FläktGroup ECO SIDE Manual

INSTALLATION AND MAINTENANCE MANUAL
ECO SIDE

eCO Side - Installation and Maintenance Manual
2
FläktGroup DC_10176GB_20180924_R3 Specifications are subject to alteration without notice
Page
1. SAFETY INSTRUCTIONS ................................................................................3
VDI 6022 ............................................................................................................3
2. DESCRIPTION OG THE UNIT..........................................................................4
3. TRANSPORT AND PLACEMENT ..................................................................5
4. CONNECTIONS
4.1 Duct connections.....................................................................................6
4.2 Post heater, electrical (9 kW).............................................................6
4.3 Post heater, hot water...........................................................................6
4.4 Cooling coil, water...................................................................................7
4.5 Valve and valve actuator......................................................................7
4.6 Damper........................................................................................................7
4.7 Silencer........................................................................................................7
5. ELECTRICAL CONNECTIONS
5.1 Fuse protection ........................................................................................8
5.2 Electrical data...........................................................................................8
5.3 Main supply...............................................................................................8
5.4 Connection of control panel................................................................9
6. CONNECTION OF EXTERNAL COMPONENTS
6.1 Electrical post heater (Size 06, 9 kW) .........................................10
6.2 Post heater, hot water.........................................................................10
6.3 Cooling coil, water................................................................................10
6.4 Cooling coil, DX......................................................................................10
6.5 Damper .....................................................................................................10
6.6 Temperature sensors...........................................................................11
6.7 Extended / Forced ventilation..........................................................11
6.8 Fire protection function .......................................................................11
6.9 Summary alarm .....................................................................................11
7. WIRING DIAGRAMS...............................................................................12
8. TESTING OF FUNCTIONS.......................................................................15
9. CONTROL PANEL, OPEERATIONS, COMMISSIONING
9.1 General.......................................................................................................16
9.2 Home screen overview ...................................................................... 17
9.3 Sub menus ..............................................................................................19
9.4 Date/time, language...........................................................................20
9.5 Advanced settings for installers and sevice personnel..........21
9.6 Commissioning Wizard.....................................................................22
9.7 Schedules................................................................................................26
Page
10. CONTROL FUNCTIONS
10.1 Rotor, heating and cooling .............................................................29
10.2 Temperature controls......................................................................29
10.3 Freeze protection...............................................................................31
10.4 Defrost function...................................................................................31
10.5 Cooling recovery................................................................................31
10.6 Night cooling........................................................................................31
10.7 Pressure or Constant flow control .......................................32
11. COMMUNICATION
11.1 Modbus, RS485...................................................................................33
11.2 Modbus, TCP/IP .................................................................................33
11.3 Webserver............................................................................................33
12. PARAMETER LIST ........................................................................................34
13. MAINTENANCE
13.1 General...................................................................................................40
13.2 Filter........................................................................................................40
13.3 Rotary Heat Exchanger...................................................................41
13.4 Post heater, hot water.....................................................................42
13.5 Post heater, electrical ....................................................................43
13.6 Cooling coil, water............................................................................ 43
13.7 Fans........................................................................................................ 44
13.8 Service schedule ..............................................................................45
14. DECLARATION OF CONFORMITY ............................................................46
15. DISPOSAL ....................................................................................................... 47
CONTENTS

eCO Side - Installation and Maintenance Manual
3
FläktGroup DC_10176GB_20180924_R3 Specifications are subject to alteration without notice
OPERATION OF AIR HANDLING UNITS
AND ACCESSORIES
WARNING
Before taking the air handling unit into
operation fit any unused connections with
protective mesh.
In addition, all electrotechnical and me-
chanical safety devices must be
installed before taking the air handling
unit into operation.
– Before opening the unit check that its power has been
disconnected.
– Take care when opening the isolating valves for the hot
water to the air heater. There is a risk of water hammer
or steam discharge.
– When servicing or inspecting the unit, turn off the
safety switch before opening the inspection doors.
Reset all safety devices before restarting.
– The clearance in front of electric heaters and electrical
cabinets shall conform to applicable electrical safety
regulations.
– Use the control panel to stop the unit.
– The unit’s hatches are fitted with locking handles.
Ensure that the unit is always left locked, and that the
keys cannot be accessed by unauthorized persons.
– Do not open inspection hatches when the unit is in
operation.
– Use protective gloves during installation and service.
1. SAFETY INSTRUCTIONS
Installation may only be
carried out by qualified personnel.
VDI 6022
eCO Side is designed in accord-
ance to hygiene standard VDI 6022
and is easy to clean with no place where dirt can accumulate.
Nonmetallic part, have been chosen as proven free of micro bac-
terial or mold growth.
Following the VDI 6022, AHU should ensure a physiologically
favourable indoor climate and a hygienically perfect indoor air
quality.
The eCO Side is designed in order, not to endanger health, not to
disturb the condition and the thermal comfort, not to lead to odour
nuisance and to prevent exposure and impact of inorganic and
organic pollutants.

