FireFlex TOTALPAC 3 Installation guide

FM-076A-0-1C
Advanced Integrated Fire Protection System
TOTALPAC®3
Owner's Operation
and
Maintenance Manual
NON INTERLOCK PREACTION SYSTEM
PNEUMATIC RELEASE

Page ii TOTALPAC®3
Integrated Fire Protection System
OWNER'S OPERATION &MAINTENANCE MANUAL
FM-076A-0-1C
Copyright © 2020 FIREFLEX Systems Inc.
All Rights Reserved
Reproduction or use, without express written permission from FIREFLEX Systems Inc, of any portion of this manual is prohibited.
While all reasonable efforts have been taken in the preparation of this manual to assure its accuracy, FIREFLEX Systems Inc
assumes no liability resulting from any errors or omissions in this manual, or from the use of the information contained herein.
TOTALPAC ®is a registered trademark of FIREFLEX Systems Inc.
FIREFLEX Systems Inc. reserves the right to make changes to this manual and the data sheets herewith at any time, without prior
notification.

TOTALPAC®3Page iii
Integrated Fire Protection System
OWNER'S OPERATION &MAINTENANCE MANUAL
FM-076A-0-1C
Table of Contents
Non Interlock Preaction System - Pneumatic Release
General Section ..........................................................................................................Section A
1- General description
2- Listings and approvals
3- Applicable standards
4- Environment
5- Features
6- Configuration description
7- System release
Mechanical Section...................................................................................................................... Section B
1- Installation, operation & maintenance instructions
1.1 Installation
1.2 Preliminary inspection before placing the system in service
1.3 Placing the system in service
1.4 System operation
1.5 Emergency instructions
1.6 Placing the system back in service after operation
1.7 Inspections & tests
1.8 Maintenance
2- System trim
2.1 Normal condition
Trim Options.................................................................................................................................Section C
1- Shut-off valve & sight glass
2- Fire department connection
3- Semi and full flanged option
4- Anti-column device option
5- OSHPD seismic option
Air Supply.....................................................................................................................................Section D
1- Cabinet air supplies
2- Operation
3- Maintenance and inspection
4- Air supply options
Control Section.............................................................................................................................Section E
1- Remotely controlled unit without release control panel
1.1 Product description
1.2 Technical data
Electrical Section..........................................................................................................................Section F
1- Remotely controlled configuration
Dimensional Data & Cabinet.......................................................................................................Section G
1- Cabinet unit
2- Skid mounted unit
Limited Warranty..........................................................................................................................Section H

Page iv TOTALPAC®3
Integrated Fire Protection System
OWNER'S OPERATION &MAINTENANCE MANUAL
FM-076A-0-1C
This page is left intentionally blank.

TOTALPAC®3Page 1 of 2
Integrated Fire Protection System
A
General Section - Non Interlock Preaction System - Pneumatic Release
FM-076A-0-21D
1- General description
This TOTALPAC®3integrated fire protection system by
FIREFLEX Systems Inc. consists of a preaction system trim
totally pre-assembled, pre-wired and factory tested. All
electrical and mechanical components of the system are
contained in one single unit.
Note:Skid units include the trim components only and must
be wired by the installing contractor.
The only connections required for installation are the water
supply inlet, the water discharge outlet, the main drain, the
pneumatic release inlet, the electrical supervisory and
alarm connections, as well as the AC power line for the
optional air compressor. The discharge outlet is
connected to a fixed piping network of automatic
sprinklers, in parallel to the pneumatic release piping
network (pilot line). Water is the extinguishing agent.
On system piping network and pneumatic release piping
network, closed heat sensitive automatic sprinklers are
spaced and located in accordance with recognized
installation standards in order to detect a fire. Only those
sprinklers immediately over or near to fire operate,
minimizing water damage.
Non interlock preaction system with pneumatic release
uses closed automatic sprinklers on the system piping
network, which is supervised with air pressure. A
pneumatic release piping network is installed in parallel
with the system piping network and is designed to operate
before an automatic sprinkler fuses from the system piping
network. Pneumatic release system operates first and
gives a supervisory signal.
Non interlock preaction system is designed so the deluge
valve will open when either a loss of pressure from the
pneumatic release piping network or from the system
piping network occurs. When the deluge valve opens,
water will flow into the system piping network and out of
any open automatic sprinklers and other opening on the
system.
In the event of no operation of the pneumatic release, the
system will operate as a dry system. In the event of
damage to the system piping network or an automatic
sprinkler, the deluge valve will open. Water will flow from
any open automatic sprinklers and any other opening in
the system piping network.
Note: Every TOTALPAC ®3unit is identified with its unique
serial number. This number is located on an adhesive
label inside the main door panel and is used to maintain a
record in our computerized data base. Have this serial
number handy when calling for information on your unit
(format is TOT3#### or TOTS#### for skid units).
2- Listings and approvals
In addition to being fabricated under tight ISO-9001
manufacturing and quality control procedures, your
TOTALPAC ®3unit has also been tested and approved by
recognized laboratories.
Here is the list of Listings & Approvals it meets:
- Underwriters Laboratories Inc. (UL): Preaction
TOTALPAC ®3systems are UL Listed under "Special
System Water Control Valves - Assembled Units,
category # VKYL.EX4641" and "Assembled Units
Certified for Canada, Category # VKYL7.EX4641 (c-UL)".
- Factory Mutual Research <FM>: Preaction TOTALPAC®3
systems are FM Approved under the heading: "Automatic
Water Control Valves" when installed with specific
components.
- OSHPD pre-approval OSP-0341-10 (optional).
WARNING Any unauthorized modification or addition made
on-site to a factory built Listed unit will void this Listing.
Such modifications or additions may void the unit's
warranty as well. Consult your nearest FIREFLEX Systems
authorized distributor before proceeding with such
modifications or additions.
3- Applicable standards
The TOTALPAC ®3complies with the following standards:
- NFPA-13 Sprinkler Systems
- NFPA-15 Water Spray Fixed Systems
- NFPA-16 Foam-Water Sprinkler and Foam-Water Spray
Systems
- NFPA-72 Fire Alarm Systems
Before installation, the contractor installing the unit shall
also be familiar with the following documents and
standards:
- Applicable Local & State Building Codes
- Any additional requirements of the Local Authority Having
Jurisdiction
4- Environment
TOTALPAC®3unit shall be installed in a dry and clean
location. Verify that all equipment is properly heated and
protected to prevent freezing and physical damage. Refer
to section E CONTROL SECTION for environment data.
The unit and its components must be kept free of foreign
matter, freezing conditions, corrosive atmospheres,
contaminated water supplies, and any condition that could
impair its operation or damage the components.
The frequency of the inspections and maintenance will
vary depending on these environmental conditions as well
as the condition of the air supply to the system. The owner
is responsible for maintaining the fire protection system
and devices in proper operating condition. Refer to
section B MECHANICAL SECTION for maintenance
instructions.

