Fireboy- Xintex DU-RBH-01 Original instructions

1
Part Number 18146, D, 08/01/2018
Deluxe Discharge Alarm
DU-RBH-01 (Round, Black, Horn)
DU-RCH-01 (Round, Chrome, Horn)
Owner’s Manual
&
Installation Instructions
Read and comply with all instructions, warnings and limitations before
installing, servicing or removing this device.

2
Part Number 18146, D, 08/01/2018
Additional copies of this manual are available at no charge by contacting the manufacturer,
distributor or dealer. Fireboy-Xintex reserves the right to change features without notice.
General Information
3
Specifications
3
Operation of Fireboy Deluxe Discharge Alarm(s)
3
Installation
5
Installing the Display Unit (DU-RBH-01/DU-RCH-01)
5
Electrical Connections (DU-RBH-01/DU-RCH-01)
5
Testing the DU-RBH-01/DU-RCH-01
5
Maintenance
5
In the Event of an Alarm
6
Repairing Fireboy Deluxe Discharge Alarm(s)
6
Returning Fireboy Deluxe Discharge Alarm(s)
6
1 Year Limited Warranty
7

3
Part Number 18146, D, 08/01/2018
General Information
The DU-RBH-01 and DU-RCH-01 Deluxe Discharge Alarms are an effective means to monitor the
status of your Fireboy Pre-engineered Fire Suppression system. The Deluxe Discharge Alarms
have both visual and audible indication of the Fire Suppression system’s status.
Specification
System Specifications (DU-RBH-01/DU-RCH-01)
Operating Voltage: 9-30 VDC
Nominal Current Draw: 25mA @ 12 VDC
Maximum Current Draw: 75mA @ 9 VDC
Operating Temperature: 22°F (-6°C) to 158°F (70°C)
Alarm Horn: ≈ 68dB
Operation of Fireboy Deluxe Discharge Alarm(s)
The Deluxe Discharge Alarm has a Green LED located on the front face of the unit. The LED will be
illuminated as long as the Fire Suppression bottle is full. If the Fire Suppression bottle drops in
pressure from either a discharge or leak, the LED will turn off, and the horn will sound.
DU-RBH-01
DU-RCH-01

4
Part Number 18146, D, 08/01/2018
DU-RBH-01
DU-RCH-01
YELLOW –Pressure Switch Input
Fireboy Fire
Extinguisher
Pressure Switch
RED –Power (+)
BLACK –Ground (-)
Ground
1.0 Amp Fuse

5
Part Number 18146, D, 08/01/2018
Installation
Installing the Display Unit (DU-RBH-01/DU-RCH-01)
The Deluxe Discharge Alarm should be located at the instrument panel, so that the visible and
audible indicators may be easily seen and heard.
Drill a 2-1/16” hole to accommodate the DU-RBH-01/DU-RCH-01.
Insert Display Unit into hole and secure with the provided threaded mounting nut.
Electrical Connections (DU-RBH-01/DU-RCH-01)
The Deluxe Discharge Alarm operates on 9-30 VDC. A Red and a Black 16 GA wire are provided for
connecting to the power source. Connect the Red wire to Power (+) with an inline 1.0 Amp fuse.
Connect the Black wire to Ground (-).
A Yellow 16 GA wire is provided for connecting the Deluxe Discharge Alarm to a Fireboy Pre-
Engineered Fire Extinguisher. Connect the Yellow wire to one of the terminals of the Pressure
Switch located on the Fire Extinguisher. The second terminal of the Pressure Switch is connected
to Ground.
Testing the DU-RBH-01/DU-RCH-01
The DU-RBH-01/DU-RCH-01 can be tested by disconnecting either wire connection at the Pressure
Switch. When the wire is disconnected, the LED will turn off and the alarm horn will sound.
Maintenance
The system should be tested periodically in the fashion described in the previous sections