eCO Side - Installation and Maintenance Manual
4
FläktGroup DC_10176GB_20180924_R3 Specifications are subject to alteration without notice
FANS
The unit has two plug fans with EC motors.
ROTARY HEAT EXCHANGER
The speed controlled rotor is fitted with a purge sector and a ro-
tation sensor.
CONTROL SYSTEM
The ISYteq Mini control system is integrated with the unit and is
ready for use with a large number of functions.
COMPONENTS
The unit can be supplied in left-hand or right-hand configurations.
Left-hand configurations is mirror-reversed to right-hand. Refer to
the order code in Technical Instruction.
2. DESCRIPTION OF THE UNIT
FILTER
Bag filter class (F7) ePM1 50% on both supply and extract air.
POST HEATER, HOT WATER
Hot water coil containing copper tubes and aluminum fins. Pipe
connection ø15 mm. Freeze protection temperature sensor is
included. Max operating pressure 3.0 MPa.
POST HEATER, ELECTRICAL
The heater for size 03 and 04 is built-in. For size 06 the heater is
duct mounted.
TOP RIGHT HAND CONFIGURATION RDSP, bb = 12 or 14 BOTTOM RIGHT-HAND CONFIGURATION RDSP, bb = 11 or 13
EXHAUST AIR UPWARDS RDSP, bb = 11 or 13 and c = 2
1 Outdoor air sensor GT3
2 Supply filter
3 Rotary heat exchanger with rotation sensor
4 Supply fan
5 Electrical heater including overheating
protection alternativelyhot water coil
with freeze protection GT5
6 Supply air sensor GT1
7 Extract air sensor GT12
8 Control equipment
9 Extract filter
10 Exhaust fan
11 Pressure guard
Outdoor air
Supply air
Extract air
Exhaust air
3 4 5 61 2
1011 8 79
64 85
3 79
10
1 211

eCO Side - Installation and Maintenance Manual
5
FläktGroup DC_10176GB_20180924_R3 Specifications are subject to alteration without notice
SOUND TRANSMISSION
When a unit is positioned next to a wall, low frequency sound can
generate vibrations in the wall, even if the sound level from the
unit is acceptable. Generally the unit should be positioned against
a wall adYescent to a room that is not sensitive for noise. When
this is not possible the unit should be positioned 400-500 mm
from the wall.
Duct lead-through must be designed with care so that rigid
connections between the duct and wall do not occur. In addition,
the seal around the duct must be carefully installed to prevent
the transmission of noise to adYescent areas. For sensitive in-
stallations it may be a good idea to connect ducts using flexible
connections.
If the floor structure is weak, noise can be transmitted to other
areas in the building. Use of a heavy insulating mat can prevent
that problem.
TRANSPORT
Use a fork lift truck, pallet truck or platform trolley for transport on
site. The unit can be lifted from the front or from the side.
To move size 06 through a 900 mm opening remove the door and
the center strut. See section 13.3.
3. TRANSPORT AND PLACEMENT
UNIT WEIGHT
Size 03 = 260 kg
Size 04 = 300 kg
Size 06 = 400 kg
SPACE REQUIREMENTS
Make sure that it is enough space around the unit for routine
service work, such as replacing filters and cleaning the fan and
casing.
Consideration has to be taken for future replacement of
components.
PLACEMENT
The unit can be placed directly onto the surface if this is flat and
horizontal, otherwise use adjustable feet.
Available as accessory RDTZ-13.
Size B1 S
03 1683 730
04 1782 780
06 1945 861
B1 = width with open doors
S = minimum space for service*)
* in front of the control cabinet there has to be enough space
according to local electrical regulations.
B1
S

