Fire-Lite Alarms Honeywell MMF-302-6 User manual

BEFORE INSTALLING
This information is included as a quick reference installation guide. Refer to
the appropriate Fire•Lite control panel installation manual for detailed sys-
tem information. If the modules will be installed in an existing operational
system, inform the operator and local authority that the system will be tempo-
rarily out of service. Disconnect the power to the control panel before install-
ing the modules. This system contains static sensitive components. Always
ground yourself with a proper wrist strap before handling any circuits so that
static charges are removed from the body. The module housing should also
be grounded.
GENERAL DESCRIPTION
The MMF-302-6 Six Zone Interface Module is intended for use in an intelli-
gent alarm system. Each module provides an interface between the intelligent
alarm system and a conventional alarm system loop. A common SLC input is
used for all modules, and the initiating device loops share a common super-
visory supply and ground. Otherwise, each monitor operates independently
from the others. Each module has its own unique address.
A pair of rotary code switches is used to set the address of the first module
from 01 to 154. The remaining modules are automatically assigned to the next
five higher addresses. Provisions are included for disabling a maximum of two
unused modules to release the addresses to be used elsewhere. Each mod-
ule also has panel controlled bicolor LED indicators. The panel can cause the
LEDs to blink, latch on, or latch off.
A list of compatible two-wire System Sensor Smoke detectors for use with the
MMF-302-6 is available on the System Sensor website at systemsensor.com.
Included:
(5) 1 x 4 Terminal Blocks (2) 1.25" Stand offs (3) Shunts
(4) Machine Screws (2) Nuts (1) Long Power Supply Jumper
(6) 3.9k Ohm End of Line Resistors
C0202-00
Shipped on Board:
(2) Shunts in Class A/B position
(Shipped in Class B position, remove shunts for Class A)
1 I56-1900-023
7/1/2022
SPECIFICATIONS
MMF-302-6 Six Zone Interface Module
COMPONENTS
Following are descriptions of the MMF-302-6 mounting frameworks. There are
two mounting options for MMF-302-6 modules:
• Up to six MMF-302-6 modules can be installed on a CH-6 in a BB-6F
cabinet
• One or two MMF-302-6 modules can be installed in a BB-2F cabinet
Chassis
The CH-6 chassis is used to mount MMF-302-6 modules in a BB-6F cabinet.
It accommodates up to six MMF-302-6 modules in a single cabinet row three
modules wide and two modules deep.
FIGURE 1. CH-6 CHASSIS
C0206-00
The BB-2F cabinet has a built-in chassis that will accommodate one or two
MMF-302-6 modules.
FIGURE 2. BB-2F CABINET
0
1
2
3
456789
0
78
6
5
4
3
21
910
11
12
13
14
15
BASEADDRESS
ADDRESS
DISABLE
NONE
ONE
TWO
THREE
0
1
2
3
456789
0
78
6
5
4
3
21
910
11
12
13
14
15
BASEADDRESS
ADDRESS
DISABLE
NONE
ONE
TWO
THREE
C0234-00
The front MMF-302-6 module positions of each chassis are offset below the
rear MMF-302-6 module positions so that all of the status indicators are visible.
Cabinets
A BB-6F will house the CH-6 chassis with up to six MMF-302-6 modules in-
stalled on it. Refer to cabinet installation documents for dimensions.
I56-1900-023
INSTALLATION AND MAINTENANCE INSTRUCTIONS
One FireLite Place
Northford, CT 06472
Phone: 203.484.7161
Normal Operating Voltage: 15-32 VDC
Stand-By Current: 2.3 mA @ 24 V
Alarm Current: 40 mA (assumes all six LEDs solid on)
Temperature Range: 32°F to 120°F (0°C to 49°C)
Humidity: 10 to 93% Non-condensing
Dimensions: 6.8˝H x 5.8˝W x 1.25˝D
Accessories: CH-6 Chassis; BB-6F Cabinet; BB-2F Cabinet
Wire Gauge: 12-18 AWG
Maximum IDC Wiring Resistance: 25 Ohms
External Power Supply Voltage: Regulated 24 VDC
Ripple Voltage: 0.1 volts RMS maximum
IDC (supervised and power limited)
DC Voltage: 18-28 volts power limited
Frequency: DC
Alarm Current: 90mA per circuit
Standby Current 6 circuits: 42mA Maximum @18 VDC
56mA Maximum @24 VDC
66mA Maximum @28 VDC NOTICE: This manual should be left with the owner/user of the equipment.