Page 2 of 2 TOTALPAC ®3
A
Integrated Fire Protection System
General Section - Non Interlock Preaction System - Pneumatic Release
FM-076A-0-21D
5- Features
The TOTALPAC ®3 unit is superior to many other products
which are actually available on the fire protection market.
It is manufactured by FIREFLEX Systems Inc. which has
developed and introduced the concept of integrated fire
protection systems.
Main features are:
Trouble free design for safe and easy application
Available in 6 sizes from 1½" (40 mm) to 8" (200 mm)
diameter
Uses the Viking deluge valve
Skid version available
Compact, aesthetic and easy to move
User-friendly standardized owner's manual with every
unit
Unique serial number on every unit
Uses only c-UL-us Listed and FM Approved components
Designed in accordance with NFPA Standards
Trim is fully assembled and tested at the factory
All trims are galvanized steel, Listed and Approved for
250 PSI (1724 kPa) service maximum
Quick connections to water supply and drain on both
sides, and sprinkler riser on top of unit, all available with
grooved end or flanged fittings
No open drain cup inside unit
Sturdy 14 gauge steel cabinet or skid, painted fire red
with oven baked polyester powder on phosphate base
Textured rust proof finish
Neoprene gasket on all doors to eliminate vibrations
Separate unlocked access hatch to emergency manual
release
Key-alike locks on all cabinet doors
Manufactured under ISO-9001 quality control procedures
6- Configuration description
TOTALPAC ®3 preaction system is built around the Viking
trim using straight through deluge valve model F-1
(model F-2 is the Halar ® coated version for use in
corrosive environments).
The valve is rated up to a maximum of 250 PSI WWP
(1724 kPa) and is available in the following diameters:
1½" (40 mm) 3" (80 mm) 6" (150 mm)
2" (50 mm) 4" (100 mm) 8" (200 mm)
TOTALPAC ®3 preaction system is supplied with groove/
groove deluge valve. Unit with flange/flange deluge valve
is also available on request.
6.1 Non interlock preaction system
Both pneumatic release piping network and system piping
network are pressurized with air or nitrogen gas. The
preaction system uses the Viking deluge valve which
opens either by the releasing of the pneumatic release
piping network, the fusing of an automatic sprinkler in the
system piping network, or anytime the handle of the
emergency release valve is pulled.
If the pneumatic release piping network releases due to
fire, damage or malfunction, the deluge valve will open but
the water will be trapped inside the system piping network
until an automatic sprinkler fuses, flowing water.
If the pneumatic release piping network does not operate,
the preaction system will operate as a dry pipe system. If
the system piping network is broken or an automatic
sprinkler fuses, the deluge valve opens, flowing water.
7- System release
7.1 Pneumatic release
Preaction system with pneumatic release requires a
pneumatic release piping network equipped with
thermostatic (rate of rise) releases, and/or fixed
temperature releases, and/or pilot heads. Release trim for
the deluge valve requires a pneumatic actuator normally
held closed by the pressure maintained in the pneumatic
release piping network and the system piping network.
In fire condition, when the pneumatic release piping
network releases, or when an automatic sprinkler fuses on
the system piping network, the deluge valve opens. If
automatic sprinklers are still closed, water will be trapped
inside the system piping network until an automatic
sprinkler fuses. If any automatic sprinkler fuses, water will
flow from the preaction system through opened sprinklers.
Automatic sprinkler must open to allow water to flow from
the preaction system.

TOTALPAC ®3 Page 1 of 8
Integrated Fire Protection System B
Mechanical Section - Non Interlock Preaction System - Pneumatic Release
FM-076A-0-41C
1- Installation, operation & maintenance
instructions
Note: Numbers indicated between brackets refer to figure 1
DETAILED SYSTEM TRIM SCHEMATICS from this section and
section D AIR SUPPLY.
1.1 Installation
1. Conform to local municipal or other codes regarding
installations of fire protection systems.
2. Install the TOTALPAC ®3 unit and connect the system
according to instruction manual and technical data
supplied.
IMPORTANT ! The cabinet must be firmly anchored to the
floor using all four (4) anchoring holes (see section G
CABINET).
Note: The drain collector shall be connected to an open
drain. Do not restrict or reduce drain piping.
3. Install the system piping network and the pneumatic
release piping network (pilot line) in accordance with
applicable standards.
4. Connect all supervisory and alarm signals according to
electrical schematics (see section F ELECTRICAL).
5. If applicable, connect the AC power to the air
compressor on a separate breaker in the electric
distribution panel (see section F ELECTRICAL).
Notes:
AC power connections must be made by a qualified
installer according to national standards and equipment
specifications.
Do not apply AC power to the air compressor yet.
6. Perform preliminary inspection prior to put system in
service (see paragraph 1.2 of the current section).
7. Place the system in service (see paragraph 1.3 of the
current section).
8. Perform the annual inspection sequence (see
paragraph 1.8 of the current section).
9. If the system does not operate as it should, make the
necessary corrections according to manuals issued or
consult your distributor or FIREFLEX Systems Inc.
10. Make sure that building owner or a delegated
representative has received instructions regarding the
operation of the system.
WARNING ! TOTALPAC ®3 unit must be installed in an area
not subject to freezing temperatures or physical damage.
1.2 Preliminary inspection before placing the system in
service
1. Open door to mechanical section.
a) Main water supply valve (D1) must be CLOSED.
b) Priming valve (B1) must be CLOSED.
c) Air supply for system piping network and pneumatic
release piping network (pilot line) must be CLOSED
(see section D AIR SUPPLY).
d) Flow test valve (B6) and main drain valve (D3) must
be CLOSED.
e) Alarm test valve (B5) must be CLOSED.
f) Gauges (B11, B12, E3 and F4) should show 0 PSI
(0 kPa).
g) If applicable, the shut-off valve (D4) must be OPEN.
2. OPEN the manual emergency release valve (B10) and
make sure the deluge valve (A1) is tripped.
3. Using the built-in contractor's hydrostatic test ports (see
figure 1 of this section and section D AIR SUPPLY), fill
system piping network with water and maintain pressure
as per NFPA-13 requirements.
WARNING ! Do not subject the pressure gauges and
pressure transducer to hydrostatic pressure above 250 PSI
(1724 kPA). Close gauge valves before proceeding with
hydrostatic test.
4. Correct leaks if any before completing test.
5. Verify that main water supply valve (D1) is still CLOSED.
6. OPEN main drain valve (D3) to completely drain the
system piping network.
7. If applicable, apply AC power to the air compressor.
The air supply must be CLOSED (see section D AIR
SUPPLY).