eCO Side - Installation and Maintenance Manual
6
FläktGroup DC_10176GB_20180924_R3 Specifications are subject to alteration without notice
NOTE! The weight of the duct system
with components must not lay weight on the unit.
4. CONNECTIONS
4.1 DUCT CONNECTIONS
Size 03 (Ø250 mm) and 04 (Ø315 mm) have circular duct connec-
tions. Size 06 has rectangular duct connections (600 x 300 mm).
4.2 POST HEATER, ELECTRICAL
The electrical post heater for size 06 is duct mounted, see sepa-
rate instruction. The rectangular connection is PG on the unit and
the accessories. If the unit is selected with flange connection the
unit is delivered with an adapter for flange. This can be placed on
the unit or on the accessories. If the accessories are not placed
directly at the unit more adapters are available with the code
RDTZ-25-06-1.
4.3 POST HEATER, HOT WATER
Connect the pipes for the heating coil inside the unit according to
pictures below. View from gables.
NOTE! To avoid freezing the temperatures for frost
protection must not be set too low. If the building
has to be left unheated for long periods during
winter, the water must be drained from both the
pipework and the heating coil.
WARNING! Wear protective gloves
when using a fin comb.
Warning - hot water!!
FläktGroup takes no responsibility neither for
the connection of air heaters to the heating
system, nor for damage or injury caused by
incorrect planning, installation or maintenance
of this system. Pipework, valves etc. are to be
designed due to pressure drop and function, not
the dimensions of the air heater connections. The
weight of the pipe work system with components
must not lay weight on the water coil.
PIPE CONNECTION
Size 03 = 3/8”
Size 04 = 12 mm
Size 06 = 12 mm
Maximum operating pressure 3.0 MPa
PREVENTING FREEZING
There is a risk of freezing in the hot water coil at low outdoor
temperatures. This can cause water damage. The risk can
appear:
1. if the temperature of the water is too high. The risk increases
in spring and autumn. Adjust the water temperature in relation
to the outdoor air temperature.
2. if the post heater is oversized. Decrease the temperature of
the water to increase the water flow.
FINS
Any deformed fins can be adjusted using fin comb EQAZ-14.
VENTING
The air must be properly vented from the system to ensure good
function. The venting is made through the pipe system.
Supply air bottom, right-hand version Supply air bottom, left-hand version
Supply air top, right-hand version Supply air top, left-hand version
Ø22.5
Ø22.5
03=108
04= 93
06=111
03=108
04= 93
06=111
03=238
04=272
06=304
03=135
04=132
06= 93
03=238
04=272
06=304
03=135
04=132
06= 93
03=108
04= 93
06=111
Ø22.5
Ø22.5
03=108
04= 93
06=111
03=238
04=272
06=304
03=491
04=559
06=534
03=238
04=272
06=304
03=491
04=559
06=534