The BB-2F cabinet houses one or two MMF-302-6 modules on the internal
chassis that is part of the cabinet. Refer to cabinet installation documents for
dimensions.
INSTALLATION STEPS
1. Cabinet Mounting
In a clean, dry area, mount the backbox using the four holes provided in the
back surface of the cabinet (Figure 3).
2. Chassis Installation
The CH-6 chassis is mounted in the BB-6F cabinet. It is attached to the two
PEM studs on the back wall of the cabinet with two 8-32 hex nuts. The hex
nuts are included with the chassis (Figure 4).
FIGURE 3. TYPICAL MOUNTING HOLE LOCATIONS
BACKBOX
MOUNTING
HOLES
C0235-00
FIGURE 4. MOUNTING THE CH-6 CHASSIS
Mount with hex nuts to PEM studs
on back of cabinet
C0239-00
The BB-2F cabinet comes with the chassis already installed, so no mounting
is necessary.
3. Module Installation
There are two methods for installing a module in the rear position of a chas-
sis. Method one is for installation of a rear module only, when no module will
be installed in front of it. Refer to Figure 5 for instructions. Method two is for
installation of a rear module when another module will be installed in the
chassis position in front of it. Refer to Figures 6a and 6b for method two. All
necessary screws and standoffs are supplied with the modules.
FIGURE 5. INSTALLATION OF REAR MODULE ONLY, METHOD ONE
2
3
1
C0237-00
Step 1: Insert the bottom of the MMF-302-6 module down into a
rear slot on the chassis.
Step 2: Carefully swing the upper edge of the board back towards the back of
the chassis until it touches the two standoffs.
Step 3: Align two 4-40 screws with the two standoffs and tighten.
Step 4: Address and wire the modules according to the instructions in this
manual.
The steps in Figures 6a and 6b describe and illustrate module installation
when the rear chassis position and the position in front of it will be filled.
Front position installation is possible only if the rear position is filled with
another module.
FIGURE 6A. INSTALLATION OF MMF-302-6 MODULE IN A REAR
CHASSIS POSITION, METHOD TWO
1
C0225-00
Step 1: Insert the bottom edge of the MMF-302-6 module down into a rear
slot of the chassis.
Step 2: Carefully swing the upper edge of the board towards the back of the
chassis until it touches the short standoff attached to the chassis.
Step 3: Align the long standoff with the short standoff and tighten.
FIGURE 6B. INSTALLATION OF MMF-302-6 MODULE IN FRONT CHASSIS
POSITION
2
3
1
C0226-00
Step 1: Insert the bottom edge of the MMF-302-6 module down into a front
slot of the chassis.
Step 2: Carefully swing the upper edge of the board towards the back of the
chassis until it touches the 1.25˝ (32 mm) standoffs installed on the
rear module.
Step 3: Align two 4-40 screws with the two standoffs and tighten.
Step 4: Address and wire the modules according to the instructions in this
manual.
WIRING
NOTE: All wiring must conform to applicable local codes, ordinances, and
regulations.
1. Install module wiring in accordance with the job drawings and appropri-
ate wiring diagrams.
2. All wiring to the MMF-302-6 is done via terminal blocks. In order to
properly make electrical connections strip approximately 0.25˝ of insu-
lation from the end of wire, sliding the bare end of the wire under the
clamping plate screw.
