FBD-2 Fire Alarm Panel

FBD-2
2
Part Number 18165, A, 04/03/2023
Safety Instructions
Important
Before starting with installation of the FBD-2 Fire alarm panel, we recommend you read the
important information below.
Qualification
The installation of the product detailed in this manual must be done by a certified installation
company. If not, the warranty becomes void.
Caution:
Before installing the FBD-2 fire alarm unit, check if all parts are present.
The package includes:
•FBD-2
•Manual
Disclaimer:
Fireboy-Xintex will not be responsible for any damage or loss of profit resulting from the use of
this equipment.

FBD-2
3
Part Number 18165, A, 05/01/2023
Table of Contents
1. INSTALLATION MANUAL........................................................................................................4
Units.......................................................................................................................................4
Mechanical Installation..........................................................................................................4
Technical Specifications .........................................................................................................5
Electrical Installation..............................................................................................................5
Connecting Sensors................................................................................................................6
Power Supply .........................................................................................................................6
Zones......................................................................................................................................6
Key Switch Input ....................................................................................................................6
Fault Output...........................................................................................................................6
Alarm Output .........................................................................................................................6
Buzzer Output ........................................................................................................................6
2. CONFIGURING THE FBD-2 FIRE ALARM PANEL......................................................................7
Short Circuit as Alarm ............................................................................................................7
3. USER MANUAL.......................................................................................................................8
Operation...............................................................................................................................8
Silence Button........................................................................................................................8
Dimming Button.....................................................................................................................8
Test Button ............................................................................................................................8
Power LED..............................................................................................................................8
4. MAINTENANCE ......................................................................................................................8
5. TROUBLESHOOTING ..............................................................................................................9
NOTES......................................................................................................................................10

FBD-2
4
Part Number 18165, A, 04/03/2023
1. Installation Manual
Units
The fire alarm panel comes in the option shown in Table 1.
Unit
Number of zones
FBD-2
2
Table 1: Unit options
Mechanical Installation
The unit consists of two parts. The front panel and a backplate. The backplate can be mounted on
a wall or console. The connector on the back of the unit will protrude though the backplate into
the wall.
A ridge on the top of the unit holds the front panel in place. The front panel can be fastened using
a screw on the bottom of the unit.
Figure 1: Mounting options
Optionally, a wall mount box (P/N: 96016) can be provided to mount the unit on a wall without
needing a hole. This box provides space for the cabling.

FBD-2
5
Part Number 18165, A, 05/01/2023
Technical Specifications
Description
Specification
Supply voltage
9-32V DC
Zone loop voltage
24V DC (regardless of input voltage)
Minimum alarm current
15mA
Maximum current per zone
400mA
Maximum sensors per zone
8
EOL resistor
5.6kΩ
Potential free transistor output (Fault, Alarm)
50V max
Relay output (Buzzer)
2A
Table 2: Specifications
Electrical Installation
Figure 2: Installation schematic
12/24V DC
24V DC Main
24V DC Backup
0V DC Main
0V DC Backup
To Zone 1
To Zone 2
Buzzer
Key Switch
(Optional)
12/24V DC
0V DC
0V DC
+
-
NO
1
11
22
12
-
+
C
NO
C

FBD-2
6
Part Number 18165, A, 04/03/2023
Connecting Sensors
Figure 3: Zone schematic
Power supply
The FBD-2 has a main and backup power supply input. A fault will be indicated on the front and
the fault output will be activated when one of the supplies fails. If only one supply is needed, the
main and backup supplies must be connected together to avoid generating a fault.
Zones
Unit has two zones. The zone output provides the sensor loop with 24V DC regardless of the
voltage supplied on the supply inputs. An End of Line resistor (EOL) of 5.6kΩshould be placed at
the end of the loop as show in Figure 3. Placing it at any other point will prevent open loop
detection from working properly. If a zone is unused the EOL resistor should still be connected.
Key Switch Input
A key switch can be added to only allow authorised personnel to accept a fire alarm. The switch
should be in the closed position when the key is turned. When no key switch is used this input
should be bridged.
Fault Output
Used with Vessel’s Monitoring System, contact factory for more information.
Alarm Output
Used with Vessel’s Monitoring System, contact factory for more information.
Buzzer Output
A buzzer can be connected to the buzzer contact. This is a potential free contact that closes when
a fire occurs. The voltage for the buzzer needs to be supplied externally.
Hochiki
+
-
5k6
EOL
1
2
6
5
1
2
6
5
Orbis
-
+
5k6
EOL
IN+
OUT+
COM-
IN+
OUT+
COM-

FBD-2
7
Part Number 18165, A, 05/01/2023
2. Configuring the FBD-2 Fire alarm panel
Short Circuit as Alarm
Some older non EN54 or BS5839 compliant systems do not use internal resistors. These systems
cause a short on the zone loop when a fire is detected. When such a system is used, the alarm
panel needs to be set to “short circuit as fire” via the jumper on the back. A short on the line will
now cause a fire alarm as a result, not a fault. Note that an actual short in the wiring can no longer
be detected and will also cause a fire alarm. The panel is set to “short circuit as fire” When the top
two pins are bridged using the jumper. When the bottom two pins are bridged, the panel is set to
“short circuit as fault”. The jumper should be placed as shown in Figure 4.
Note: Changing the jumper requires a restart to take effect
Short circuit a fire:
Short circuit as fault:
Figure 4: Short circuit jumper