eCO Side - Installation and Maintenance Manual
7
FläktGroup DC_10176GB_20180924_R3 Specifications are subject to alteration without notice
When installing a 3-way valve check as follows:
Mixture from A/B to AB
Splitting from AB to A/B
4.6 DAMPER
Duct mounted damper with a spring return on/off actuator. The
actuator has to be connected to the terminal block in the electri-
cal cabinet. Size 03 and 04 have circular duct connections and
size 06 has rectangular. The damper is designed for duct insula-
tion of up to 50 mm.
4.7 SILENCER, DUCT MOUNTED
Size 03 and 04 have circular duct connections and size 06 has
rectangular. Fire resistance rating EI30. The distance to the fan
has to be at least 300 mm.
4. CONNECTIONS
4.4 COOLING COIL, WATER
The cooling coils have circular duct connections with rubber
ring seals. For size 06 a converter from rectangular to circular
is available as an accessory (RDTZ-24). The cooler has to be
installed horizontally and the distance to nearest bend has to be
at least 600 mm. Venting and draining is carried out via the pipe
system. The pipe connection, Ø 22 mm, is located on the outlet
end, is smooth and is intended for a compression fitting. The
drainage tray is in stainless steel and has an R 1/2” connection.
Maximum operating pressure 1.0 MPa and maximum operating
temperature 150° C.
4.5 VALVE AND VALVE ACTUATOR
ACTUATORS FOR HEATING SV1 AND COOLING SV2
Connected to terminal in electrical cabinet. Stroke length 5.5 mm.
Intended for assembly on 2-way and 3-way valves of the type
VVG44 or VXG44.
ACCEPTED INSTALLATION METHODS
VALVE FOR HEATING AND COOLING
The valve and valve actuator can be easily installed without
special tools. A particle filter should be fitted before the valve to
extend its service life.
2-WAY VALVE VVG
The flow is increased by turning the spindle inwards, the flow is
reduced by moving the spindle outwards. Note that the 2-way
valve cannot be used as a 3-way valve.
The flow direction is indicated by an arrow.
ACCEPTED INSTALLATION METHODS
3 -WAY VA LV E V X G
The bypass is closed by turning the spindle inwards, the bypass
is opened by turning the spindle outwards.
ACCEPTED INSTALLATION METHODS

eCO Side - Installation and Maintenance Manual
8
FläktGroup DC_10176GB_20180924_R3 Specifications are subject to alteration without notice
5. ELECTRICAL CONNECTIONS
5.3 MAIN SUPPLY
NY BILD!
5.1 FUSE PROTECTION
Size Unit with Hot water coil Electrical coil
03 Supply 1 x 230 V 3 x 400 V
Fuse 10 A 10 A
04 Supply 1 x 230 V 3 x 400 V
Fuse 10 A 16 A
06 Supply 1 x 230 V 1 x 230 V1)
Fuse 10 A 10 A
1) Duct mounted heater size 06 has sparate supply.
5.2 ELECTRICAL DATA
MOTORS
Size Power, kW Current, A
03 0,385 x 2 2,5 x 2
04 0,50 x 2 2,2 x 2
06 0,75 x 2 3,3 x 2
ELECTRICAL POST HEATER
Power, kW Current, A Voltage, V
410 2 x 400
615 2 x 400
91) 13 3 x 400
1) Duct mounted heater size 06 has sparate supply.
Units with built-in electrical heater, main supply 3 x 400V.
Units with hot water coil can be supplied with 1 x 230V.
Units with duct mounted electrical heater can be supplied with 1
x 230V.
Units are not available for 3 x 230V..
The main supply cable must be fitted with an external safety
switch located close to the unit. Connect main supply to terminals
U, V, W, N and PE in the control box.

eCO Side - Installation and Maintenance Manual
9
FläktGroup DC_10176GB_20180924_R3 Specifications are subject to alteration without notice
5. ELECTRICAL CONNECTIONS
1. Open the control panel using a screwdriver.
5.4 CONNECTION OF CONTROL PANEL
The control panel is connected when delivered from factory and
provided with a magnet for easy handling. For wall mounting see
below.
2. Lift the display out of the enclosure.
3. Push the connection cable through a suitable hole and if
needed make an outlet for the cable in the side of the cover.
4. Mount the enclosure directly on the wall.
5. Connect the cable to the back of the display as shown above.
Note. Please do not touch the electronics.
6. Push back the display in the enclosure.
NOTE! The control panel is only for indoor use.