6
Part Number 18146, D, 08/01/2018
In the Event of an Alarm
1. Immediately shutdown all engines, powered ventilation, and electrical systems.
2. Extinguish all smoking materials.
3. DO NOT open the engine compartment.
4. Before inspecting for damage, allow the agent to “soak” the compartment for at least
15 minutes and wait for hot metals or fuels to cool.
5. Have approved portable extinguishers in hand and ready for use.
6. Do not breathe fumes or vapors caused by the fire and/or suppression agent. They are
hazardous and toxic. Refer to Health and Safety section of the Extinguisher Manual.
7. Forced ventilation will often be necessary. Care should be taken to readily dissipate
hazardous atmospheres and not merely move them to another location. Consideration
should be given to exhaust paths when opening or venting the enclosure after
discharge. Ventilation should not be directed near any area that might be used as a
gathering spot for personnel.
Repairing Fireboy Deluxe Discharge Alarm(s)
Fireboy Deluxe Discharge Alarms are not field serviceable. Components must be returned to the
factory for any repairs.
Returning Fireboy Deluxe Discharge Alarm(s)
No product may be returned for credit or repair without a written “Returned Material
Authorization” (RMA) form. Purchaser must call or email Fireboy-Xintex 616-735-9380 or
returned, after approval it must be received in 100% new/resalable condition. Products stored by
the buyer for more than 26 weeks may not be returned for any reason. Maintaining fresh and
current inventory is the responsibility of the buyer.

7
Part Number 18146, D, 08/01/2018
1 Year Limited Warranty
This Warranty is in lieu of all other expressed or implied Warranties
Seller warrants title, materials, and workmanship on equipment, except components
manufactured by others for which the Seller assigns, as permitted, the original manufacturer’s
warranty. Seller’s warranty shall be for a period of (1) one year from the date of sale to the
ORIGINAL CONSUMER PURCHASER, during which non-conforming equipment returned to the
Seller at Buyer’s expense and risk, be repaired or replaced at the Seller’s option. Fireboy-Xintex
LLC will repair or replace products found to be defective in materials or workmanship within the
period set forth above, provided that: (a) the product has not been subjected to abuse,
contamination, neglect, accident, incorrect wiring not our own, improper installation or servicing,
or used in violation of instructions furnished by Fireboy-Xintex LLC and (b) as to any prior defects
in materials or workmanship covered by this warranty, the product has not been repaired or
altered by anyone except Fireboy-Xintex LLC and (c) the serial number has not been removed,
defaced or otherwise changed, and (d) examination discloses, in the judgment of Fireboy-Xintex
LLC, does not assume the costs of removal and/or installation of the product or any other
incidental costs of removal and/or installation of the product or any other incidental costs which
may arise as a result of any defect in material or workmanship, and (e) upon discovery of defect,
Buyer shall immediately cease use of and notify Fireboy-Xintex LLC.
Any warranty implied by law, including warranties of merchantability or fitness, is in effect only
for the duration of the expressed warranties set forth above, no person is authorized to give any
other warranty, or to assume for Fireboy-Xintex LLC any other liability in connection with the sale
of its products; Fireboy-Xintex LLC shall not be liable for the loss of use, revenue, or profit or for
any injury, or for any other consequential or incidental damages, buyer is not relying on seller’s
judgment regarding his or her particular requirements, and has had an opportunity to inspect the
product to his or her satisfaction.
This warranty gives you specific legal rights, and you may also have other rights, which vary, from
state to state.
www.fireboy-xintex.com
Fireboy-Xintex LLC
O-379 Lake Michigan Dr. NW
Grand Rapids, MI 49534
Phone (616) 735 9380
Fireboy-Xintex UK Operations Limited
10 Holton Road, Holton Heath Trading Park
Poole Dorset BH16 6LT UK
Phone 44 (0) 845 9462
This manual suits for next models
1
Table of contents
Other Fireboy- Xintex Security System manuals
Popular Security System manuals by other brands

Falcon
Falcon 7 inch Wireless Camera System manual

FBII
FBII LEGEND 7100 owner's manual

MOFLASH SIGNALLING
MOFLASH SIGNALLING X450 Series Installation and technical information

On Automation
On Automation FL1 instruction manual

Cooper
Cooper CFDAU30 Installation and maintenance manual

E2S
E2S BexCS11005D24DC-RD instruction manual