WHAT LEVELS OF CO CAUSE AN ALARM?
Und rwrit rs Laboratori s Inc. Standard UL2034 r quir s r sid ntial CO
Alarms to sound wh n xpos d to l v ls of CO and xposur tim s as
d scrib d b low. CO l v ls ar m asur d in parts p r million (ppm) of
CO ov r tim (in minut s).
UL2034 Required Alarm Points*:
• If th alarm is xpos d to 400 ppm of CO, IT MUST ALARM
BETWEEN 4 and 15 MINUTES
• If th alarm is xpos d to 150 ppm of CO, IT MUST ALARM
BETWEEN 10 and 50 MINUTES.
• If th alarm is xpos d to 70 ppm of CO, IT MUST ALARM
BETWEEN 60 and 240 MINUTES.
*Approximat ly 10% COHb xposur at l v ls of 10% to 95% R lativ
Humidity (RH).
Th unit is d sign d not to alarm wh n xpos d to a constant l v l
of 30 ppm for 30 days.
CO Alarms ar d sign d to alarm b for th r is an imm diat lif
thr at. Sinc you cannot s or sm ll CO, n v r assum it’s not pr s nt.
• An xposur to 100 ppm of CO for 20 minut s may not aff ct
av rag , h althy adults, but aft r 4 hours th sam l v l may
caus h adach s.
• An xposur to 400 ppm of CO may caus h adach s in av rag ,
h althy adults aft r 35 minut s, but can caus d ath aft r 2 hours.
This CO Alarm m asur s xposur to CO ov r tim . It alarms if CO
l v ls ar xtr m ly high in a short p riod of tim , or if CO l v ls r ach
a c rtain minimum ov r a long p riod of tim . Th CO Alarm g n rally
sounds an alarm b for th ons t of symptoms in av rag , h althy
adults.
This CO Alarm is intended or residential use. It is not intended or
use in industrial applications where Occupational Sa ety and Health
Administration (OSHA) requirements or carbon monoxide detectors
must be met.
CO alarms may not waken all individuals. If childr n or oth rs do not
r adily wak n to th sound of th CO alarm, or if th r ar infants or
family m mb rs with mobility limitations, mak sur that som on is
assign d to assist th m in th v nt of an m rg ncy.
CO Alarms will not work without power. This CO Alarm r quir s a
continuous supply of AC pow r. Plug into an unswitch d 120V AC outl t
only.
CO Alarms or Solar or Wind Energy users and battery backup
power systems: AC pow r d CO Alarms should only b op rat d with
tru or pur sin wav inv rt rs. Op rating this CO Alarm with most
batt ry-pow r d UPS (unint rruptibl pow r supply) products or squar
wav or “quasi sin wav ” inv rt rs will damage the Alarm. If you ar
not sur about your inv rt r or UPS typ , pl as consult with th manu-
factur r to v rify.
This CO Alarm will not sense carbon monoxide that does not reach
the sensor. This CO Alarm will only s ns CO at th s nsor. CO may b
pr s nt in oth r ar as. Doors or oth r obstructions may aff ct th rat
at which CO r ach s th CO Alarm. For this r ason, if b droom doors
ar usually clos d at night, w r comm nd you install a CO Alarm in
ach b droom and in th hallway b tw n th m.
CO Alarms may not sense CO on another level o the home. For
xampl , a CO Alarm on th s cond l v l, n ar th b drooms, may not
s ns CO in th bas m nt. For this r ason, on CO Alarm may not giv
ad quat warning. Compl t cov rag is r comm nd d. Plac CO
Alarms on ach l v l of th hom .
CO Alarms may not be heard. Th alarm horn loudn ss m ts or
xc ds curr nt UL standards of 85 dB at 10 f t (3 m t rs). How v r,
if th CO Alarm is install d outsid th b droom, it may not wak up a
sound sl p r or on who has r c ntly us d drugs or has b n drinking
alcoholic b v rag s. This is sp cially tru if th door is clos d or only
partly op n. Ev n p rsons who ar awak may not h ar th alarm horn
if th sound is block d by distanc or clos d doors. Nois from traffic,
st r o, radio, t l vision, air condition r, or oth r applianc s may also
pr v nt al rt p rsons from h aring th alarm horn. This CO Alarm is
not int nd d for p opl who ar h aring impair d.
CO Alarms are not a substitute or a smoke alarm. Although fir is a
sourc of carbon monoxid , this CO Alarm do s not s ns smok or
fir . This CO Alarm s ns s CO that may b scaping unnotic d from
malfunctioning furnac s, applianc s, or oth r sourc s. Early warning of
fir r quir s th installation of smok alarms.