Page 2 of 8 TOTALPAC ®3
B
Integrated Fire Protection System
Mechanical Section - Non Interlock Preaction System - Pneumatic Release
FM-076A-0-41C
1.3 Placing the system in service
1. Verify that the main water supply valve (D1) is CLOSED.
Verify that the system has been properly drained.
2. Verify that all automatic sprinklers are set and that
inspector's test valves and/or piping auxiliary drain
valves are CLOSED.
3. CLOSE main drain valve (D3). Verify that the manual
emergency release valve (B10) is CLOSED.
4. Air supply must be OPEN (see section D AIR SUPPLY).
5. Establish recommended supervisory pressure to the
system piping network (see paragraph 2.1 NORMAL
CONDITION of the current section and section D AIR
SUPPLY).
Note: On system provided with air pressure maintenance
device (air supply style "B"), verify that the APMD bypass
valve (E8) is CLOSED and that APMD input and output
valves (E6 and E7) are OPEN.
6. Establish recommended supervisory pressure to the
pneumatic release piping network (pilot line) (see
paragraph 2.1 NORMAL CONDITION of the current section
and section D AIR SUPPLY).
7. OPEN priming valve (B1). Verify that the pressure
indicated at the priming pressure gauge (B11) is equal
to, or greater than the pressure indicated at the water
supply pressure gauge (B12).
8. OPEN flow test valve (B6). PARTIALLY OPEN main water
supply valve (D1).
9. When full flow develops from the flow test valve (B6),
CLOSE the flow test valve. Verify there is no flow from
drip check valve (B7) when the plunger is pushed.
10. FULLY OPEN the main water supply valve (D1).
11. Verify that the alarm test valve (B5) is CLOSED and that
all other valves are in their "normal" operating position
(see paragraph 2.1 NORMAL CONDITION of the current
section).
12. Check and repair all leaks.
13. On new installation, system that has been placed out of
service, or where new equipment has been installed,
trip test the system to verify that all equipment functions
properly (see paragraph 1.7.3 FULL FLOW TRIP TEST of
the current section).
14. Notify the AUTHORITY HAVING JURISDICTION, remote
station alarm monitors, and those in the affected area
that the system is in service.
Note: When a valve has been removed from service and is
subject to freezing or will be out of service for an extended
period of time, all water must be removed from the priming
chamber, trim piping, water supply piping and any other
trapped areas.
1.4 System Operation
1.4.1 In the SET condition
System water supply pressure enters the priming chamber
of the deluge valve (A1) through the priming line which
includes a normally open priming valve (B1), strainer (B2),
restricted orifice (B3) and spring loaded check valve (B4).
Water supply pressure is trapped in the priming chamber
of the deluge valve (A1) by spring loaded check valve (B4),
pneumatic actuator (F3), PORV (B9) (pressure operated
relief valve) and manual emergency release valve (B10).
The pressure in the priming chamber holds the deluge
valve clapper closed, keeping the outlet chamber and
system piping dry.
1.4.2 In a fire condition
When a releasing device operates from the pneumatic
release piping network (pilot line), or when an automatic
sprinkler fuses on the system piping network, the low air
supervisory switch (E4) activates and pneumatic
actuator (F3) opens.
Pressure from the priming chamber of the deluge
valve (A1) is released to the open drain manifold faster
than it is supplied through the restricted orifice (B3). The
deluge valve clapper opens to allow water to flow into the
piping network and alarm devices, causing water flow
alarms connected to the alarm pressure switch (C1) and
the optional water motor alarm (C2) to activate. When an
automatic sprinkler fuses, water will flow from the system
piping network.
When the deluge valve (A1) opens, the sensing end of the
PORV (B9) is pressurized, causing it to open. It then
continually vent the priming chamber, preventing the
closure of the deluge valve. The deluge valve can only be
reset after the system is taken out of service.
Note: If the pressure from the pneumatic release piping
network (pilot line) is lost due to mechanical damage or
malfunction of a release device, the deluge valve (A1) will
open but the water will be trapped in the system piping
network. Alarm devices (C1 and optional C2) will operate.
1.4.3 Manual operation
Anytime the handle of the manual emergency release
valve (B10) is triggered, pressure is released from the
priming chamber of the deluge valve (A1) causing deluge
valve to open. Water will flow into the system piping
network and alarm devices (C1 and optional C2) will
operate. The PORV (B9) keeps the deluge valve open.
When an automatic sprinkler fuses, water will flow from the
system piping network.
1.4.4 Supervisory condition
If an automatic sprinkler opens prior the operation of a
pneumatic release device or any time the supervisory
pressure is lost in the system piping network, the low air
pressure switch (E4) will signal a low air pressure
condition. Pressure is then released from the priming
chamber of the deluge valve (A1) causing deluge valve to
open. Alarm devices (C1 and optional C2) will operate.
Water will flow through the system piping network.