3. Set the address on the modules per the job drawing. Use the rotary code
switches to set the address of the first module (between 01 and 154).
In Class B operation, the remaining modules are automatically assigned to the
next five higher addresses. For example, if the base address switch is set to 28,
the next five modules will be addressed to 29, 30, 31, 32 and 33.
The module is shipped in Class B position, remove shunts for Class A. When
operating in Class A, alternate modules are paired together (+0/+1, +2/+3,
+4/+5), resulting in a total of three modules. For example, if the base ad-
dress switch is set to 28, then 30 and 32 will be automatically assigned to the
modules while 29, 31 and 33 are available to be used for other modules on the
SLC. For Class A and B operation, DO NOT set the lowest address above 154,
as the other modules will be assigned to nonexistent addresses.
NOTE: Some panels support extended addressing. In order to set the module
above address 99 on compatible systems, carefully remove the stop on the
upper rotary switch (see Figure 7). If the panel does not support extended ad-
dressing, do not set the lowest address above 94.
2 I56-1900-023
7/1/2022

WIRING NOTES
• Power-limited circuits must employ type FPL, FPLR, or FPLP cable as
required by Article 760 of the NEC.
• All wiring must be in accordance with the NEC, NFPA 72 and all other
applicable codes and standards. All external power supplies must be
power limited with battery back-up. All external power supplies and
detectors must be UL listed for fire protection signaling applications.
PROGRAMMING
Connect the module to listed-compatible control panels only. Refer to panel
installation documentation to confirm compatibility.
The modules are programmed as devices in each system according to the pro-
gramming instructions in the appropriate FACP manual.
3 I56-1900-023
7/1/2022
4. A shunt is provided to disable a maximum of
two unused modules in Class B operation and
Class A operation. Modules are disabled from
the highest address and work downward. If
two modules are disabled, the lowest four ad-
dresses will be functional, while the highest
two will be disabled. For example, in Class B
operation, if the shunt for Address Disable is
placed on “two” and the base switch is set to 28,
the modules will be assigned to 28, 29, 30 and 31 while disabling the
highest two positions.
NOTE: Place unused shunts on single pin to store on board for future use.
NOTE: Power must not be applied to the unit when changing functionality of
the shunts.
FIGURE 8. INTERFACE TWO-WIRE CONVENTIONAL DETECTORS – CLASS B
1. To use a common power supply between multiple MMF-302-6 modules, connect a long power supply jumper from T5 or T6 to T5 or T6 on the adjacent
MMF-302-6 module.
0
1
2
3
456789
BASE ADDRESS
TO NEXT DEVICE
–
STATUS
INDICATORS
—
+
—
+
—
+
—
+
—
+
—
+
IN
OUT
+0
+1
+2
+3
+4
+5
IDC
ADDRESS
IDC
ADDRESS
IDC
ADDRESS
—
+
—
+
SLC
—
+
—
+
+
–
+
FROM PANEL OR
PREVIOUS DEVICE
3.9K EOL
RESISTOR
(INCLUDED)
CONNECT MODULES TO
LISTED COMPATIBLE
FIRE•LITE CONTROL
PANELS ONLY
SIGNAL LINE CIRCUIT 32 VDC MAX.
TWISTED PAIR IS RECOMMENDED.
CLASS B IDC (TYPICAL)
A/B SELECT
A/B SELECT
DISABLE 1
DISABLE 2
0
1
2
3
45678910
11
12
13
14
15
+
–
+
–
T6 T5
DETECTORS MUST BE UL LISTED COMPATIBLE WITH THE MODULE.
INSTALL DETECTORS PER MANUFACTURER'S INSTALLATION INSTRUCTIONS.
(–)
(+)
TO PANEL CONTROLLED
RESETTABLE POWER SUPPLY
EXTERNAL SUPPLY
POWER-LIMITED
AND SUPERVISED
C0779-04
FIGURE 9. INTERFACE TWO-WIRE CONVENTIONAL DETECTORS – CLASS A
1. To select Class A, remove the two shunts from the “A/B select” positions.
2. To use a common power supply between multiple MMF-302-6 modules, connect a long power supply jumper from T5 or T6 to T5 or T6 on the adjacent
MMF-302-6 module.