eCO Side - Installation and Maintenance Manual
10
FläktGroup DC_10176GB_20180924_R3 Specifications are subject to alteration without notice
6.1 ELECTRICAL POST HEATER (SIZE 06, 9 KW)
Duct mounted. Separate supply 3 x 400V, 16 A.
Connect alarm, start and control signal to the control box in the
unit. eCO Side is preconfigured for electrical post heater.
(Electrical heater for size 03 and 04 is built-in in the unit, no
further connections are needed).
Component Terminal Connection Remark
Electrical
heater
9 kW
CP1/SK1
Heater
1 – 2
C- NO Start signal
ALM CP1 43 – 44
NO - C Alarm, overheating (NC)
SV1 CTRL 35 – 36
Y - M Control signal 0-10 V
Supply 3 x 400 V Not from the unit
6.2 POST HEATER, HOT WATER
Circulation pump (CP1) and valve actuator (SV1) connects
according to table below.
Component Terminal Connection Remark
Circulation
pump CP1
CP1/SK1
Heater 1 – N – PE Pump supply
(230 V max 2A1)
CP1/SK1
Heater
2 - 3
NO – L1
Loop only with
circulation pump
ALM CP1 43 – 44
NO - C
Voltfree alarm input
(NO, configurable)
Valve
actuator SV1 SV1 CTRL 35 – 36 – 37 - 38
Y – M – G – G0
1) The current consumption for CP1 and CP2 is limited to 2 A.
6. CONNECTION OF EXTERNAL COMPONENTS
6.3 COOLING COIL, WATER
Circulation pump (CP2) and valve actuator (SV2) connects
according to table below.
Component Terminal Connection Remark
Circulation
pump CP2
CP2/DX
Cooler 4 – N – PE Pump supply
(230 V max 2A1)
CP2/DX
Cooler
5 - 6
NO – L1
Loop only with
circulation pump
ALM CP2/
DX
45 – 46
NO - C
Voltfree alarm input
(NO, configurable)
Valve
actuator SV2 SV2 CTRL 39 – 40 – 41 - 42
Y – M – G – G0
1) The current consumption for CP1 and CP2 is limited to 2 A.
6.4 COOLING COIL, DX
The unit can manage cooling DX, 1-step. Note that the coil is not
included in the delivery of the unit. For configuration see control
functions.
Component Terminal Connection Remark
DX-cooling,
1-step
CP2/DX
Cooler
4 – 5
C – NO
Start: 10 %
Stop: 0 %
ALM CP2/DX 45 – 46
NO - C
Voltfree alarm input (NO,
configurable)
6.5 DAMPER
On/off actuator with spring return, 15 Nm, 24 VAC.
Component Terminal Connection Remark
Damper ST1 29 – 30
G – G0
Exhaust air damper if used
is connected in parallel
(Maximum 2 dampers)
Use the cable flange on the top of the unit to connect all external
accessories.
For information about how to connect available accessories see
below.

eCO Side - Installation and Maintenance Manual
11
FläktGroup DC_10176GB_20180924_R3 Specifications are subject to alteration without notice
6. CONNECTION OF EXTERNAL COMPONENTS
6.6 TEMPERATURE SENSORS
The unit is provided with:
Supply air sensor GT1, located at supply air spigot.
Outdoor air sensor GT3, located at outdoor air spigot.
Frost protection sensor GT5 (when hot water coil is used), located
on the return pipe of the coil.
When using cooling coil or duct mounted post heater a supply
temperature sensor (GT1) is supplied for duct mounting. Then
there is no supply air sensor mounted in the unit.
Room sensor GT2 (accessory) is supplied when the unit is con-
figured for room temperature control. Then there is no exhaust air
sensor mounted in the unit.
The room sensor is intended for wall mounting and needs to have
good air circulation and not direct sun light. Cable is not included.
Component Terminal Connection Remark
Supply air
sensor GT1 25 – 26
B – M
Standard sensor is replaced
with a duct mounted sensor
when using cooling coil or duct
mounted heater
Room
sensor GT2 27 – 28
B – M
Replaces exhaust air sensor
GT12 when room control is
selected
6.7 EXTENDED / FORCED VENTILATION
For external electronic timer, push button, PIR or other volt free
contact. Electronic timer and/or PIR if ordered is supplied
separately. When using a push button the time has to be set in
the control panel.
Component Terminal Connection Remark
Timer 1 TMR1 31 - 32
NO - C Can also be used for PIR
Timer 2 TMR2 33 – 34
NO - C Can also be used for PIR
Function of aux. inputs Timer 1 (T1) and Timer 2 (T2) can be
selected according to the following tables.
TIMER FUNCTION 1 (DEFAULT)
Timer 1 Timer 2
Manual/Automatic Mode 0 0
Trickle 1 0
Normal 0 1
Boost 1 1
TIMER FUNCTION 2
Timer 1 Timer 2
Manual/Automatic Mode 0 0
Trickle 1 0
Boost 0 1
Stop 1 1
TIMER FUNCTION 3
Timer 1 Timer 2
Manual/Automatic Mode 0 0
Normal 1 0
Boost 0 1
Stop 1 1
TIMER FUNCTION 4
Timer 1 Timer 2
Stop 0 0
Manual/Automatic Mode 1 0
Stop 0 1
Boost 1 1
TIMER FUNCTION 5
Timer 1 Timer 2
Stop 0 0
Manual/Automatic Mode 1 0
Stop 0 1
Normal 1 1
6.8 FIRE PROTECTION FUNCTION
External fire alarm to stop the unit can be connected to terminals
in the control box.
Smoke detectors and fire dampers cannot be connected directly
to the air handling unit, a separate fire system is needed.
Component Terminal Connection Remark
Fire protection
function FIRE 23 – 24
NC – C
6.9 SUMMARY ALARM
The alarm output can be configured to indicate A-alarms or both
A- and B-alarms.
Component Terminal Connection Remark
Summary
alarm ALARM 21 – 22
NO – C
Voltfree contact
Maximum load 24 V, 200 mA