TOTALPAC ®3 Page 3 of 8
Integrated Fire Protection System B
Mechanical Section - Non Interlock Preaction System - Pneumatic Release
FM-076A-0-41C
1.5 Emergency instructions
To take system out of service
WARNING ! Placing a control valve or detection system out
of service may eliminate the fire protection capabilities of
the system. Prior to proceeding, notify all local
AUTHORITIES HAVING JURISDICTION. Consideration should
be given to employ a fire patrol in the affected areas.
After a fire, verify that the fire is OUT and that placing the
system out of service has been authorized by the
appropriate local AUTHORITY HAVING JURISDICTION.
Sprinklers piping that have been subjected to a fire must
be returned to service as soon as possible. The entire
system must be inspected for damage, and repaired or
replaced as necessary.
1. CLOSE main water supply valve (D1).
Note: Electric alarms controlled by a pressure switch
installed at the ¾"-NPT (20mm) connection (C2) for a non-
interruptible alarm signal cannot be shut-off until the
deluge valve (A1) is reset or taken out of service.
2. Air supply must be CLOSED (see section D AIR SUPPLY).
3. OPEN main drain valve (D3).
4. OPEN flow test valve (B6).
5. CLOSE priming valve (B1).
6. Replace any automatic sprinkler that have opened,
been damaged or exposed to fire conditions.
7. Return the system to service as soon as possible (see
paragraph 1.6 PLACING THE SYSTEM BACK IN SERVICE
AFTER OPERATION of the current section).
8. Perform all recommended maintenance procedures
(see paragraph 1.8 MAINTENANCE in the current section).
Note: When a system has been removed from service and
is subject to freezing or will be out of service for an
extended period of time, all water must be removed from
the priming chamber, trim piping, water supply piping and
any other trapped areas.
1.6 Placing the system back in service after operation
1. Verify that the system has been properly drained. Verify
that all automatic sprinklers are set and/or inspector's
test valve and system piping auxiliary drain valves are
CLOSED.
2. Verify that the main water supply valve (D1) is CLOSED,
and that the manual emergency release valve (B10) is
CLOSED. CLOSE main drain valve (D3).
3. Air supply must be OPEN (see section D AIR SUPPLY).
4. Restore supervisory pressure to the system piping
network (see section D AIR SUPPLY).
Note: On system provided with air pressure maintenance
device (air supply style "B"), verify that the APMD bypass
valve (E8) is CLOSED and that APMD input and output
valves (E6 and E7) are OPEN.
5. Restore supervisory pressure to the pneumatic release
piping network (pilot line) (see section D AIR SUPPLY).
6. OPEN priming valve (B1). Verify that the pressure
indicated at the priming pressure gauge (B11) is equal
to, or greater than the pressure indicated at the water
supply pressure gauge (B12).
7. OPEN flow test valve (B6). PARTIALLY OPEN main water
supply valve (D1).
Note: Do not open main water supply valve (D1) until
gauge (B11) shows stabilized pressure.
8. When full flow develops from the flow test valve (B6),
CLOSE the flow test valve. Verify there is no flow from
drip check valve (B7) when the plunger is pushed.
9. FULLY OPEN the main water supply valve (D1).
10. Verify that the alarm test valve (B5) is CLOSED and that
all other valves are in their "normal" operating position
(see paragraph 2.1 NORMAL CONDITION of the current
section).
11. Check and repair all leaks.
12. Notify the local AUTHORITY HAVING JURISDICTION, remote
station alarm monitors, and those in the affected area
that the system is back in service.

Page 4 of 8TOTALPAC®3
B
Integrated Fire Protection System
Mechanical Section - Non Interlock Preaction System - Pneumatic Release
FM-076A-0-41C
1.7 Inspections and tests
NOTICE:The owner is responsible for maintaining the fire
protection system and devices in proper operating
condition.
It is imperative that the system be inspected and tested on
a regular basis in accordance with NFPA-25. Refer to
Inspections and Tests recommended in Viking technical
data describing individual components of the preaction
system used.
The frequency of the inspections may vary due to
contaminated or corrosive water supply, corrosive
atmospheres, as well as the condition of the air supply to
the system. For minimum maintenance and inspection
requirements, refer to NFPA-25. In addition, the
AUTHORITY HAVING JURISDICTION may have additional
maintenance, testing, and inspection requirements that
must be followed.
WARNING ! Any system maintenance that involves placing
a control valve or detection system out of service may
eliminate the fire protection capabilities of that system.
Prior to proceeding any testing, notify all local AUTHORITIES
HAVING JURISDICTION. Consideration should be given to
employment of a fire patrol in the affected areas.
1.7.1System piping network low air supervisory test
1. To prevent operation of the deluge valve (A1) and filling
of the piping network with water during the test, CLOSE
main water supply valve (D1) and OPEN flow test
valve (B6).
2. If applicable, verify that the shut-off valve (D4) is OPEN.
3. FULLY OPEN the inspector's test valve on the system
piping network, or the main drain valve (D3).
4. Verify that low air supervisory signal operate within
acceptable time period and continue without
interruption.
5. CLOSE the inspector's test valve, or the main drain
valve (D3).
6. CLOSE priming valve (B1).
7. Establish recommended supervisory pressure to the
system piping network (see section D AIR SUPPLY).
8. OPEN priming valve (B1). Verify that the pressure
indicated at the priming pressure gauge (B11) is equal
to, or greater than the pressure indicated at the water
supply pressure gauge (B12).
9. PARTIALLY OPEN main water supply valve (D1).
10. When full flow develops from the flow test valve (B6),
CLOSE the flow test valve. Verify there is no flow from
drip check valve (B7) when the plunger is pushed.
11. FULLY OPEN the main water supply valve (D1).
1.7.2Pneumatic release piping network (pilot line) low
air supervisory test
1. To prevent operation of the deluge valve (A1) and filling
of the piping network with water during the test, CLOSE
main water supply valve (D1) and OPEN flow test
valve (B6).
2. FULLY OPEN the inspector's test valve on the piping
network being tested.
3. Verify that low air alarm signal operate within acceptable
time period and continue without interruption.
4. CLOSE the inspector's test valve.
5. CLOSE priming valve (B1).
6. Establish recommended supervisory pressure to the
system piping network (see section D AIR SUPPLY).
7. OPEN priming valve (B1). Verify that the pressure
indicated at the priming pressure gauge (B11) is equal
to, or greater than the pressure indicated at the water
supply pressure gauge (B12).
8. PARTIALLY OPEN main water supply valve (D1).
9. When full flow develops from the flow test valve (B6),
CLOSE the flow test valve. Verify there is no flow from
drip check valve (B7) when the plunger is pushed.
10. FULLY OPEN the main water supply valve (D1).
1.7.3Full flow trip test
Performance of a full flow trip test is recommended
annually during warm weather. Consider coordinating this
test with operation testing of the releasing devices.
Caution ! Performance of this test will cause the deluge
valve (A1) to open and the system piping network to be
filled with water.If it is not required to fill the system piping
network with water, use the shut-off valve (if applicable)
(see paragraph 1.7.5 OPERATION OF THE SHUT-OFF VALVE of
the current section).
To trip test the pneumatic release system
1. Trip the deluge valve (A1) by performing the following
paragraph “a” or “b”.
a) Open the inspector's test valve from the pneumatic
release piping network (pilot line) or activate a
pneumatic release device according to the
manufacturer's instructions.
b) Open the door of the manual emergency release
valve (B10) and trigger the handle.
2. The deluge valve (A1) should open. Alarm devices (C1
and optional C2) should operate. The piping network
will be filled with water.
3. OPEN the inspector's test valve from the system piping
network to verify adequate flow.

