frako EM-PQ 2500 User manual

Power Quality Analyzer
EM-PQ 2500
Operating Manual
FRAKO Kondensatoren- und Anlagenbau GmbH •Tscheulinstraße 21a •79331 Teningen •Germany

2
Index of Contents
General 3
Goods-in Check 6
Description 8
Intended Use 8
Features 9
Measurement Method 10
EM-PQ VIS software 11
Assembly 12
Place of Installation 12
Installation extradata 12
Front Board Cutout 12
Ethernet Connection 13
Fixing 13
Installation 14
Supply Voltage 14
Voltage Measurement 16
Current measurement 22
RS485 26
Ethernet 30
Digital outputs 32
Digital Inputs 34
Operation 36
Measurement value displays 37
"Home“ measurement value display 38
Select measurement value display 39
Call up additional information 40
Delete min/max values individually 41
List of transients 42
List of events 43
Configuration 44
Language 45
Communication 46
Measurement 48
Transients 54
Events 56
Display 58
System settings 60
Password 61
Delete minimum and maximum values 62
Delete power meters 63
Extensions 66
Initialization 70
Applying the supply voltage 70
Apply measurement voltage 71
Rotary field direction 71
Applying measurement current 72
Checking the power measurement 74
Checking communication 75
Profibus 76
Service and Maintenance 80
Technical data 84
Dimensioned drawings 94
Configuration overview 96
Measurement value displays overview 98
Connection example 100

3
General
Copyright
This handbook is subject to the legal regulati-
ons of copyright law protection and may not be
mechanically or electronically photocopied or
reprinted in full in or parts and, without the legal,
written permission of
FRAKO
Kondensatoren- und Anlagenbau GmbH
Tscheulinstr. 21a
D - 79331 Teningen, Germany
may not be reproduced or further publication in
any other way.
Protected trademarks
All trademarks and the resulting rights belong to
the respective owners of the rights.
Disclaimer
FRAKO Kondensatoren- und Anlagenbau GmbH
does not accept any liability for errors or deficits
in this handbook and is not obliged to keep the
contents of this handbook updated.
Comments on the handbook
We welcome your comments. If anything in this
handbook seems unclear, please let us know
and send us an EMAIL to:
General

4
Meaning of Symbols
The following pictograms are used in this hand-
book:
Gefährliche Spannung!
Danger of death or risk of major injury.
Disconnect the system and device be-
fore beginning any work.
Protective ground connection.
Caution!
Please pay attention to the documenta-
tion. This symbol should warn against
possible dangers that can occur during
assembly, initialization and use.
m
c
Safety information
Inductive.
The voltage lags the current
Capacitive.
The voltage lags the current.
CNote.

5
Safety Information
Application Information
Please read this operating manual and all other
publications that have to be consulted to work
with this product (particularly for installation,
operation or maintenance).
Please pay attention to all safety regulations and
warning information. If you fail to follow the in-
formation, it can result in personal damage and/
or damages to the product.
Any unauthorized change or use of this device
beyond the specified mechanical, electrical or
other operating limits can cause personal da-
mage and/or damage to the product.
Any such unauthorized change represents "mi-
suse" and/or "negligence" in the sense of gua-
rantee for the product and therefore makes the
guarantee covering possible consequential da-
mages void.
This device is to be exclusively operated and
maintained by a specialist.
Specialists are persons who, due to their rele-
vant training and experience, are capable of re-
cognizing risks and avoiding possible hazards
that can be caused when operating or servicing
the device.
When using the device, the necessary legal and
safety regulations should be considered additio-
nally for the respective application case.
Caution!
If the device is not operated according
to the operating manual, protection is
no longer ensured and the device may
cause dangers.
c
Cables with single wires must be provi-
ded with ferrules.
Only screw plugs with the same pole
number and the same type of const-
ruction can be plugged together.
m
m