eCO Side - Installation and Maintenance Manual
12
FläktGroup DC_10176GB_20180924_R3 Specifications are subject to alteration without notice
7. WIRING DIAGRAMS
Outside the AHU
Not in FläktGroup’s delivery
Outside the AHU
Not in FläktGroup’s delivery

eCO Side - Installation and Maintenance Manual
13
FläktGroup DC_10176GB_20180924_R3 Specifications are subject to alteration without notice
7. WIRING DIAGRAMS
Control panel
ISYteq Touch 3.5”
Control panel
ISYteq Touch 3.5”
Control board

eCO Side - Installation and Maintenance Manual
14
FläktGroup DC_10176GB_20180924_R3 Specifications are subject to alteration without notice
7. WIRING DIAGRAMS
EXTERNAL CONNECTIONS DIAGRAM
230/400 V
EXTERNAL CONNECTIONS DIAGRAM 24 V

eCO Side - Installation and Maintenance Manual
15
FläktGroup DC_10176GB_20180924_R3 Specifications are subject to alteration without notice
STARTING THE UNIT
When the electrical connections are made and all the accesso-
ries are mounted the unit is ready to start up.
1. Turn the safety switch to 1 (ON).
2. Start the unit.
DAMPERS
Check that all dampers opens and closes correctly.
VALVE ACTUATORS
Check that valve actuators for heating and cooling works correctly.
DIRECTION OF ROTATION
Check that the direction of rotation for the heat exchanger corre-
sponds to the alternatives below.
LEFT-HAND VERSION:
The rotor should rotate upwards when looking from the front.
RIGHT-HAND VERSION:
The rotor should rotate downwards when looking from the front.
AIR FLOW MEASUREMENT
The eCO Side has measuring nipples for air flow measurement.
Using a measuring pressure Dpm (Pa) and a constant (k) the air
flow q (R/W) can be calculated using the following equation:
NOTE! When the unit is supplied with
Constant Air Volume Control there will be
no measuring nipples on top of the unit.
TEMPERATURE CORRECTION
The air flow formula above applies to air with a temperature of
+20 °C. At other air temperatures the air flow must be corrected
using the formula:
The value of the constant (k) is shown in the table below.
q = 1000
k
Dp
m
x
Size 03 04 06
k-value extract air fan 58,4 51,5 49,2
k-value supply air fan 62,5 52,1 51,4
The measuring pressure, Dpm, is the difference between the
pressure in the empty section at the fan inlet and the pressure
inside the inlet cone. A manometer (RDTZ-56) can be connected
to view the measuring pressure. This is used as a reference for
monitoring the unit.
If the unit is supplied with Constant Air Volume control the air
flow can be read in the control panel.
q = q
20
(273 + t)
293
, m3
/s
8. TESTING OF FUNCTIONS
q = actual air flow
q
20
= calculated air flow in formula abowe
t = current temperature in ° C
FILTER, FINAL PRESSURE DROP
It is time to replace the filters when the final pressure drop is
reached, see table below.
SIZE 03
Air flow m3/s 0,15 0,25 0,35
Supply air/Extract air 119 148 177
SIZE 04
Air flow m3/s 0,15 0,25 0,35
Supply air/Extract air 125 142 159
SIZE 06
Air flow m3/s 0,15 0,25 0,35
Supply air/Extract air 121 139 157
FILTER MONITOR
When using filter monitors use the values in the table above. If
the unit is supplied with Constant Pressure control increase the
final pressure drop with 50 Pa.