TOTALPAC®3Page 5 of 8
Integrated Fire Protection System
B
Mechanical Section - Non Interlock Preaction System - Pneumatic Release
FM-076A-0-41C
When trip testing is complete
1. Perform steps 1 through 5 of paragraph 1.5 EMERGENCY
INSTRUCTIONS to take the system out of service.
2. Perform steps of paragraph 1.6 PLACING THE SYSTEM
BACK IN SERVICE AFTER OPERATION.
1.7.4Main drain test
A main drain test shall be conducted to determine whether
there has been a change in the condition of the water
supply piping and control valves.
Test procedure
1. Record the pressure indicated by the water supply
gauge (B12).
2. If applicable, CLOSE the alarm control valve.
3. FULLY OPEN the flow test valve (B6).
4. Record residual pressure.
5. CLOSE the flow test valve (B6) slowly.
6. Record the time taken for supply water pressure to
return to the original pressure.
Note: A main drain test shall be conducted any time the
main water supply valve (D1) is closed and reopened at
the system.
1.7.5Operation of the optional shut-off valve
Inspection of the system can be implemented without filling
the system piping network with water. The use of shut-off
valve (D4) and sight glass assembly (D5) allows to verify
the operation of the system and prevents water from
reaching the piping network.
1. CLOSE the shut-off valve (D4) to isolate the system
piping network.
2. Execute the full flow trip test (see paragraph 1.7.3 of the
current section). The deluge valve (A1) should open.
3. Using a flashlight in one of the sight glasses, verify that
water flows through the sight glass assembly (D5).
When trip testing is complete
1. Perform steps 1 through 5 of paragraph 1.5 EMERGENCY
INSTRUCTIONS to take the system out of service.
2. Perform steps of paragraph 1.6 PLACING THE SYSTEM
BACK IN SERVICE AFTER OPERATION.
1.8 Maintenance
NOTICE:The owner is responsible for maintaining the fire
protection system and devices in proper operating
condition.
The system shall be maintained in full operation condition
at all times.
All troubles or impairments shall be corrected promptly
consistent with the hazard being protected.
Refer to MAINTENANCE INSTRUCTIONS provided in Viking
Technical Data describing individual components of the
system used.
The air supply shall be maintained in full operating
condition at all times (refer to section D AIR SUPPLY).
The following requirements are based upon NFPA-25.
Records
Records of inspections, tests and maintenance of the
system and its components shall be made available to the
AUTHORITY HAVING JURISDICTION upon request. Typical
records include, but are not limited to: valves inspection;
flow, drain, and pump tests, and trip test of the deluge
valves.
Acceptance test records should be retained for the life of
the system or its special components. Subsequent test
records should be retained for a period of one (1) year
after the next test. The comparison determines
deterioration of system performance or condition and the
need for further testing or maintenance.
1.8.1 Monthly
1. Inspection of gauges (water supply (B12) and priming
chamber (B11) pressure) to ensure good condition and
normal water supply pressure.
2. Control valve shall be externally inspected. The valve
inspection shall verify the following:
a) The gauges indicate that normal supply water
pressure is being maintained.
b) The valve is free of physical damage.
c) All valves are in the appropriate open or closed
position (see paragraph 2.1 of the current section).
d) There is no leakage from the alarm drains.
1.8.2 Quarterly
1. Check alarm pressure switch (C1)and optional water
motor gong (C2)by opening the alarm test valve (B5).
2. Conduct system piping network low air supervisory test
(see paragraph 1.7.1 of the current section).
3. Conduct pneumatic release piping network (pilot line)
low air alarm test (see paragraph 1.7.2 of the current
section).

Page 6 of 8TOTALPAC®3
B
Integrated Fire Protection System
Mechanical Section - Non Interlock Preaction System - Pneumatic Release
FM-076A-0-41C
1.8.3 Semi-annually
1. Main water supply valve (D1) switch shall be operated
to verify the switch actuation upon movement of the
hand wheel.
2. Check alarm pressure switch (C1)and optional water
motor gong (C2)by opening the alarm test valve (B5).
3. Perform functional test of all components of the system.
1.8.4 Annually
1. Perform full flow trip test (see paragraph 1.7.3 of the
current section).
2. Record indicating the date of the last trip, tripping time
and name of the organization conducting the test shall
be maintained at a location available for review by the
AUTHORITY HAVING JURISDICTION.
3. Perform main drain test (see paragraph 1.7.4 of the
current section).
1.8.5 Every 5 years
1. Test on gauge (gauge precision required: less than 3%
of the full scale).
2. Perform test on control valve operation.
3. Deluge valve (A1) and their associated strainers, filters
and restriction orifices shall be inspected internally.
4. Perform main drain test (see paragraph 1.7.4 of the
current section).
2- Non interlock preaction system with
pneumatic release
Note: Numbers indicated between brackets refer to figure 1
DETAILED SYSTEM TRIM SCHEMATICS from this section and
section D AIR SUPPLY.
2.1 Normal condition
1. Valves
a) Main water supply valve (D1) is OPEN.
b) All upstream water supply valves are OPEN.
c) Priming valve (B1) is OPEN.
d) Flow test valve (B6) is CLOSED.
e) Main drain valve (D3) is CLOSED.
f) Alarm test valve (B5) is CLOSED.
g) Manual emergency release valve (B10) is CLOSED
(handle in vertical position).
h) Air supply is OPEN (see section D AIR SUPPLY).
i) All gauge valves are OPEN.
j) Shut-off valve (D4) is OPEN (if applicable).
3. Gauges
a) Water supply pressure (B12) shall not exceed
175 PSI (1207 kPa) or 250 PSI (1724 kPa).
b) Priming chamber pressure (B11) should be equal to,
or higher than, water supply pressure (B12).
c) System piping network (E3 and F4) shall be at 35 PSI
(242 kPa) or 55 PSI (380 kPa) (see section D AIR
SUPPLY).
d) Pneumatic release piping network (pilot line) (E13)
shall be 35 PSI (242 kPa) or 55 PSI (380 kPa) (see
section D AIR SUPPLY).
4. Pressure switches & settings (factory set)
a) Alarm pressure switch (C1) should activate when
pressurized higher than 5 PSI (34 kPa).
b) Low air pressure switch (E4) should activate when
pressurized lower than 25 PSI (173 kPa) or 45 PSI
(311 kPa) (see section D AIR SUPPLY).
c) Pilot line low air pressure switch (E14) should activate
when pressurized lower than 25 PSI (173 kPa) or
45 PSI (311 kPa) (see section D AIR SUPPLY).