FBD-2
8
Part Number 18165, A, 04/03/2023
3. User Manual
The FBD-2 fire alarm panel provides fire detection and alarm functionality.
Operation
The unit is always operational when powered. During normal operation the “OK”LED should be
on to indicate the zone is working properly.
The “FAULT”LED will blink, and an audible alarm will be generated when a fault is detected on a
zone. There are two fault situations:
Short:
There is a short in the zone cabling. The FBD-2 removes the power from the zone and indicates a
fault situation. When the “SILENCE” button is pressed the alarm will be muted, the “FAULT”LED
will light up without blinking and the “OK”LED will blink for one minute. After a minute the zone
will turn back on. A new fault will be generated if the short persists. A fault will not be generated
when the unit is configured for “short circuit as alarm”, a fire alarm will be generated instead.
Note that when a key switch is present, the alarm can only be accepted when the key is turned to
the closed position.
Open Circuit:
The EOL resistor is no longer detected. This indicates there is a break in the zone loop. When the
“SILENCE” button is pressed the alarm will be muted and the “FAULT”LED will light up without
blinking. When the EOL resistor is detected the “OK”LED will turn on and the zone will be
operational again once the “SILENCE” button has been pressed again.
Silence Button
Pressing the “SILENCE” button will accept and mute alarms, fire alarms can only be accepted if the
key is in the closed position or bridged.
When a fire is detected the “FIRE” LED will light up and an audible alarm will be generated. If the
fire alarm is accepted but still active after 2 minutes, the alarm will return.
Dimming Button
The front LEDs can be dimmed to preserve night vision. Press and hold the “DIM” button until the
LEDs reach the desired brightness. The “FAULT”and “FIRE”LEDs will not be dimmed for safety.
Test Button
The “TEST” button can be pressed to test the LEDs. Pressing the “TEST” button for 30 seconds will
also activate the buzzer and alarm and fault outputs.
Power LED
The “POWER” LED blinks green while the unit is in operation normally. If one of the power
supplies fails, the “POWER” LED will light up red.
4. Maintenance
The FBD-2 unit is maintenance free. It is permitted to clean the front of the FBD-2 unit with a
damp cloth.

FBD-2
9
Part Number 18165, A, 05/01/2023
5. Troubleshooting
Symptom
Possible Cause
Test and Remedies
Green LED is not flashing
Power supply is not connected
Check if power supply is
connected
Green LED light up without
flashing
Micro controller is in error.
Power the unit off and on
A fault is generated when a
manual call point is pressed
A shorting call point is used
The jumper should be set to
“short circuit as fire”
A short causes a fire alarm
instead of a fault
The unit is setup for shorting
call points
The jumper should be set to
“short circuit as fault”
Alarm or fault cannot be
accepted
The key switch contacts are not
bridged
The key is not in de closed
position or if the key is not
installed bridge the key switch
contact
Table 3: Troubleshooting
Do not use aggressive cleaning agents!

FBD-2
10
Part Number 18165, A, 04/03/2023
Notes
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
_____________________________________________________

FBD-2
11
Part Number 18165, A, 05/01/2023
1 Year Limited Warranty
This Warranty is in lieu of all other expressed or implied Warranties.
Seller warrants title, materials, and workmanship on equipment, except components
manufactured by others for which the Seller assigns, as permitted, the original manufacturer’s
warranty. Seller’s warranty shall be for a period of (1) one year from the date of sale to the
ORIGINAL CONSUMER PURCHASER, during which non-conforming equipment returned to the
Seller at Buyer’s expense and risk, be repaired, or replaced at the Seller’s option. Fireboy-Xintex
will repair or replace products found to be defective in materials or workmanship within the
period set forth above, provided that: (a) the product has not been subjected to abuse,
contamination, neglect, accident, incorrect wiring not our own, improper installation or servicing,
or used in violation of instructions furnished by Fireboy-Xintex and (b) as to any prior defects in
materials or workmanship covered by this warranty, the product has not been repaired or altered
by anyone except Fireboy-Xintex and (c) the serial number has not been removed, defaced or
otherwise changed, and (d) examination discloses, in the judgment of Fireboy-Xintex, does not
assume the costs of removal and/or installation of the product or any other incidental costs of
removal and/or installation of the product or any other incidental costs which may arise as a
result of any defect in material or workmanship, and (e) upon discovery of defect, Buyer shall
immediately cease use of and notify Fireboy-Xintex.
Any warranty implied by law, including warranties of merchantability or fitness, is in effect only
for the duration of the expressed warranties set forth above, no person is authorized to give any
other warranty, or to assume for Fireboy-Xintex any other liability in connection with the sale of
its products; Fireboy-Xintex shall not be liable for the loss of use, revenue, or profit or for any
injury, or for any other consequential or incidental damages, buyer is not relying on seller’s
judgment regarding his or her particular requirements, and has had an opportunity to inspect the
product to his or her satisfaction.
This warranty gives you specific legal rights, and you may also have other rights, which vary, from
location to location.
Contact information is listed below. For US customers, contact Fireboy-Xintex. For international
customers, contact Fireboy-Xintex UK Operations Limited.
www.fireboy-xintex.com
United Safety Acquisition Corporation
(d/b/a Fireboy-Xintex)
O-379 Lake Michigan Dr. NW
Grand Rapids, MI 49534
fireboy@fireboy-xintex.com
Phone (616) 735 9380
Fireboy-Xintex UK Operations Limited
10 Holton Road, Holton Heath Trading Park
Poole Dorset BH16 6LT UK
fireboyeu@fireboy-Xintex.com
Phone +44 (0) 845 389 9462
Table of contents
Other Fireboy- Xintex Fire Alarm manuals
Popular Fire Alarm manuals by other brands

SLAT
SLAT AES 56V 4A C48 SB operating instructions

Teletek electronics
Teletek electronics SensoIRIS WSOU Installation instruction

Fike
Fike 68-140 Installation and maintenance instructions

Apollo
Apollo Orbis IS installation guide

Fire-Lite Alarms
Fire-Lite Alarms MS-4424 manual

Dorgard
Dorgard DG1328-FP operating guide