6
The operating manual also descri-
be options that do not belong to the
scope of supply.
Goods-in Check
Correct and safe operation of this device is
subject to appropriate transportation, correct
warehousing, installation and assembly as well
as careful operation and maintenance. If it can
be assumed that safe operation without any
danger is no longer possible, the device must
be taken out of operation immediately and se-
cured against unintentional initialization.
Unpacking and packing must take place, with
the usual care without applying force and using
suitable tools. The devices must be checked for
perfect condition with visual tests.
It should be assumed that risk-free operation is
not possible if, for example:
• There is visible damage,
• it no longer works due despite the main sup-
ply being intact,
• has been subject to unfavorable conditions
(e.g. storage outside of the authorized climate
limits without adaptation to the room climate,
thawing etc.) over a longer period of time or
transport stresses (e.g. a fall from a height, in-
cluding without any visisble external damage
etc).
• Please check the delivered items for comple-
teness before starting with the installation of
the device. All supplied options and design versi-
ons are described on the delivery note.
Goods-in Check
All screw clamps that belong to the
scope of supply are attached to the
device.
C
C
C

7
Goods-in Check
Name
Profibus plug, 9-pole DSUB, with integrated switchable terminating resistors.
Seal, 144x144.
Available accessories
Scope of Supply
Number Name
1 EM-PQ2500
1 Operating manual
1 CD with the following contents:
- Configuration and visualization software „EM-PQ VIS“
- Functional descriptions, EM-PQ VIS, EM-PQ2500 ..
- GSD file „U5080C2C.GSD“ for Profibus DP V0
1 Screw clamp, pluggable, 2-pole (auxiliary power).
1 Screw clamp, pluggable, 5-pole (voltage measurement 1-4).
1 Screw clamp, pluggable, 8-pole (current measurement 1-4).
1 Screw clamp, pluggable, 6-pole (digital outputs).
1 Screw clamp, pluggable, 5-pole (digital inputs).
1 3m patch cable, blue (Connection EM-PQ2500 - switch/hub).
1 2m patch cable, twisted (connection EM-PQ2500 - PC).
1 fixing clips.

8
Description
Description
Intended Use
The EM-PQ2500 is intended for measurements
in the building installation, on distributors, pow-
er switches and bus bars.
Measurement voltages and measurement cur-
rents must come from the same network.
The EM-PQ2500 is suitable for installation in
switch boards with a fixed, weather-protected
extradata.
The EM-PQ2500 can be used in 2, 3 and 4 sup-
ply networks and in TN and TT networks.
The current measurement inputs of the EM-
PQ2500 are connected using external ../1A or
../5A current transformers.
The measurement in medium and high-voltage
networks generally takes place using current
and voltage transformers.
The EM-PQ2500 can be used in residential and
industrial areas.
Measurement results can be displayed, saved
and read-out using serial interfaces for further
processing.

9
Description
Features
• Front board installation, 144x144mm,
• Working temperature range -10°C .. +55°C,
• Colour graphic display 320x240, 256 colours, 6 keys,
• 8 digital inputs, 5 digital outputs,
• 16Bit A/transformer, data memory 256MByte Flash, SDRAM 32Mbyte,
• Continuous scanning of voltage and current measurement inputs with 20kHz,
• Frequency range of fundamental oscillation 40Hz .. 70Hz
• 4 voltage measurement inputs, 4 current measurement inputs,
• Measurement in TN and TT networks,
• RS485: Profibus DP/V0, Modbus RTU, Modbus-Master,
• Ethernet: Web-Server, EMAIL, BACnet (Option),TCP/IP, EMAIL (SMTP), DHCP-Client (BootP),
Modbus/TCP, Modbus RTU over Ethernet, FTP, ICMP (Ping), NTP, TFTP, SNMP.
• Detection of transients >50µs and storage with up to 16000 scanning points,
• Detection of more than 800 measurement values,
• Measurement of harmonics 1 to 40, for
- Uln, I, P (ref/supply) and
- Q (ind/cap),
• Programming own applications in Jasic.

10
Description
Measurement Method
The EM-PQ2500 measures without any gaps
and calculates all effective values over a 200ms
Interval.
The EM-PQ2500 measures the real effective va-
lue (TRMS) of the voltages and currents applied
to the measurement inputs.
Operating Concept
You can program the EM-PQ2500 in several
ways and call up measurement values.
• Direct- on the device using 6 keys and the
display.
• Using the configuration and visualization soft-
ware EM-PQ VIS.
• Using the EM-PQ2500 homepagefor devices
with an Ethernet interface.
• Using the RS485 with the Modbus-protocol.
You can change and call up data with the help
of the Modbus address list (stored on the en-
closed data carrier).
Only operating the EM-PQ2500 using the integ-
rated display and the 6 keys is described in this
operating manual.
The EM-PQ VIS configuration and visualization
software and the homepage have their own "on-
line assistance“.