TOTALPAC ®3 Page 7 of 8
Integrated Fire Protection System B
Mechanical Section - Non Interlock Preaction System - Pneumatic Release
FM-076A-0-41C
Figure 1 - Detailed system trim schematic
Typical non interlock preaction system with pneumatic release (3" (80 mm) system shown)
D1
A1
D3
B13
To Air Supply
System Trim
FIELD CONNECTION
TO WATER SUPPLY
(on both sides)
TO RELEASE SYSTEM TRIM
AND OPTIONAL ACCELERATOR
(when used)
B11
B5
1
F4
F5
B3
FIELD CONNECTION
TO OPEN DRAIN
(on both sides)
C1
B6
CONTRACTOR'S
HYDROSTATIC TEST PORT
(water supply side)
B1
FIELD CONNECTION TO
SPRINKLER PIPING NETWORK
B4
B8
B10
F3
To Air Supply System Trim
E4
D2
C2
B12
B7
2
B9
B2
TOTALPAC 3 Base
(shown without enclosure) FM-061H-0-102C
Trim components
A1 Deluge valve
B1 Priming valve (N.O.)
B2 Strainer
B3 1/16" (1.6 mm) Restricted orifice
B4 Spring loaded check valve
B5 Alarm test valve (N.C.)
B6 Flow test valve (N.C.)
B7 Drip check valve (N.O.)
B8 Drain check valve
B9 PORV (pressure operated relief valve)
B10 Manual emergency release valve (N.C.) (shown in
closed position)
B11 Priming pressure water gauge & valve (N.O.)
B12 Water supply pressure gauge & valve (N.O.)
B13 Clapper check valve
C1 Alarm pressure switch (PS10-1)
C2 ¾"-NPT (20 mm) connection to optional water motor
gong (strainer to be supplied by contractor)
D1 Main water supply valve (N.O.)
D2 Riser check valve
D3 Main drain valve (N.C.)
E4 Air pressure supervisory switch (PS40-1)
F3 Pneumatic actuator
F4 Pneumatic actuator pressure gauge & valve (N.O.)
F5 Float check assembly

Page 8 of 8TOTALPAC®3
B
Integrated Fire Protection System
Mechanical Section - Non Interlock Preaction System - Pneumatic Release
FM-076A-0-41C
This page is left intentionally blank.

TOTALPAC®3Page 1 of 2
Integrated Fire Protection System
C
Trim Options
FM-076A-0-81C
Preaction trim options
1. Shut-off valve & sight glass
The shut-off valve & sight glass option is intended to be
used for applications where testing of the system operation
without filling the sprinkler piping network is desirable and
where it is critical that all functions of the preaction system
be tested under actual discharge conditions. Examples of
such applications are freezers, ovens, museums, data
processing and other hazards where the possibility of
water leaking from the piping system is to be avoided at all
costs.
Operation of the shut-off valve
Inspection of the system can be implemented without filling
the sprinkler piping network with water.
1. CLOSE the sprinkler piping network shut-off valve (D4);
the valve is supervised on the same circuit as the main
water supply valve (D1).
2. OPEN the main drain valve (D3).
3. Simulate the operation of the system to open the deluge
valve (A1); see annual test under section B
INSPECTION AND MAINTENANCE. Using a flashlight in the
sight glasses, verify that water flows through the sight
glass assembly (D5).
4. Once tests are completed, make sure the main drain
valve (D3) is completely CLOSED. Return the system in
service as per section B PLACING THE SYSTEM BACK IN
SERVICE.
5. Fully OPEN the shut-off valve (D4). Reset the release
control panel as per section E CONTROL BUTTONS.
Warning : Shut off valve (D4) is not available on 8"
(200 mm) system.
Figure 1 – Shut-off valve & sight glass
(figure is shown without cabinet for clarity)
FM-061H-0-75C
Sight glass
assembly (D5)
Point flash
light here
Main drain
valve (D3) Supervised
shut-off valve (D4)
Supervised
main water
supply valve (D1)
2. Fire department connection
The fire department connection option consists of a
grooved tee fitting installed at the outlet of the deluge
valve (A1). An access hole of the proper diameter is
factory pre-drilled on the right side of the TOTALPAC®3
enclosure for connection going to the fire department
connection.
Note : The fire department connection hardware itself
(drain, Siamese, etc.) is not provided with this option and
shall be provided by the installing contractor. Refer to
NFPA-13 Standards for additional information about the
equipment layout and installation.
Warning : The fire department connection is not available
on 6" (150 mm) and 8" (200 mm) systems.
Figure 2 – Fire department connection
(figure is shown without cabinet for clarity)
Grooved tee fitting
with coupling & cap
Towards fire department
connection (hardware by
contractor)
FM-061H-0-76C

Page 2 of 2TOTALPAC®3
C
Integrated Fire Protection System
Trim Options
FM-076A-0-81C
3. Semi and full-flanged option
When required by the user, TOTALPAC®3unit can be
provided in either a semi-flanged of full flanged
configuration.
The semi flanged option provides flanged fittings only on
the water inlet pipe (side needs to be specified at the time
of order) and on the system riser outlet. The drain
manifold is then provided with a threaded end that also
needs to have its side specified (left or right). The rest of
the fittings are the same as usual with the main
components being provided in the standard flanged/
grooved configuration.
The full flanged option is the same as above but goes a
step further with the main components being also provided
with a flanged-flanged configuration.
When provided, the face of the flanges will always be
located 6 inches from the outside face of the mounting
base or cabinet surface. On skid unit, the surface of the
flange on the outlet riser will always be 6 inches above the
dimension shown on the dimensional data of the system
ordered.
Figure 3 – Semi-flanged unit typical detail
(figure is shown without cabinet for clarity)
Flanged fitting outside cabinet
(when provided)
Field connection
to water supply
(specify side)
Field connection
to open drain
(specify side)
FM-061H-0-77C
Flanged fitting outside cabinet
(when provided)
Threaded end
4. Anti-column device option
The model LD-1 anti-column device is an optional trim
component designed for use with preaction sprinkler
system. The anti-column device automatically prevents an
unwanted water column from establishing within the
system riser. On preaction sprinkler systems, the anti-
column device prevents water from columning downstream
of the easy riser check valve.
Figure 4 – Anti column device detail
From sprinkler riser
To drain collector
FM-061H-0-146A
5. OSHPD seismic option
Pre-approved construction, under OSP-0341-10, using
specific requirements.

