONS MUST REMAIN WITH EQUIPMENT
Installation Information
Model No.: _______________________________________
Installer’s Name: __________________________________
Installer’s Company:________________________________
Phone No.: _______________________________________
Date of Installation: ________________________________
Page 7
Diagram B

This manual suits for next models

1

Other Field Controls Controllers manuals

Field Controls 46294900 User manual

Field Controls

Field Controls 46294900 User manual

Field Controls SWGII-4CC User manual

Field Controls

Field Controls SWGII-4CC User manual

Field Controls 46304000 User manual

Field Controls

Field Controls 46304000 User manual

Field Controls 46457800 User manual

Field Controls

Field Controls 46457800 User manual

Field Controls 46298500 User manual

Field Controls

Field Controls 46298500 User manual

Field Controls 46400900 User manual

Field Controls

Field Controls 46400900 User manual

Field Controls 46262500 User manual

Field Controls

Field Controls 46262500 User manual

Field Controls HHSC+ User manual

Field Controls

Field Controls HHSC+ User manual

Field Controls 46382500 User manual

Field Controls

Field Controls 46382500 User manual

Field Controls 960524 User manual

Field Controls

Field Controls 960524 User manual

Field Controls FAVC User manual

Field Controls

Field Controls FAVC User manual

Field Controls 46335000 User manual

Field Controls

Field Controls 46335000 User manual

Field Controls 4615900 User manual

Field Controls

Field Controls 4615900 User manual

Field Controls CK-61 User manual

Field Controls

Field Controls CK-61 User manual

Field Controls CAC-24 User manual

Field Controls

Field Controls CAC-24 User manual

Field Controls 1986800 User manual

Field Controls

Field Controls 1986800 User manual

Popular Controllers manuals by other brands

Asentria SiteBoss 550 user manual

Asentria

Asentria SiteBoss 550 user manual

dixell iCHILL 100CX EVO Quick reference guide

dixell

dixell iCHILL 100CX EVO Quick reference guide

iseg Crate Controller 2 Series Technical documentation

iseg

iseg Crate Controller 2 Series Technical documentation

Mercoid MPCJR Series Specifications-installation and operating instructions

Mercoid

Mercoid MPCJR Series Specifications-installation and operating instructions

Epever MPPT user manual

Epever

Epever MPPT user manual

Oldham WX16 user manual

Oldham

Oldham WX16 user manual

National Instruments sbRIO-9607 user manual

National Instruments

National Instruments sbRIO-9607 user manual

Shinko DCL-33A Communication instruction manual

Shinko

Shinko DCL-33A Communication instruction manual

Ikelite EV-Controller instruction manual

Ikelite

Ikelite EV-Controller instruction manual

Ametek Dunkermotoren BGE 6005 A Operation manual

Ametek

Ametek Dunkermotoren BGE 6005 A Operation manual

Trinamic TMCM-3110 Hardware manual

Trinamic

Trinamic TMCM-3110 Hardware manual

McQuay MicroTech III RAH Operation and maintenance manual

McQuay

McQuay MicroTech III RAH Operation and maintenance manual

REV Robotics SPARK user manual

REV Robotics

REV Robotics SPARK user manual

EAE UD105 product manual

EAE

EAE UD105 product manual

Samson 42-24 Mounting and operating instructions

Samson

Samson 42-24 Mounting and operating instructions

DINUY PE K5X 002 instruction manual

DINUY

DINUY PE K5X 002 instruction manual

Savant SmartLighting 2 Quick reference guide

Savant

Savant SmartLighting 2 Quick reference guide

Doepke DFA operating instructions

Doepke

Doepke DFA operating instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.