11
EM-PQ VIS configuration and
visualization software
The EM-PQ2500 can be programmed and read-
out with the EM-PQ VIS configuration and vi-
sualization software included in the scope of
supply. A PC must be connected using a serial
interface (RS485/Ethernet) to the EM-PQ2500.
EM-PQ VIS features
• Programming the EM-PQ2500.
• Configuration of recordings.
• Recordings read-out.
• Saving data in a database.
• Graphic presentation of measurement values.
• Programming specific applications for the cli-
ent.
Description
PC EM-
PQ2500
Ethernet
Illu. Connection of a EM-PQ2500 to a PC using
an interface converter.
PC
EM-
PQ2500
RS232
RS485
Interface
Converter
Illu. Connection of a EM-PQ2500 to a PC using
Ethernet.

12
Assembly
Assembly
Place of Installation
The EM-PQ2500 is suitable for installation in
fixed, weather protected switch boards. Con-
ducting switch boards have to be grounded.
Installation extradata
In order to achieve sufficient ventilation, the EM-
PQ2500 has to be installed vertically. The clea-
rance has to be at least 50mm at the top and
bottom and 20mm at the side.
Front Board Cutout
Cutout size: 138+0.8 x 138+0.8 mm
Failure to maintain the minimum clea-
rances can destroy the EM-PQ2500 at
high environmental temperatures!
Illu. EM-PQ2500 installation extradata; view
from back.
m
EM-PQ2500

13
Assembly
Ethernet Connection
Patch Cable
Ethernet Connection
The EM-PQ2500's Ethernet connection is loca-
ted on the underside of the housing.
Depending on the bending radius of the Ether-
net cable and plug type, you must provide a
connection area beneath the EM-PQ2500.
The connection area beneath the EM-PQ2500
should not be less than 50 mm.
50 mm
Fixing
The EM-PQ2500 is fixed into the switch board
with two fixing clips that are each mounted on
the device at the top and bottom.
Fixing Clips

14
Installation
Installation
Protective Wire Connection
Use a ring cable lug for connecting the protecti-
ve wire to the EM-PQ2500.
Supply Voltage
A supply voltage is required to operate the EM-
PQ2500. The type and level of the necessary
supply voltage is noted on the label.
Before applying the supply voltage, make sure
that the voltage and the frequency match the
details on the label!
The connection cables for the supply voltage
must be connected using a fuse. Use a UL/IEC
listed fuse (6A type C).
Illu. Connection example; connection of supply
voltage to a EM-PQ2500.
Separator
Fuse
L1 N PEL3L2
Protective wire
cWarning - danger of death!
It is necessary for the protective wire
connection on the device to be con-
nected with the system grounding.
Connection point for
protective wire

15
- An isolator or circuit breaker must be
provided for the voltage supply in buil-
ding installation.
- The isolator must be attached near
to the device and must be easy for the
user to access.
- The switch must be marked as a se-
parator for this device.
-Voltages above the authorized voltage
range can destroy the device.
m
Warning!
The inputs for the supply voltage are
dangerous to touch!
c
Installation
Warning!
Please pay attention to the details on
the supply voltage provided on the
EM-PQ2500 label.
c

16
Installation
Illu. Basic circuit diagram, EM-PQ2500 in theTN-
network.
Voltage Measurement
Three-phase 4 conductor systems
The EM-PQ2500 can be used in three-phase
4 conductor systems (TN, TT network) with a
grounded neutral wire. The bodies of the elec-
trical system are grounded.
Three-phase 3 conductor systems
The EM-PQ2500 is only suitable for use in IT
networks with restrictions, because the measu-
rement voltage is measured against the housing
potential and the input impedance of the device
causes a leakage current against ground. The
leakage current can cause isolation monitoring
in IT networks to respond.
Connection variations with a voltage transfor-
mer are suitable for IT networks without any re-
strictions.
Illu. Basic circuit diagram, EM-PQ2500 in the IT
network without N.
System
grounding
DC
AC/DC
PE
347V/600V 50/60Hz
L2
L3
N
L1
Auxiliary power
Voltage measurement
4M
4M
4M
4M
V1 V3V2 Vref
4M
V4
EM-PQ2500
600V 50/60Hz
DC
AC/DC
L2
L3
Auxiliary power
Voltage measurement
4M
4M
4M
4M
V1 V3V2
4M
V4
System
grounding
Impedance
L1
EM-PQ2500
Vref