Detectors must be UL listed compatible with the module. Install detectors per
manufacturers installation instructions.
0
1
2
3
456789
BASE ADDRESS
TO NEXT DEVICE
–
STATUS
INDICATORS
—
+
—
+
—
+
—
+
—
+
—
+
IN
OUT
+0
+1
+2
+3
+4
+5
IDC
ADDRESS
IDC
ADDRESS
IDC
ADDRESS
—
+
—
+
SLC
—
+
—
+
+
–
+
FROM PANEL OR
PREVIOUS DEVICE
CONNECT MODULES TO LISTED COMPATIBLE
FIRE•LITE CONTROL PANELS ONLY
SIGNAL LINE CIRCUIT 32 VDC MAX.
TWISTED PAIR IS RECOMMENDED.
CLASS A IDC (TYPICAL)
A/B SELECT
A/B SELECT
DISABLE 1
DISABLE 2
0
1
2
3
45678910
11
12
13
14
15
T6 T5
IDC 2
IDC 3
(–)
(+)
EXTERNAL SUPPLY
POWER-LIMITED
AND SUPERVISED
+
–
+
–
TO PANEL CONTROLLED
RESETTABLE POWER SUPPLY
C0780-03
TENS
0
78
6
5
4
3
21
910
11
12
13
14
15
FIGURE 7

4 I56-1900-023
©2022 Fire•Lite. 7/1/2022
FIGURE 10. EXAMPLE OF MULTIPLE BOARDS SHARING SAME EXTERNAL SUPPLY
Refer to figures 8 and 9 for typical wiring. Make certain lip on long power supply jumper engages retaining tab on T5 or T6 as shown in View A-A.
—
+
—
+
—
+
—
+
—
+
—
+
IN
OUT
+0
+1
+2
+3
+4
+5
IDC
ADDRESS
IDC
ADDRESS
IDC
ADDRESS
—
+
—
+
SLC
—
+
—
+
A/B SELECT
A/B SELECT
DISABLE 1
DISABLE 2
T6 T5
EXTERNAL SUPPLY
—
+
—
+
—
+
—
+
—
+
—
+
IN
OUT
+0
+1
+2
+3
+4
+5
IDC
ADDRESS
IDC
ADDRESS
IDC
ADDRESS
—
+
—
+
SLC
—
+
—
+
A/B SELECT
A/B SELECT
DISABLE 1
DISABLE 2
T6 T5
EXTERNAL SUPPLY
EXTERNAL
POWER
SUPPLY
—
+
PCB 1 PCB 2
VIEW A-A
0
1
2
3
456789
BASE ADDRESS
0
1
2
3
45678910
11
12
13
14
15
0
1
2
3
456789
BASE ADDRESS
0
1
2
3
45678910
11
12
13
14
15
C0781-00
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this
device must accept any interference received, including interference that may cause undesired operation.
Note: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to
provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not
installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not
occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off
and on, the user is encouraged to try to correct the interference by one or more of the following measures:
– Reorient or relocate the receiving antenna.
– Increase the separation between the equipment and receiver.
– Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
– Consult the dealer or an experienced radio/TV technician for help.
FCC STATEMENT
DEVICE AND SYSTEM SECURITY
Before installing this product ensure that the tamper seal on the packaging is present and unbroken and the product has not been tampered with since leaving the factory. Do not
install this product if there are any indications of tampering. If there are any signs of tampering the product should be returned to the point of purchase.
It is the responsibility of the system owner to ensure that all system components, i.e. devices, panels, wiring etc., are adequately protected to avoid tampering of the system that could
result in information disclosure, spoofing, and integrity violation.
Fire•Lite® Alarms is a registered trademark of Honeywell International, Inc.