
DF-51276 Page 3 of 4
COMPATIBLE ADDRESSABLE DEVICES
SD300(A) Addressable Photoelectric Smoke Detec-
tor. Includes mounting plate and plug-in
wiring terminal block.
SD300T(A) Same as SD300, plus a 135°F thermostat
heat detector.
CP300(A) Addressable Ionization Smoke Detector.
BG-10LX(A) Addressable Manual Station based on the
popular FireLite BG-10L dual-action
station.
M300(A) Addressable Monitor Module for one zone
of normally open dry contact initiating
devices. Mounts in standard 4" box.
Includes plastic cover plate and end-of-
line resistor. Features polling/alarm LED
and decimal address switches. May be
configured for either Style B (Class B) or
Style D (Class A) operation.
M301(A) Miniature version of M300. Excludes LED
and Style D option. Connects with wire
pigtails. May mount in device backbox.
M302(A) Similar to M300, but may monitor up to 20
conventional 2-wire detectors. Requires
external 24 VDC power. (Consult factory
for compatible smoke detectors.)
C304(A) Addressable Control Module for one Style
Y/Z (Class B/A) zone of supervised
polarized Notification Appliances, or may
be configured as a dry contact (Form-C)
relay rated at 2 amps. Mounts in standard
4" box. Features polling LED and decimal
address switches. Notification Appliance
Circuit option requires external 24 VDC
power. (Consult factory for compatible
Notification Appliances.)
I300(A) This module isolates the SLC loop from
short circuit conditions (required for Style 7
operation).
NOTES: 1) A suffix should be included only when order-
ing ULC listed units (e.g. SD300A, M300A). 2) For more
detailed information on Compatible Addressable Devices
for use with the MS-9200, please see the following data
sheets (document numbers): SD300/SD300T (DF-51320),
CP300 (DF-51311), MS-9200 Addressable Modules (DF-
51339), and BG-10LX (DF-51366).
COMPATIBLE ANNUNCIATORS
LCD-40 Series: 40-character, backlit LCD-type fire an-
nunciators capable of displaying English-language text
(requires one DIM-485 per MS-9200 panel to interface
with up to 32 LCD-40 annunciators).
AFM/AFM-X Series: LED-type fire annunciators ca-
pable of providing up to 56 software zones of annuncia-
tion. Available in increments of 16 or 32 with expandable
(AFM-X Series) and non-expandable (AFM Series) con-
figurations to meet a variety of applications.
LDM Series: Lamp Driver Module series for use with
custom graphic annunciators.
NOTE: For more detailed information on Compatible
Annunciators for use with the MS-9200, please see the
following data sheets (document numbers): LCD-40 (DF-
51474), AFM/AFM-X (DF-51465), and LDM Series (DF-
51384).
FIELD-PROGRAMMING FEATURES
Off-Line Programming: Create entire program in your
office using a Windows®-based PC computer (order pro-
gramming kit PK-9200W separately). Upload/Download
system programming locally to the MS-9200 in less than
one minute.
Auto-Programming: Command the MS-9200 to pro-
gram itself (takes less than 30 seconds). In the Auto-
Program mode, the MS-9200 scans for all possible de-
vices at all addresses, stores the device types, and ad-
dresses found, and then loads default values for all op-
tions (General Alarm). It also checks for two or more
devices set to the same address.
On-Line Edit: While still providing fire protection, the
MS-9200 may be programmed from the front panel. Sim-
ple menu trees displayed on the LCD allow the trained
user to perform all functions without referring back to the
programming manual.
English Label Library: Quickly select labels from a
standard library of more than 50 adjectives/nouns, such
as FLR 3 HALLWAY, or enter custom labels letter-by-
letter. Use recall function to repeat previously used label.
Program Check: Automatically catch common errors,
such as relays not linked to any zone or point.
MAINTENANCE ALERT
The MS-9200 continually monitors each smoke detector
and responds to a reading of 80% of the detectors alarm
threshold. If the detector continually reports an 80% thresh-
old reading (8/10 of what is required to be an alarm condi-
tion) for 24 hours, a trouble condition is created. This
reduces the risk of false alarms due to dust and dirt by
alerting a trouble (maintenance) condition rather than initi-
ating a false alarm.
AUTOMATIC TEST OPERATION
The MS-9200 performs an automatic test of each detector
every 2 hours. Failure to meet the test limits causes an
AUTO TEST FAIL trouble type. System Reset clears this
trouble.
NFPA STANDARDS
The MS-9200 complies with the following NFPA 72-1993
Edition, Fire Alarm Systems:
LOCAL (Automatic, Manual, Waterflow, and Sprinkler
Supervisory).
AUXILIARY (Automatic, Manual, and Waterflow) (re-
quires RTM-8F).
REMOTE STATION (Automatic, Manual, and Water-
flow) (requires RTM-8F or UDACT-F).
PROPRIETARY (Automatic, Manual, and Waterflow).
CENTRAL STATION(Automatic, Manual,and Waterflow)
(requires UDACT-F).
SPECIFICATIONS
Primary input power: 120 VAC, 50/60 Hz, 2.3 Amps.
Total 24 V system power: 3.6 A (expandable to 6.6 A).
Standard Notification Circuits: 2 (Style Y or Z).