17
Installation
Maximum nominal voltage of
the network according to UL
Maximum nominal voltage
of the network
UL-N / UL-L
66V / 115V
120V / 208V
127V / 220V
220V / 380V
230V / 400V
240V / 415V
260V / 440V
277V / 480V
347V / 600V
400V / 690V
417V / 720V
Illu. Table of suitable network nominal voltages
for the voltage measurement inputs according
to EN60664-1:2003.
Illu. Table of suitable network nominal voltages
for the voltage measurement inputs according
to EN60664-1:2003.
Ungrounded three-phase 3 conductor
systems.
Three-phase 4 conductor systems with
grounded neutral wire.
Nominal Voltages
Lists of the networks and their nominal network
voltages in which the EM-PQ2500 can be used.
UL-L
66V
115V
120V
127V
200V
220V
230V
240V
260V
277V
347V
380V
400V
415V
440V
480V
500V
577V
600V Maximum nominal voltage of
the network

18
Installation
Voltage Measurement Inputs
The EM-PQ2500 has 4 voltage measurement
inputs (V1, V2, V3, V4).
Overvoltage
The voltage measurement inputs are suitable for
measurements in networks in which overvolta-
ges in the overvoltage category 600V CATIII can
occur.
Frequency
The EM-PQ2500 requires the rated frequency
for measuring and calculating measurement va-
lues.
The EM-PQ2500 is suitable for measurements
in networks with a rated frequency in the range
of 40Hz to 70Hz.
Illu. Connection example for voltage measure-
ment.
A connection diagram does not have
to be configured for the measurement
inputs V4 and I4.
C
L1 N PEL3L2
10A
(UL/IEC listed)

19
Installation
The following has to be considered when con-
necting the voltage measurement:
• A suitable separator is to be provided in order
to disconnect the EM-PQ2500 from the cur-
rent and voltage.
• The separator must be placed near to the
EM-PQ2500, labelled for the user and must
be easy to reach.
• Use UL/IEC authorized overcurrent protection
and isolators (10A type C) only.
• The overcurrent protection device must have
a nominal value calculated for the short-cir-
cuit current at the connection point.
• Measurement voltages and measurement
currents must come from the same network.
Warning!
The voltage measurement inputs on the
EM-PQ2500 are dangerous to touch!
c
Warning!
The EM-PQ2500 is not suitable for
measuring DC voltages.
Warning!
Voltages that exceed the authorized
network nominal voltages must be
connected using a voltage converter.
c
Warning!
The voltage measurement inputs may
not be used for voltage measurement
in SELV circuits (Safety Extra Low Vol-
tage).
c
c

20
Installation
Connection diagrams, voltage measurement
Table of contents
Other frako Measuring Instrument manuals
Popular Measuring Instrument manuals by other brands

Wicked lasers
Wicked lasers S3 Krypton Series Users manual and laser safety guide

FRC
FRC FPA400 instruction manual

Yamaha
Yamaha MB1000 owner's manual

Emerson
Emerson Micro Motion 1700 Configuration and Use Manual

Dostmann Electronic
Dostmann Electronic DewPoint Pro H560 Operating instruction

SATO KEIRYOKI
SATO KEIRYOKI 7720-00 instruction manual

Awex
Awex WZ 4 Assembly instructions

VIDA TECH
VIDA TECH F7012 installation manual

Reed Instruments
Reed Instruments SMART Series instruction manual

Airmar Technology Corporation
Airmar Technology Corporation UDST800 Owner's guide & installation instructions

Feasa
Feasa 20-F user manual

promesstec
promesstec UDA 50-U Series user manual