TOTALPAC ®3 Page 1 of 12
Integrated Fire Protection System D
Air Supply - Preaction System
FM-076A-0-86C
1. Cabinet Air Supplies
Preaction sprinkler system using air pressure for
supervisory or releasing purposes is provided with either
internal or external supervised air supply.
WARNING Pressures other than the factory pressure
settings may affect the operation of the system.
Four (4) styles of air supplies are available for the
TOTALPAC ®3 units depending on needs or configurations.
These air supplies are all factory assembled, mounted in
the cabinet and pressure tested. Following is the
description of those options.
1.1 Air supply Style "A" (refer to figure 2)
Used only for the sprinkler piping network of preaction
systems. Air supply style "A" includes the air compressor
mounted inside the TOTALPAC ®3 cabinet with its
supervisory trim and options. Air compressor is of the
oilless piston type without reservoir and is factory piped to
the sprinkler piping system riser, all within the TOTALPAC ®3
cabinet.
A factory wired isolation switch (see figure 2 in section E
CONTROLS SECTION) is also provided in the TOTALPAC®3
cabinet, allowing powering off the air compressor while
some maintenance work on the unit is done, without
disturbing the rest of the system.
To connect non-energized AC power to the air
compressor, refer to field wiring diagram (see section F
ELECTRICAL SECTION).
Table 1 - Air compressor F.L.A. (full load amp) rating
Air compressor
size
115Vac
60Hz
208Vac
60Hz
230Vac
60Hz
1/6 HP 5.0 Amp 2.3 Amp 2.5 Amp
1/3 HP 7.4 Amp 3.5 Amp 3.7 Amp
1/2 HP 10.0 Amp 4.9 Amp 5.0 Amp
1 HP 18.0 Amp 7.7 Amp 9.0 Amp
1.5 HP 16.6 Amp 8.2 Amp 8.3 Amp
2 HP n/a 11.6 Amp 11.0 Amp
Air compressor
size
220Vac
50Hz
240Vac
50Hz
0.12 KW 1.3 Amp 1.3 Amp
0.25 KW 2.5 Amp 2.6 Amp
0.56 KW 4.0 Amp 4.5 Amp
1.2 KW 6.0 Amp 6.0 Amp
1.5 KW 6.3 Amp 6.0 Amp
Note : Selection of the appropriate wire size is the
responsibility of the installing contractor.
1.2 Air supply Style "B" (refer to figure 3)
Used only for the sprinkler piping network of preaction
system, when an external air supply is provided by others
(either a compressor, plant air or dry nitrogen cylinders)
and piped to the air inlet port of the unit.
Air supply style "B" provides an APMD (air pressure
maintenance device) trim, factory mounted in the
TOTALPAC ®3 cabinet. The APMD regulates and restricts
the inlet pressure. It allows an outlet pressure range from
5 PSI to 75 PSI (34 kPa to 517 kPa) ±2 PSI (14 kPa). An
internal ball check valve prevents back flow.
Warning : When air supply style "B" is selected, the air
supply should be provided and installed by the sprinkler
contractor OUTSIDE of the TOTALPAC ®3 cabinet. Air
supply is NOT provided with the unit.
1.3 Air supply Style "C" (refer to figure 4)
Used only for the pilot line release. An external air supply
has to be provided by others (compressor, plant air or dry
nitrogen cylinders) and piped to the air inlet port of the unit.
Air supply style "C" provides an APMD (air pressure
maintenance device) trim, factory mounted in the
TOTALPAC ®3 cabinet. The APMD regulates and restricts
the inlet pressure. It allows an outlet pressure range from
5 PSI to 75 PSI (34 kPa to 517 kPa) ±2 PSI (14 kPa). An
internal ball check valve prevents back flow.
Warning : When air supply style "C" is selected, the air
supply should be provided and installed by the sprinkler
contractor OUTSIDE of the TOTALPAC®3 cabinet. Air
supply is NOT provided with the unit.
1.4 Air supply Style "D" (refer to figure 5)
Mainly used with preaction system protecting refrigerated
spaces and freezers, where a special dry external air
supply unit is piped directly to the system riser inside the
freezer itself, as shown in NFPA-13. Air supply style "D"
provides only an air supervisory and shut-off trim.
Ambient temperature at the special external air supply unit
location should not exceed 104°F (40°C). Refer to NFPA
and Factory Mutual Codes & Standards for details on
refrigerated spaces applications. Air supply style "D" can
also be used when the contractor prefers to provide his
own air supply & regulation trim, mounted outside the
TOTALPAC ®3 cabinet.
Note : External air supply MUST always be restricted to
insure that the air supply cannot replace air as fast as it
escapes when an automatic sprinkler operates.
Warning : When air supply style "D" is selected, the air
supply should be provided and installed by the sprinkler
contractor OUTSIDE of the TOTALPAC ®3 cabinet. Air
supply is NOT provided with the unit.

Page 2 of 12 TOTALPAC ®3
D
Integrated Fire Protection System
Air Supply - Preaction System
FM-076A-0-86C
2. Operation
2.1 Air supply Style "A" (refer to figure 2)
To apply air supply
Establish AC power for the air compressor by activating
the correspondent circuit breaker at the electrical
distribution panel. Start air compressor by activating the
compressor isolating switch (E15) located on the junction
box of the unit (see figure 2 in section E CONTROLS
SECTION).
If the air compressor motor fails to start or slows down
under load, shut the air compressor off. Check that the
supply voltage agrees with the motor nameplate.
To close air supply
Turn off the compressor isolating switch (E15) (see
figure 2 in section E CONTROLS SECTION).
To adjust air supply
The air compressor cut-off pressure switch (E2) is factory
set. This switch should not need any adjustment but if
necessary, follow the instructions below:
WARNING The adjustment screw of the cut-out/cut-in
differential pressure switch (E2) (small screw to the right)
is factory set. DO NOT CHANGE ITS SETTING. Any
unauthorized modification of this adjustment screw will
void the system warranty and may also prevent the system
from operating normally.
1. Remove the metal cover of the compressor air pressure
switch (E2).
2. To raise the cut-out pressure of the air compressor, turn
the cut-out adjustment screw (middle) half a turn
CLOCKWISE. Use the same method turning the cut-
out adjustment screw COUNTER-CLOCKWISE to lower
the air compressor cut-out pressure.
Figure 1 - Air pressure adjustment
INCREASE PRESSURE
LINE MOTOR LINE
Turn clockwise to increase
both cut-out and cut-in
pressure adjustment
Factory set
DO NOT CHANGE !
FM-072Q-0-109B
Note : Do not turn the cut-out adjustment screw (middle) all
the way down in one shot. Proceed by steps.
3. OPEN the main drain valve (D3) and let the pressure
drop until the air compressor restarts. Check pressure
reading on the system pressure gauge when the air
compressor stops again. Repeat until the desired
pressure is reached. Once all done, replace the metal
cover on the switch (E2).
2.2 Air supply Style "B" or "C" (refer to figure 3 or 4)
To apply air supply
1. Turn on upstream air supply.
2. OPEN APMD (air pressure maintenance device) input
valve (E6) by placing handle in line with valve body.
3. OPEN APMD output valve (E7) by placing handle in line
with the valve body.
4. OPEN bypass valve (E8) by placing handle in line with
valve body in order to accelerate filling of sprinkler
piping network by air pressure, while piping is initially
filled.
5. Once the piping network pressure is reached, CLOSE the
bypass valve (E8) by placing handle crossways to valve
body, and kept in this position.
Note: The bypass valve (E8) must be kept closed once the
system is filled with air.
To close air supply
1. CLOSE APMD output valve (E7) by placing handle
crossways to valve body.
2. CLOSE APMD input valve (E6) by also placing handle
crossways to the valve body.
3. Be sure bypass valve (E8) is CLOSED (handle crossways
to valve body).
To adjust air supply
1. Verify that APMD input valve (E6) and APMD output
valve (E7) are both OPEN (handle in line with the valve
body).
2. Be sure that bypass valve (E8) is CLOSED (handle
crossways to valve body) prior to performing this
operation.
3. Loosen lock nut of the APMD (E5) and turn pressure
adjustment nut clockwise to increase air pressure or
counter-clockwise to decrease pressure.
4. Tighten lock nut.
Note: Depending on site conditions, the internal filter of the
APMD may need maintenance on a regular basis. Refer to
Viking data sheet #127 for more details.
2.3 Air supply Style "D" (refer to figure 5)
To apply air supply
1. Turn on upstream air supply.
2. OPEN air shut-off valve (E6).
To close air supply
1. CLOSE bypass air shut-off valve (E6).