eCO Side - Installation and Maintenance Manual
16
FläktGroup DC_10176GB_20180924_R3 Specifications are subject to alteration without notice
9. CONTROL PANEL, OPERATIONS, COMMISSIONING
9.1 GENERAL
HMI
This section provides an introduction to the touchscreen LCD
control panel, also known as the ‘Human Machine Interface’, or
simply, HMI.
The HMI serves two main purposes: To provide information about
the current operational state of the unit. To allow the unit to be
setup and configured.
TOUCH SCREEN TIPS
To select an item, touch the center of the icon or option. Do not
press too hard, the touch screen is sensitive enough to pick up
light, firm touches. Use the tip of your finger or the back of a
pencil to touch the required option. Be careful not to touch any
other options.
CLEANING THE SCREEN
Disconnect the power cord. Gently wipe the screen with a soft,
dry non-abrasive cloth. If the marks remain, moisten the cloth
slightly with a detergent that is designed for LCD or mobile
screens and wipe the screen gently from top to bottom. Never
use other detergents, as these may contain ammonia or other
additives.
IMPORTANT:
• Never spray, or pour liquids directly on to the screen.
• Do not clean the screen while the system is on.
CONVENTIONS USED WITHIN THIS MANUAL
The following buttons and symbols are universal and available on
many menu pages.
Home key, to return to the Home Screen.
Back button, to cancel and return to the previous
page.
Confirm button to confirm and proceed.
Changing a value:
Option 1: Press the arrow keys to increase or
decrease the value.
Option 2: Press the displayed number to
numerically adjust the value.
USING THE UNIT
POWERING ON
Each time power is applied, the unit will run through a series of
internal system tests which take approximately 20 seconds to
complete.
Once the internal system tests have been completed, the HMI will
always display the Home screen. The unit will be in Manual Mode
the first time that power is applied.
HOME SCREEN
From the Home screen it is possible to determine how the unit is
operating as well as navigating to further screens to configure the
unit to suit the demands of the end system.
From the Home Screen, it is possible to:
Navigate to further configuration screens to setup system param-
eters.
• Manually adjust the fan speed.
• Determine the operating status of the product.
• Interrogate and acknowledge system alarms.
Use the number buttons to enter
a value.
Confirm with or cancel with .
Values that can only be read, but not written,
are displayed without a surrounding window.
Values that can be both read and written,
are displayed with a surrounding window.
Some submenus has several
pages. Touch the upper or the
lower part of the scroll list to
navigate between pages.
14

eCO Side - Installation and Maintenance Manual
17
FläktGroup DC_10176GB_20180924_R3 Specifications are subject to alteration without notice
9. CONTROL PANEL, OPERATIONS, COMMISSIONING
OPERATING STATUS
ALARM
No alarm
Alarm B
Alarm A
Heat recovery active
Post-heater active
Defrosting in progress
Cooling active
Manual mode
Automatic mode
Constant pressure
Constant air volume
CO
2
Control
Timer 1
Timer 2
Timer 1/Timer 2
Stop
Shut down time
9.2 HOME SCREEN
STATUS LINE
CLOCKCURRENT SET
POINT VALUE
Trickle or low speed
Normal or medium speed
Boost or high speed
OPERATING MODES

eCO Side - Installation and Maintenance Manual
18
FläktGroup DC_10176GB_20180924_R3 Specifications are subject to alteration without notice
9. CONTROL PANEL, OPERATIONS, COMMISSIONING
9.2 HOME SCREEN, CONT.
STOP MANUAL AUTO-
MATIC
ALARM
See section 9.3..
SHORTCUT TO SET THE
TEMPERATURE SET POINT
USER SETTINGS
See section 9.3.
SHORTCUT TO SET THE TIME
AND DATE
SELECT OPERATING MODE
See section 9.3.
TRICKLE OR
LOW SPEED
NORMAL OR
MEDIUM SPEED
BOOST OR
HIGH SPEED
Press each field to select the operating mode.
Only active in Manual Mode.
SHORTCUT TO COMMISSIONING
WIZARD

