  9. Notifier NBG-12LX User manual

Notifier NBG-12LX User manual

DN-6726 • 06/13/05 — Page 1 of 2
GENERAL
The NOTIFIER NBG-12LX is a state-of-the-art, dual-ac-
tion (i.e., requires two motions to activate the station) pull
station that includes an addressable interface for any
NOTIFIER intelligent control panel. Because the NBG-12LX
is addressable, the control panel can display the exact
location of the activated manual station. This leads fire
personnel quickly to the location of the alarm.
FEATURES
• Maintenance personnel can open station without causing
an alarm condition.
• Built-in bicolor LED, which is visible through the handle of
thestation,flashesinnormaloperationandlatchessteady
red when in alarm.
• Handle latches in down position and the word “ACTI-
VATED” appears to clearly indicate the station has been
operated.
• Captive screw terminals wire-ready for easy connection
to SLC loop (accepts up to 12 AWG/3.1 mm² wire).
• Semi-flush, mounts to a standard single-gang (2.125"
[5.3975 cm] minimum depth), double-gang, or 4" (10.16
cm) square electrical box.
• Smooth dual-action design.
• Within ADA 5 lb. pull force.
• Highly visible.
• Attractive shape and textured finish.
• Key reset.
• Includes Braille text on station handle.
• Optional trim ring (BG-TR).
• Meets UL 38, Standard for Manually Actuated Signaling
Boxes.
• Up to 99 NBG-12LX stations per loop on classic protocol
systems.
• Up to 159 NBG-12LX stations per loop on FlashScan®
protocol systems.
• Dual-color LED blinks green to indicate normal on
FlashScan® systems.
CONSTRUCTION
Shell, door, and handle are molded of durable LEXAN®
(or polycarbonate equivalent) with a textured finish.
OPERATION
Pushing in, then pulling down on the handle causes it to
latch in the down/activated position. Once latched, the
word “ACTIVATED” (in bright yellow) appears at the top of
the handle, while a portion of the handle protrudes from
The NBG-12LX
Addressable Manual Pull Station
FlashScan® and NOTIFIER® are registered trademarks of Hon-
eywell International INC. LEXAN® is a registered trademark of
GE Plastics, a subsidiary of General Electric Company.
June 13, 2005
Section: Intelligent/Addressable Devices
NBGNBG
NBGNBG
NBG-12LX-12LX
-12LX-12LX
-12LX
Addressable Manual Pull StationAddressable Manual Pull Station
Addressable Manual Pull StationAddressable Manual Pull Station
Addressable Manual Pull Station
with FlashScan®with FlashScan®
with FlashScan®with FlashScan®
with FlashScan®
DN-6726 • H-240
the bottom of the station. To reset the station, simply un-
lock the station with the key and pull the door open. This
action resets the handle; closing the door automatically
resets the switch.
Each manual station, on command from the control panel,
sends data to the panel representing the state of the manual
switch. Two rotary decimal switches allow address set-
tings (1 – 159 on FlashScan® systems, 1 – 99 on CLIP
systems).
6643cov.jpg
S692
7150-0028:199
California
State Fire
Marshal MEA
67-02-E
Patented, U.S. Patent No. D428,351; 6,380,846
U.S. Patent Pending: 09/686,286
U.S. Coast Guard
161.002/23/3
(AFP-200)
93/60141 (E3)
02/6007
BSMI
CI313066760047
This document is not intended to be used for installation purposes. We try to keep our
product information up-to-date and accurate. We cannot cover all specific applications or
anticipate all requirements. All specifications are subject to change without notice.
For more information, contact NOTIFIER. Phone: (203) 484-7161 FAX: (203) 484-7118
12 Clintonville Road, Northford, Connecticut 06472
Page 2 of 2 — DN-6726 • 06/13/05
PRODUCT LINE INFORMATION
NBG-12LX Dual-action addressable pull station.
Includes key locking feature.
SB-10 Surface backbox.
SB-I/O Indoor/outdoor surface backbox.
BG-TR Optional trim ring.
INSTALLATION
The NBG-12LX will mount semi-flush into a single-gang,
double-gang, or standard 4" (10.16 cm) square electrical
outlet box, or will surface mount to the model SB-10 or
SB-I/O surface backbox. If the NBG-12LX is being semi-
flush mounted, then the optional trim ring (BG-TR) may be
used. The BG-TR is usually needed for semi-flush mount-
ing with 4" (10.16 cm) or double-gang boxes (not with
single-gang boxes).
ELECTRICAL SPECIFICATIONS
Normal operating voltage: 24 VDC.
Maximum SLC loop voltage: 28.0 VDC.
Maximum SLC loop current: 375 µA.
ARCHITECTURAL/
ENGINEERING SPECIFICATIONS
Manual Fire Alarm Stations shall be non-coded, with a
key-operated reset lock in order that they may be tested,
and so designed that after actual Emergency Operation,
they cannot be restored to normal except by use of a key.
An operated station shall automatically condition itself so
as to be visually detected as activated. Manual stations
shall be constructed of red-colored LEXAN® (or polycar-
bonate equivalent) with clearly visible operating instruc-
tions provided on the cover. The word FIRE shall appear
on the front of the stations in white letters, 1.00 inches
(2.54 cm) or larger. Stations shall be suitable for surface
mounting on matching backbox SB-10; or semi-flush mount-
ing on a standard single-gang, double-gang, or 4" (10.16
cm) square electrical box, and shall be installed within the
limits defined by the Americans with Disabilities Act (ADA)
or per national/local requirements. Manual Stations shall
be Underwriters Laboratories listed.
Manual stations shall connect with two wires to one of the
control panel SLC loops. The manual station shall, on com-
mand from the control panel, send data to the panel repre-
senting the state of the manual switch. Manual stations
shall provide address setting by use of rotary decimal
switches.
The loop poll LED shall be clearly visible through the front
of the station. The LED shall flash while in the normal
condition, and stay steadily illuminated when in alarm.
Back of station without door.
Cover open to show easy access to miniature
monitor module, rotary switch, and UL label.
6726back.wmf
6726open.wmf
6726rtsw.wmf
*Remove tab to select addresses
above 99 (FlashScan® systems only).
Terminal
Connections
1 SLC (–)
2 SLC (+)