TOTALPAC ®3 Page 3 of 12
Integrated Fire Protection System D
Air Supply - Preaction System
FM-076A-0-86C
3. Maintenance and inspection
Important : Advise local authorities of the necessary work
over the fire protection equipment. In order to avoid
accidental water release, it is considered good practice to
completely close the main water supply valve (D1) while
doing maintenance work.
3.1 Air supply Style "A" (refer to figure 2)
The Style “A” air accumulator should be drained once a
year. The amount of moisture pumped into the system
and how quickly it accumulates is proportional to the
amount of humidity in the air and how long the compressor
is in operation.
To drain the air supply accumulator
At least once a year, OPEN air option drain valve (E12) until
all condensate water is drained from the air receiver.
CLOSE air option drain valve.
Safety valve pressure
A safety relief valve is provided on standard compressor
and is preset at the factory. Do not adjust or exceed
safety relief pressure other than those preset at the
factory.
WARNING The relief valve and outlet pipe of the air
compressor may become very hot during normal
operation. Do not touch the valve, compressor heads or
outlet piping until the compressor has been turned off and
allowed to cool.
WARNING Do not unscrew relief valve head entirely off
while the compressor is operating. Ejection of valve parts
could cause severe injury.
3.2 Air supply Style "B" or C" (refer to figure 3 or 4)
The Viking Model D-2 APMD (air pressure maintenance
device) (E5) is a pressure regulator that automatically
reduces the supply air pressure to a pre-set requirement
when connected to a constantly maintained air supply
(plant air, external tanked air compressor or dry nitrogen
tank).
Determine the appropriate pressure to be maintained in the
system. Refer to table 2 or table 3 of the current section.
If adjustment is necessary, refer to paragraph 2.2 of the
current section.
To clean APMD (air pressure maintenance device)
1. Turn off external air supply.
2. CLOSE APMD output valve (E7) by placing handle
crossways to valve body.
3. CLOSE APMD input valve (E6) by also placing handle
crossways to the valve body.
NOTE : Never disconnect or disassemble the APMD (E5)
without closing those isolation valves.
4. Carefully loosen the union between the outlet of
APMD (E5) and the outlet isolation valve (E7) to relieve
pressure.
5. Remove and clean air pressure maintenance device
APMD (E5) filter. If admission filter is blocked, replace
with filter kit (part #03007 A).
Refer to Viking data sheet #127 for additional details.
3.3 Air supply Style "D" (refer to figure 5)
The air or nitrogen supply provided must be continuous,
clean, dry and oil free.
Determine the appropriate pressure to be maintained in the
system. Refer to table 2 or table 3 of the current section.

Page 4 of 12 TOTALPAC ®3
D
Integrated Fire Protection System
Air Supply - Preaction System
FM-076A-0-86C
Table 2 - Water pressure up to 175 PSI (1207 kPa)
System type Air supply
Style
Air
regulator
Compressor
start
Compressor
stop
Low air
supervisory
Non interlock
Pneumatic release
A n/a 30 PSI
(207 kPa)
35 PSI
(241 kPa)
25 PSI
(172 kPa)
B or D 35 PSI
(241 kPa) n/a n/a 25 PSI
(172 kPa)
Single interlock
Pneumatic release
A n/a 30 PSI
(207 kPa)
35 PSI
(241 kPa)
25 PSI
(172 kPa)
B or D 35 PSI
(241 kPa) n/a n/a 25 PSI
(172 kPa)
Double interlock
Pneumatic/pneumatic
A n/a 30 PSI
(207 kPa)
35 PSI
(241 kPa)
25 PSI
(172 kPa)
B or D 35 PSI
(241 kPa) n/a n/a 25 PSI
(172 kPa)
Release (pilot) line C 35 PSI
(241 kPa) n/a n/a 25 PSI
(172 kPa)
Table 3 - Water pressure from 175 PSI to 250 PSI (1207 kPa to 1724 kPa)
System type Air Supply
Style Air Regulator Compressor
Start
Compressor
Stop
Low Air
Supervisory
Non interlock
Pneumatic release
A n/a 50 PSI
(345 kPa)
55 PSI
(379 kPa)
45 PSI
(310 kPa)
B or D 55 PSI
(379 kPa) n/a n/a 45 PSI
(311 kPa)
Single interlock
Pneumatic release
A n/a 50 PSI
(345 kPa)
55 PSI
(379 kPa)
45 PSI
(310 kPa)
B or D 55 PSI
(379 kPa) n/a n/a 45 PSI
(310 kPa)
Double interlock
Pneumatic/pneumatic
A n/a 50 PSI
(345 kPa)
55 PSI
(379 kPa)
45 PSI
(310 kPa)
B or D 55 PSI
(379 kPa) n/a n/a 45 PSI
(310 kPa)
Release (pilot) line C 55 PSI
(379 kPa) n/a n/a 45 PSI
(310 kPa)
This manual suits for next models
2
Table of contents
Popular Fire Alarm manuals by other brands

Potter
Potter PAD100-PSSA installation manual

Honeywell
Honeywell NOTIFIER NFS-320C manual

Panasonic
Panasonic Firetracker FT1020G3 CIE Technical and Programming Manual

Johnson Controls
Johnson Controls IFC-1010 Technical manual

Satel
Satel SPP-110 instructions

Teletek electronics
Teletek electronics SensoIRIS T110 IS quick guide