CO Alarms are not a substitute or li e insurance. Though th s CO
Alarms warn against incr asing CO l v ls, BRK Brands, Inc. do s not
warrant or imply in any way that th y will prot ct liv s from CO poisoning.
Hom own rs and r nt rs must still insur th ir liv s.
CO Alarms have a limited li e. Although th CO Alarm and all of its
parts hav pass d many string nt t sts and ar d sign d to b as
r liabl as possibl , any of th s parts could fail at any tim . Th r for ,
you must t st your CO Alarm w kly.
CO Alarms are not oolproo . Lik all oth r l ctronic d vic s, CO
Alarms hav limitations. Th y can only d t ct CO that r ach s th ir
s nsors. Th y may not giv arly warning to rising CO l v ls if th CO
is coming from a r mot part of th hom , away from th CO Alarm.
TROUBLESHOOTING GUIDE
PROBLEM... THIS MEANS... YOU SHOULD...
R d light is OFF. Unit will not alarm wh n you
pr ss th T st/Sil nc button. CO Alarms may not b plugg d all th way in, or
is not r c iving pow r. G ntly push unit all th way into outl t. Mak
sur it is not plugg d into an outl t controll d by
a switch.
Th light flash s (RED) and th horn sounds 3
“chirps” v ry minut . MALFUNCTION SIGNAL. CO Alarm n ds to b
r plac d. Mak sur unit is plugg d in s cur ly.
CO Alarms und r warranty should b r turn d
to manufactur r for r plac m nt. S “Limit d
Warranty” for d tails.
CO Alarm go s back into alarm 4 minut s aft r
you pr ss th T st/Sil nc button. CO l v ls indicat a pot ntially dang rous
situation. IF YOU ARE FEELING SYMPTOMS OF CO
POISONING, EVACUATE your hom and call 911
or th Fir D partm nt. If not, pr ss th T st/
Sil nc button again and keep ventilating your
home.
CO Alarm sounds fr qu ntly v n though no high
l v ls of CO ar r v al d in an inv stigation. Th CO Alarm may b improp rly locat d.
R f r to “Wh r to Install CO Alarms.” R locat your Alarm. If fr qu nt alarms continu ,
hav hom r ch ck d for pot ntial CO probl ms.
You may b xp ri ncing an int rmitt nt CO
probl m.
Th light flash s (RED) and th horn sounds 5
“chirps” v ry minut . END OF LIFE SIGNAL. CO Alarm n ds to b
r plac d. Imm diat ly r plac th CO Alarm.
Why is this important? B caus you n d to b warn d of a pot ntial
CO probl m whil you can still r act in tim . In many r port d cas s of
CO xposur , victims may b awar that th y ar not f ling w ll, but
b com disori nt d and can no long r r act w ll nough to xit th
building or g t h lp. Also, young childr n and p ts may b th first
aff ct d. Th av rag h althy adult might not f l any symptoms wh n
th CO Alarm sounds. How v r, p opl with cardiac or r spiratory
probl ms, infants, unborn babi s, pr gnant moth rs, or ld rly p opl
can b mor quickly and s v r ly aff ct d by CO. If you xp ri nc
v n mild symptoms of CO poisoning, consult your doctor imm diat ly!
Standards: Und rwrit rs Laboratori s Inc. Singl and Multipl Station
carbon monoxid alarms UL2034.
According to Und rwrit rs Laboratori s Inc. UL2034, S ction 1-1.2:
“Carbon monoxid alarms cov r d by th s r quir m nts ar int nd d
to r spond to th pr s nc of carbon monoxid from sourc s such as,
but not limit d to, xhaust from int rnal-combustion ngin s, abnormal
op ration of fu l-fir d applianc s, and fir plac s. CO Alarms ar
int nd d to alarm at carbon monoxid l v ls b low thos that could
caus a loss of ability to r act to th dang rs of Carbon Monoxid
xposur .” This CO Alarm monitors th air at th Alarm, and is d sign d
to alarm b for CO l v ls b com lif thr at ning. This allows you
pr cious tim to l av th hous and corr ct th probl m. This is only
possibl if Alarms ar locat d, install d, and maintain d as d scrib d in
this manual.
Gas Detection at Typical Temperature and Humidity Ranges: Th
CO Alarm is not formulat d to d t ct CO l v ls b low 30 ppm typically.
UL t st d for fals alarm r sistanc to M than (500 ppm), Butan (300
ppm), H ptan (500 ppm), Ethyl Ac tat (200 ppm), Isopropyl Alcohol
(200 ppm) and Carbon Dioxid (5000 ppm). Valu s m asur gas and
vapor conc ntrations in parts p r million.
Audible Alarm: 85 dB minimum at 10 f t (3 m t rs).