
Rotar Plus 20-25 Easytronic - Cod.197AA2702 - Edition 00 01/2004 7
GB
MODIFIABLE PARAMETERS
Pressing the key with the machine OFF, the operating parameters menu will be displayed; in certain cases a password
is required in order to make changes. The menu is scrolled using the keys and .
0) control unit ID (service password): selects the identification code of the control unit; if several compressors are connected
to the same RS485 line, multiple IDs can be selected.
1) Pre-alarm time lapse (service password): each hour of operation clocked by the machine is counted down automatically;
when the count reaches 0, the control unit trips a Maintenance alarm.
The count, preceded by a minus sign (-), indicates how many hours have elapsed since the last maintenance alarm; the keys
and can be used to set a new value (entering the new value has the effect of overriding the previous alarm).
2) Alarm history (no password required): this menu can be used to display the 30 most recent alarms.
3) Pre-alarm temperature (factory password): this menu is used to set the delta temperature (delta, in °C) referred to the
maximum alarm temperature; the value can be set between 1 and 20.
Example: if the maximum temperature is 120 °C and the differential is 10 °C, the maximum temperature pre-alarm will trip at 110 °C.
4) Maximum temperature (factory password): this menu is used to set the maximum permissible temperature; the adjustment
range is 0 to 150 °C.
5) Minimum temperature (factory password): this menu is used to set the minimum temperature; the adjustment range is 0 to -14 °C.
7) Duration of loadless operation (service password): this menu is used to change the duration of the no-load cycle; the range
of adjustment is 1 to 250 seconds.
8) Auto start (service password): this parameter enables automatic Start; if activated, the compressor will restart automatically
following an electrical power supply failure.
If the compressor starts up unexpectedly, persons happening to be nearby could be harmed or injured. With this in mind, use
of the automatic start function is not generally recommended.
9) Internal phase sequence (service password): this parameter enables control of the phase sequence internally, or disables
internal control and activates the phase sequence control input at the terminals.
10) Language (no password required): this parameter is used to select the language in which messages are displayed; there
are 5 available (English, French, German, Italian, Spanish).
11) Enable RS485 (no password required): this parameter is used to enable data transmission using RS485, and automatically
disable transmission on RS232.
12) Pressure sensor (service password): enables the 4-20 mA input to which the pressure sensor is connected. With this
parameter activated, the pressure measurement is displayed. To display machine operation time, press the key; the display will
revert to the pressure measurement automatically after 20 seconds.
Enabling this parameter, the external pressure switch contact changes function and becomes an input for the oil separator
minimum pressure switch; in this situation, the compressor is prevented from restarting if pressure in the oil separator is high.
13) PSI/BAR (no password required): selects the unit of measure used to display pressure.
14) No-Load/operating pressure set point (no password required): this parameter is used to set the pressure at which the
compressor must switch off; if inverter drive is enabled, it indicates the operating pressure at which the inverter will begin modulating
output to maintain the pressure steady.
15) Load/operating Delta set point (no password required): indicates the pressure at which the control unit enables compressor
restart.
For example, if the set differential value is 1 bar and maximum operating pressure is 9 bar, this means that the compressor will
switch off at 9.5 bar and switch on again at 8.5 bar.
16) Maximum pressure (service password): this parameter sets the maximum pressure value permissible in operation, i.e. the
maximum pressure of point 14.
17) Maximum alarm pressure (factory password): this parameter sets the maximum pressure value at which an alarm is
tripped in the control unit.
18) Remote pressure(service password): enabling this parameter, the pressure and the relative alarms continue to be displayed,
but the compressor starting sequence is controlled from an external pressure switch contact.
19) Load delay(factory password): this parameter sets the delay, in seconds, from the moment when the starting cycle terminates
to the moment when the air solenoid valve energizes.
AL AYS HIT KEYS AND PRESS TO CONFIRM ENTRY
°C
°C
°C
sec.
Hours
Max.
20
150
0
250
2768
NO
NO
BAR
Min.
0
0
-14
1
0
YES
YES
PSI
Standard
5
110
-7
20
000
NO
YES
BAR
MODIFIABLE PARAMETERS
Oil temperature pre-alarm (differential)
Maximum oil temperature
Minimum oil temperature
No-load (EMPTY) time
Maintenance pre-alarm
Automatic start
Pressure sensor
PSI/BAR
bar
bar
bar
bar
sec.
No-Load/operating pressure set point
Load/pressure differential set point
Maximum permissible pressure
Maximun alarm pressure
Load (CHARGED) delay
Internal phase sequence control
Language
Display contrast level
Enable RS485
Min.
0
0
0
0
0
YES
1
SI
Max.
15
15
15
16
200
NO
20
NO
Standard
10
8,5
11
1
10
YES
ITA
5
SI
SETTINGS AND CONTROLS