Other Notifier Fire Alarm manuals

Notifier VGM NION UniNet 2000 User manual

Notifier

Notifier VGM NION UniNet 2000 User manual

Notifier NFS-3030/E Owner's manual

Notifier

Notifier NFS-3030/E Owner's manual

Notifier UZC-256 User manual

Notifier

Notifier UZC-256 User manual

Notifier ID50 SERIES Instruction Manual

Notifier

Notifier ID50 SERIES Instruction Manual

Notifier ID50 SERIES User manual

Notifier

Notifier ID50 SERIES User manual

Notifier ID50 SERIES Instruction sheet

Notifier

Notifier ID50 SERIES Instruction sheet

Notifier LCD-80F User manual

Notifier

Notifier LCD-80F User manual

Notifier ONYX Series User manual

Notifier

Notifier ONYX Series User manual

Notifier 002-439 Instruction Manual

Notifier

Notifier 002-439 Instruction Manual

Notifier NBG-12LOB User manual

Notifier

Notifier NBG-12LOB User manual

Notifier RP-1001 User manual

Notifier

Notifier RP-1001 User manual

Notifier AM2020 User manual

Notifier

Notifier AM2020 User manual

Notifier INERTIA-2464/64 User manual

Notifier

Notifier INERTIA-2464/64 User manual

Notifier 1010 User manual

Notifier

Notifier 1010 User manual

Notifier AFP-300 Owner's manual

Notifier

Notifier AFP-300 Owner's manual

Notifier AVL-1 Specification sheet

Notifier

Notifier AVL-1 Specification sheet

Notifier AFC-600 User manual

Notifier

Notifier AFC-600 User manual

Notifier UniNet 2000 Simplex 4010 NION User manual

Notifier

Notifier UniNet 2000 Simplex 4010 NION User manual

Notifier IFS-2600 Technical manual

Notifier

Notifier IFS-2600 Technical manual

Notifier NBG-12S User manual

Notifier

Notifier NBG-12S User manual

Notifier NBG-12LX User manual

Notifier

Notifier NBG-12LX User manual

Notifier UniNet 2000 AFP-300 NION User manual

Notifier

Notifier UniNet 2000 AFP-300 NION User manual

Notifier UZC-256 User manual

Notifier

Notifier UZC-256 User manual

Notifier NAM-232 User manual

Notifier

Notifier NAM-232 User manual

Popular Fire Alarm manuals by other brands

Cooper Notification RSSR-2415C installation instructions

Cooper Notification

Cooper Notification RSSR-2415C installation instructions

Shield D-A412 user manual

Shield

Shield D-A412 user manual

ESP MAGDUO quick start guide

ESP

ESP MAGDUO quick start guide

Zeta Alarm Systems 80-210 installation guide

Zeta Alarm Systems

Zeta Alarm Systems 80-210 installation guide

Interlogix ATS1521N Installation sheet

Interlogix

Interlogix ATS1521N Installation sheet

Zeta Alarm Systems Premier Quatro QT/4P User manual, maintenance guide & log book

Zeta Alarm Systems

Zeta Alarm Systems Premier Quatro QT/4P User manual, maintenance guide & log book

SharpEye 20 User and maintenance manual

SharpEye

SharpEye 20 User and maintenance manual

Evacuator Synergy Zone Leader quick start guide

Evacuator

Evacuator Synergy Zone Leader quick start guide

Fire-Lite BG-12SL Installation

Fire-Lite

Fire-Lite BG-12SL Installation

Fire-Lite LCD-80F manual

Fire-Lite

Fire-Lite LCD-80F manual

Brooks ALARM 2000 Site Manual

Brooks

Brooks ALARM 2000 Site Manual

FireClass Precept EN13 Installation & commissioning manual

FireClass

FireClass Precept EN13 Installation & commissioning manual

Keltron SDACT user manual

Keltron

Keltron SDACT user manual

Ampac SmartTerminal Installation, commissioning & operation

Ampac

Ampac SmartTerminal Installation, commissioning & operation

Honeywell Fire-Lite Alarms BG-12S manual

Honeywell

Honeywell Fire-Lite Alarms BG-12S manual

Faraday RND-2 installation instructions

Faraday

Faraday RND-2 installation instructions

Siemens FS720 Series Mounting & installation

Siemens

Siemens FS720 Series Mounting & installation

Ampac ACP-02 installation guide

Ampac

Ampac ACP-02 installation guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.