eCO Side - Installation and Maintenance Manual
19
FläktGroup DC_10176GB_20180924_R3 Specifications are subject to alteration without notice
9. CONTROL PANEL, OPERATIONS, COMMISSIONING
9.3 SUB MENUS
OPERATING MODES
The operating status icon present on the Home Screen dis-
plays the current operating mode. To change the operating
mode, press the large fan icon located on the Home Screen.
The unit has three operating modes selectable through the
Operating Modes screen:
Stop Mode: In this mode, the unit will stop both the
supply and the extract fans.
Manual Mode: In this mode, the unit can be manually
adjusted on the Home Screen to run at three different
speeds.
Automatic Mode: In this mode, the unit will be automa-
tically controlled using internal schedules and timers,
CO
2
demand control, PIR sensors, etc.
ALARM SCREEN
The alarm icon on the Home Screen indicates the status of any
system alarms:
Alarm type B are deemed non-critical
and do not stop the unit ventilation.
Alarm type A are deemed critical and will
cause the unit to stop ventilating.
Press the icon to enter the Alarm Screen.
USER SETTINGS
TEMPERATURE STATUS
The temperature set point is used to determine when
the post-heater (if fitted) starts to warm the supply air
entering the property. The temperature set point can be
adjusted to any temperature between 15° C and 35° C,
factory setting is 19° C.
Temperatures and output signals are read only values.
FAN STATUS
From the Fan Status screen it will be possible to view
parameters such as supply and extract fan speeds, %,
off, pressures and flow rates.
AIR QUALITY
CO
2
value and CO
2
set point (if activated).
SYSTEM OVERVIEW
Version Control Panel IP Octet 1
Bootloader Control Panel IP Octet 2
Version Control Card IP Octet 3
Bootloader Control Card IP Octet 4
Unit type
SCHEDULES
Read only. For more information see section ”Schedules”,
section 9.7.
ADVANCED SETTINGS
See section ”Advanced settings”, section 9.4.
Example 1: No alarm Example 2: Active alarms
CLEARING ALARMS
To clear an individual alarm, press the Ack button. To clear all the
Alarms press the Ack All button on top of the screen.
It may not always be possible to clear the status of an alarm as the
source of the alarm may immediately trigger the status to return.
For example, it will not be possible to clear a faulty temperature
sensor alarm until the sensor itself has been repaired or replaced.
Alarm B
No alarm
Alarm A
ALARM HISTORY

eCO Side - Installation and Maintenance Manual
20
FläktGroup DC_10176GB_20180924_R3 Specifications are subject to alteration without notice
9.4 DATE AND TIME, LANGUAGE
9. CONTROL PANEL, OPERATIONS, COMMISSIONING
SETTINGS
To enter the settings menu:
1. Push the gear cog button.
2. Push the spanner button.
3. In this menu you set the date, time and language. It is also
possible for installers and service personnel to log in and
access additional parameters.
DATE/TIME
2 Set the time and press the Confirm button
1. Set the date and press the Confirm button.
CHOOSE LANGUAGE
1. Choose the appropriate language flag and press
the Confirm button.
Note, further language flags are available after pressing the right
arrow icon. Not all translations are available.
Table of contents
Other FläktGroup Fan manuals

FläktGroup
FläktGroup eCO Premium Manual

FläktGroup
FläktGroup EQAZ-04 User manual

FläktGroup
FläktGroup Roofmaster STEC Series Instruction Manual

FläktGroup
FläktGroup eQ PRIME Use and maintenance manual

FläktGroup
FläktGroup eQ PRIME Series Guide

FläktGroup
FläktGroup MultiMAXX HN11 User manual

FläktGroup
FläktGroup GMPM Instruction Manual

FläktGroup
FläktGroup HYPOWER-GEKO User manual

FläktGroup
FläktGroup CENTRIFLOW 3D PLUG FAN GMEC User manual

FläktGroup
FläktGroup VEKA ver C Instruction Manual